Rain Bird IC System Design Manual Download Page 16

 

16 

IC System

TM

 Design Guide, v2.3 

 

Grounding 

Proper grounding is very important for the IC system

TM

.  The system grounding is accomplished through 

the ICSD surge devices that are installed on the wire path. Rain Bird MSP surge devices are installed on 

each wire path prior to entering the Integrated Control Interface (ICI) at the central. 

Important!

  

An  Integrated  Control  Surge  Device  “ICSD”  should  be  located  every  15  ICMs  or  every  500  feet  (150 

meters),  whichever  condition  is  reached  first.    This  is  a  guideline  for  design  purposes  and  designers 

should  try  to  stay  as  close  to  these  guidelines  as  possible.  However  in  the  example  of  a  herringbone 

system with 4 stations per pipe lateral, an ICSD could be installed every fourth lateral (therefore every 

16

th

 station) as a normal design practice.  

The  purpose  of  field  surge  devices  is  to  offer  “containment”  of  surge  during  an  event  so  that  damage 

caused by the event will be limited by an ICSD located on either side of the event. The key for successful 

containment is proper installation of ground rods or plates so that the desired Ohms resistance level is 

achieved. 

During long runs of wire where there are no ICMs, an ICSD is not required every 500 feet (150 meters). 

For example, if there is a wire length run of 2,000 feet (609 meters) between ICMs, an ISCD should be 

installed  immediately  after  the  last  ICM  and  just  prior  to  the  next  ICM.  ICSDs  are  not  required  at  500 

foot (150 meter) intervals on the 2,000 foot (609 meter) run of wire.  

At  the  ICI,  for  a  long  run  (greater  than  500  feet or  150 meters)  at  the  beginning  of  the  wire  path, the 

MSP should be installed at the interface and an ICSD installed just prior to the first ICM on the wire path. 

 

Grounding Requirements - Field 

The  IC  System  must  have  grounding  throughout  the  wire  path  to  allow  any  transient  surges  the 

opportunity  to  leave  the wire  path.    The  following  requirements must  be  followed  to  properly  ground 

the IC System: 

1.

 

Each ICSD must have an earth ground resistance of less than 50 ohms and be no more than 500 

feet (150 meters) from the next ICSD. 

2.

 

Each ICSD can be located either next to a valve-in-head rotor or in-line valve.  The ICSD should 

be accessible in case of maintenance.  Either a ground rod or plate can be utilized to obtain an 

earth ground reading of 50 ohms or less. 

3.

 

The grounding requirement at the central control is to have less than 10 ohms of earth ground 

resistance.  5  ohms  or  less  of  ground  resistance  is  preferable.  The  central  control  shall  utilize 

Summary of Contents for IC System

Page 1: ...IC SystemTM Design Guide v 2 3 Updated August 2016...

Page 2: ...of the IC Interface ICI 6 Uninterruptable Power Supply UPS 7 How the System Works 8 Basic Design Data 9 System Capacity 10 Flexible Design 10 Wire Path 11 Wire Sizing Charts 12 Examples 13 15 Groundin...

Page 3: ...the proper design for the specific application IC System Product Definitions Central Control Software CirrusTM Nimbus IITM Stratus IITM and Stratus LTTM are the Central Control applications that are a...

Page 4: ...nterface ICI is the electronic hardware and firmware that accepts commands from the Central Control Software and directs them to the field The ICI also communicates intelligently with the field in ord...

Page 5: ...ware via Rain Bird MAXITM cable two wire path and the ICI interface The central control software automatically operates the rotors and valves throughout the golf course by activating each individual I...

Page 6: ...PU Board The CPU Board provides communication between the Central Control Computer and each of the wire paths Driver Board The Driver Board provides communication between the CPU board and the ICMs in...

Page 7: ...r the IC System Different countries may have differing requirements and APC typically makes a Smart UPS for each country according to the needs of that country If sourcing a Smart UPS for a different...

Page 8: ...ed Long Address The user must enter the Long Address into the central control software at initial start up The central control software communicates with the ICMs in the field through a high speed met...

Page 9: ...has a maximum capacity of two 2 wire path inputs 4 A single Driver Board has a maximum capacity of 1 500 stations when both wire paths are used 5 The ICI has a maximum capacity of 3 000 stations when...

Page 10: ...h 12 ICIs Standard configuration is number of stations and ICIs available in the software without purchasing a Hybrid Software Module ICIs are purchased separately as needed and are not included with...

Page 11: ...provide the proper guidelines for wire sizing on the wire path The most important calculation is that of the primary Trunk wire length on each wire path The Trunk wire length is considered to be the l...

Page 12: ...2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 100 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 150 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm 2 2 5mm...

Page 13: ...l be up to 10 000 feet 3 000 meters Utilizing the sizing chart the Trunk wire should use 14 AWG 2 5 mm2 MAXITM wire for the installation Although there are multiple branches off of the main Trunk wire...

Page 14: ...rt the Trunk wire should be designed using 12 AWG 4 0 mm2 wire NOTE 12 AWG 4 0 mm2 wire will be used for the Trunk wire only 14 AWG 2 5 mm2 wire can be used for all branch lines as long as each branch...

Page 15: ...MAXITM wire for the installation As the initial 3 500 feet 1 067 meters is greater than 2 500 feet it requires an increase in wire size to 12 AWG 4 0mm2 The initial 3 500 feet 1 067 meters of Trunk wi...

Page 16: ...there are no ICMs an ICSD is not required every 500 feet 150 meters For example if there is a wire length run of 2 000 feet 609 meters between ICMs an ISCD should be installed immediately after the l...

Page 17: ...vide a good earth ground at the ICSD A measurement with the shield connected does not give a true reading of the individual ground location at the ICSD and will give a reading that is considerably low...

Page 18: ...oting will be more difficult so looping is not recommended Combining Wire Paths at the Interface While a single IC wire path can easily handle 750 ICMs when sized according to the design guide table t...

Page 19: ...communication between the central control computer and the remotely located ICI The MRLK900 Kit includes two radios that operate in the 902 928MHz range and automatically hop between frequencies to av...

Page 20: ...20 IC SystemTM Design Guide v2 3...

Page 21: ...IC SystemTM Design Guide v2 3 21...

Reviews: