Pro Max System Troubleshooting
Symptom Action
Max-UA) -
Check the valve solenoid and replace if
necessary.
-
Check the station wiring for short circuit
to common, check for insulation nicks
and exposed wiring in standing water.
-
When field problem is fixed, turn station
back ON.
-
Cycle Pro Max receiver power to reset the
unit.
Note
: The Pro Max system will continue to
operate normally for non-shorted stations.
Keys beep at Pro Max
transmitter but no valves
turn on at a non Rain
Master controller. (Model
Pro Max-UA)
•
Check installation, and antenna connections
(see Section 3.2, Figure 8 and Figure 9)
•
Remove the large 37-pin connector from the
universal adapter assembly and then re-insert.
•
Upon re-insertion of the cable listen for the
Pro Max receiver tone(s).
-
No tone – check the 24 Volts AC and
common connections.
-
One tone, OK (approximately 1/2
second)
-
Two tones, OK (see Section 4.6 Access
Code)
-
Any other tones (contact factory)
•
Press the AUTO UP key and listen for a
confirmation beep at the Pro Max receiver. If
no beep contact factory.
•
Verify water is ON at the selected stations. If
no water is available, is a Master Valve/Pump
required? Verify field station wiring is correct.
•
Confirm that the remote continues to work at
maximum distance. If not, contact factory.