background image

Chimney

 

The chimney is the driving force which makes the stove function. In order for the stove to 
perform satisfactorily the chimney height must be sufficient to ensure the correct draught 
of 14 to 18 Pa, so as to clear the products of combustion and prevent problems of smoke 
leaking into the room when the stove is lit. 
Note: A chimney height of not less than 4.5 metres, measured vertically from the outlet of 
the stove to the top of the chimney, should be satisfactory. 
Alternatively the calculation procedure given in BS 5854:1980 may be used as the basis 
for deciding whether a particular chimney design will provide sufficient draught. 
Please Note, this appliance has been tested by the manufacturers and works on a 3m 
straight flue. 

The outlet from the chimney should be above the roof of the building in accordance with 
the provisions of the Building Regulations Approved Document J. 

If the installation is into an existing chimney, then it must be sound and have no cracks or 
other faults which may allow fumes into the house. Older properties, especially, may have 
chimney faults or the cross section may be too large i.e. more than 230 x 230mm. 
Remedial action should be taken if required, expert advice should be sought where 
required. 
If the chimney requires lining, then a suitable solid fuel flue liner must be used, in 
accordance with Building Regulations Approved Document J. 

Any existing chimney must be clear of obstruction and should have been swept clean 
immediately before the installation of the stove. If the stove is fitted in place of an open 
fire, then the chimney should be swept one month after installation to clear any soot falls 
which may have occurred due to the difference in combustion between the stove and the 
open fire. 

If there is no existing chimney then either a prefabricated block chimney, in accordance 
with Building Regulations Approved Document J or a twin wall insulated stainless steel 
flue to BS 4543 can be used. These chimneys must be fitted in accordance with the 
manufacturer’s instructions and the Building Regulations. 

A single wall metal fluepipe is suitable for connecting the stove to the chimney but is 
not suitable for using for the complete chimney. The chimney and 
connecting fluepipe must have a minimum diameter of 150mm and it’s 
dimension should be not less than the size of the outlet socket of the stove which is 
150mm. Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° 
bends should not be used. 

Combustible material should not be located where the heat dissipating through the 
walls of fireplaces or flues could ignite it. Therefore when installing the stove in the 
presence of combustible materials due account must be taken of the guidance on the 
separation of combustible material given in Building Regulations Approved Document 
J and also in these stove instructions.

Summary of Contents for RAIS Q-BIC

Page 1: ...NT INFORMATION On first lighting the stove you must be careful not to touch the painted surfaces and it is MOST IMPORTANT that the door is kept slightly ajar in order for the door seal and sealant to...

Page 2: ......

Page 3: ...ER INSTALLATION 45 22 360 SWIVEL BASE 22 FOR THE INSTALLER 23 OPERATING INSTRUCTIONS 24 FUEL 24 DRYING AND STORAGE 25 REGULATION OF COMBUSTION AIR 25 USING THE WOOD BURNING STOVE 26 ADJUSTMENT OF AIR...

Page 4: ...n number We therefore recommend that you note down the number in the table below The production number is located at the back of the stove at the bottom Warranty Your Rais wood burning stove comes wit...

Page 5: ...gs of wood approx 25cm 1 6 1 6 Min uptake Min draught Pascal 12 12 Weight kg 143 153 Smoke gas mass flow g s 6 3 6 3 Smoke gas temperature C 253 253 Intermittent operation Fuelling should be undertake...

Page 6: ...e cold air is sucked in at the base of the stove and up through the convection channel which runs along the stove s combustion chamber The heated air comes out at the top of the stove which ensures a...

Page 7: ...s heating appliance is governed by the Health and Safety at Work Act 1974 it is the responsibility of the installer to ensure that all requirements of this Act are met during the installation works At...

Page 8: ...accordance with Building Regulations Approved Document J Any existing chimney must be clear of obstruction and should have been swept clean immediately before the installation of the stove If the sto...

Page 9: ...ssible soot door or doors must be provided for sweeping the chimney and connecting fluepipe You should also familiarise yourself with the draught conditions for chimneys with 2 flues For strong draugh...

Page 10: ...egulations Approved Document J gives specific guidance on the required permanent ventilation into the room for combustion air of solid fuel appliances The floor structure must be able to carry the wei...

Page 11: ......

Page 12: ...rner both door side DO NOT UNSCREW ENTIRELY Now it is possible to remove the stove body from the cassette Preparation of the cassette Remove the two screws keeping the stiffening rib in position For a...

Page 13: ...oken off before it is assembled with the two self tapping screws The top plate is not used N B A 30 degree bend must always be used for a brick wall The legs are fixed onto the box and then the box ca...

Page 14: ...ORTANT Using a spirit level ensure that the stove is perfectly level both horizontally and vertically Fixing hole for solid wall installation Fixing holes for the angle brace for a stud wall installat...

Page 15: ...picture on the left Note The basic settings on the adjusting bolts are approximately 32 5mm between the bottom of the stove s base plate and the base plate on the internal box Please note adjustment...

Page 16: ...Push the stove body in until the front is level with the wall on both sides Re tighten the screws in the upper left and lower left corners...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...a non combustible hearth of a size and construction that is in accordance with the provisions of the current UK Building Regulations Approved Document J If the stove is to be installed on a wooden fl...

Page 21: ...Q Bic...

Page 22: ......

Page 23: ...to the chimney Ensure that the appliance and chimney flue are functioning correctly before finally handing over to the user Read the later parts of this manual for guidance on care required when first...

Page 24: ...wood wood with a synthetic surface painted refuse wood chipboard plywood domestic waste paper bri quettes and pit coal as this will produce malodorous smoke which could be poisonous When firing with...

Page 25: ...is added in the gas combustion zone i e air which contributes to the combustion of the pyrolysis gasses preheated air which is used for the cleaner glass system and combustion This air is sucked thro...

Page 26: ...ration Using the wood burning stove Adjustment of the air damper the damper has 3 settings Rais Q Bic Position 1 The damper closed which means no air supply Position 2 Push the handle to the left to t...

Page 27: ...which means no air supply Position 2 Push the handle to the left to the first mark This position gives full secondary air During normal use the lever is set between position 1 and 2 When the flames a...

Page 28: ...ot when in use always wear protective gloves when tending the stove If the stove has not been used for a while follow the steps as if you were using it for the first time IMPORTANT Warning Note Proper...

Page 29: ...ighting the stove Tips before firing up Open a door or window close to the wood burning stove If there is storm in the stove coming from the chimney it is advisable to place a screwed up piece of news...

Page 30: ...bers add 2 3 pieces of wood Leave the door ajar until the fire has caught properly then close the door Damper see adjustment of the damper After approximately 5 minutes or when the flames are clear an...

Page 31: ...ovel the ash out and store it in a non flammable container until it has cooled down You can dispose of ash with your normal household waste or recycle on the garden REMEMBER Never remove all the ashes...

Page 32: ...arked by a circle in the next picture The baffle plate is pulled forwards and then tipped down towards the firebox Note the skamol on the sides are now loose The smoke connector is located above the b...

Page 33: ...2 Pa draught control regulator should be installed A stove burning too weakly could be caused by too little firewood too little air supply for the room ventilation dirty smoke channels leaking chimney...

Page 34: ...agrams for the individual products Position Number Item Number Description 1 1 706060290 95 Top plate 2 1 706010490 95 Steel back panel 3 1 706010590 95 Fixed window 4 1 706010190 95 Steel side panel...

Page 35: ......

Page 36: ...panel 3 1 706010590 95 Fixed window 4 1 706010190 95 Steel side panel 5 1 7061090 95 Door 6 1 7060905SV Air control handle 7 1 7061301 Smoke connector 8 1 7062200 Set of skamol stones 9 1 7060590 95 F...

Page 37: ......

Page 38: ...d window 3 1 7061090 95 Door 4 1 7060905SV Air control handle 5 1 7061301 Smoke connector 6 1 7062200 Set of skamol stones 7 1 7071301SV Complete smoke connector 45 adaptor 8 1 0006504 Complete smoke...

Page 39: ......

Page 40: ...U K Distributor Robeys Ltd Riverside Goods Road Belper Derbyshire England DE56 1UU Tel 01773 820940 Fax 01773 820477 E Mail info robeys co uk www robeys co uk June 2011...

Reviews: