Advanced Setup
Configuring Digital I/O
The PT5002 has remote reset capabilities for relays and totalizers through any one
of six channels�
All six channels are input-only and can be configured for any combination of
the following�
Option
Description
DISABLED
The I/O channel will have no function
RESET: RELAY 1
Resets latch on Relay 1
RESET: RELAY 2
Resets latch on Relay 2
RESET: RELAY 1 AND RELAY 2
Resets latches on Relays 1 and 2
RESET: FLOW TOTAL
Resets
Flow Total
RESET: RELAY 1 AND FLOW TOTAL
Resets latch on Relay 1 and resets
Flow Total
RESET: RELAY 2 AND FLOW TOTAL
Resets latch on Relay 2 and resets
Flow Total
RESET: ALL RELAYS AND ALL TOTALS
Resets Relay 1, Relay 2 and
Flow Total
Table 19: Channel options
Figure 18: Digital I/O menu
1� Navigate to
SETUP > ADVANCED SETUP > DIGITAL I/O
�
2� Press UP/DOWN to scroll to any of the six input channels�
3� Press ENTER repeatedly until the desired function appears� Each time ENTER is
pressed, the channel toggles through the available functions�
To disable any channel, simply highlight the digital I/O channel, and press ENTER
until
DISABLED
appears�