background image

12

Notice that before the first use of the unit, it may be necessary to pass through the configuration process prior to defining the flushing 

program in order to adjust the features of controller to the specific application. The configuration process is described below.

6.2.1  The chain of editable fields

Below is the chain of editable fields. The existence of the DP SET-POINT field depends on whether the system contains a built-in electronic 

DP or not.

Flush Time

Accumulations

DP

Accumulations

Time

Accumulations

Manual

DP Set-Point

Flush Mode

6.2.2   The Flush Time

Flush Time defines the duration of the flushing time per station. The following options are selectable:

• 5-20 sec in steps of 1 sec

• 20-55 sec in steps of 5 sec

• 1-6 min in steps of 0.5 min

6.2.3   The DP Set Point

NOTE: 

The controller is pre-set to a 9 PSI differential pressure. This value  can be adjusted up or down based on water quality and screen 

size to adequately keep the screen clean. Lower differential pressure values will decrease the amount of contaminant that imbeds into the 

screen, especially with finer screens. A balance between differential pressure and the backwash frequency must be established based on 

site conditions. The lower the differential pressure, the more backwashes will occur. The higher the differential pressure, the harder the 

screen will become to clean. Typical differential set point is generally set somewhere between 6 and 9 PSI.

At this field the user defines the pressure difference between the filter’s inlet and outlet that when reached, a flushing cycle will take place. 
The DP set-point field will disappear if there is no Electronic DP connected. In this case the Digital DP input can be used.

Up to version 1.02 of the Filtron 1-10, 

A non-zero value Set-point would have caused the controller to ignore the Digital DP input completely, but a zero Set-point would make 

the Digital DP effective and cause the Electronic DP to be ignored.

Starting from version 1.03 

A change was made so that a non-zero Set-point does no longer cause the Digital DP input to be ignored, but instead a closed contact 

Digital DP input will cause the unit to keep on executing flushing cycles as long as the contact remains closed, ignoring the looping limit. 

When

the DP contact reopens, the flushing stops right away without completing the running flushing cycle.

Starting from version 1.03 if there is no Analog DP connected or when the set-point equals zero the unit refers to the Digital DP in the 

normal way, namely when the contact of the Digital DP is constantly closed it will execute consecutive flushing cycles until reaching the 

Looping Limit and then declare an endless Looping problem.

When the pressure is expressed in BAR the range of values is 0.1 – 1.0 BAR.

When the pressure is expressed in PSI the range of values is 1- 15 PSI.

The closed Digital DP contact will be indicated by the symbol :

Summary of Contents for HN-G-01 Filter Series

Page 1: ...rity to operate the equipment WARNING It is extremely dangerous to open the filter or control tubing while under pressure Always depressurize before performing any maintenance or troubleshooting HN G...

Page 2: ...D THE INSTRUCTIONS BEFORE INSTALLING THE HN G FILTER 1 1 Models This document relates to multiple models of the HN G filter system sections that relate to specific models are indicated as such 1 2 In...

Page 3: ...filtered out The clean water then exits through the outlet The build up of contaminants on the filter screen creates a differential pressure across the filter Based on a preset Differential Pressure...

Page 4: ...ten inches above the HN G for safe removal of the filter cover 2 Locate the HN G filter as close to a drain as possible This will maximize the efficiency of the automatic self cleaning 3 An AC to 12V...

Page 5: ...may be removed for service and any threaded connections can also be easily accessed if any of these need to be tightened up or resealed due to movement during shipping or installation Install an isola...

Page 6: ...upplied into the HP high pressure and LP low pressure fittings 3 Read the instructions in the following Filtron 1 10 DC Manual 3 4 3 Turning On Water Supply 1 Ensure Drain pipe is securely in the drai...

Page 7: ...outlet 4 4 2 If Battery Powered 1 Remove the top gray cover push up the sides over the indent 2 Remove the black battery tray and install the 4x D Cell batteries as shown 3 The controller will come t...

Page 8: ...r by checking the reading on the pressure gauges if installed 4 HN G 01 1 XXX HN G 02 1 XXX models only Remove Low Pressure 5 16 plastic tube from the Inlet to release the pressure and drain the HN G...

Page 9: ...e cycled in and out a few times to get the grease distributed to the inner O ring seal Two applications of grease and cycling is adequate 5 The Piston may drip water from the lower vent hole This is n...

Page 10: ...gation controller must be able to program station run times in seconds or a 24 VAC one shot relay capable of delivering a 7 second signal to the filter must be added The backwash time station run time...

Page 11: ...the unit is left untouched for a minute the display is switched off and the only life signal is given by a beep sound that can be heard every 20 seconds The beep can be disabled in the programming se...

Page 12: ...to clean Typical differential set point is generally set somewhere between 6 and 9 PSI At this field the user defines the pressure difference between the filter s inlet and outlet that when reached a...

Page 13: ...nd up 2 The last backflush valve can be cancelled and then its allocated output will be left unused 3 Alarm output Delay Valve and Main Valve when defined will be allocated in this order right after t...

Page 14: ...ered as a trigger for flushing The following flushing cycles will be triggered by the interval count down only The problem will be considered as solved when the constant indication of the DP sensor wi...

Page 15: ...ER DP DELAY 30 seconds 5 ENTER LOOPING 10 6 ENTER ALARM No 7 ENTER DELAY VALVE No 8 ENTER VIEW OUTPUT No 9 ENTER Pressure PSI 10 ENTER BEEP Yes No set to No to prevent sign of life beep every 20 secon...

Page 16: ...sure during Self Clean Solution Make sure water pressure during Self Clean is at least 40 psi Close the isolation valve on Outlet pipe of the HN G Press the M button on the Backwash Controller HN G wi...

Page 17: ...Very Poor lines Water source should be rated at worst case scenario if water quality varies during the year such as algae blooms during summer A general guide to Water Quality is also shown below Good...

Page 18: ...llation easier With unions at all recommended spots the filter may be removed for service and any threaded connections can also be easily accessed if any of these need to be tightened up or resealed d...

Page 19: ...mmodate low flow rate applications where all pressure and flow must be utilized for backwash the controlled outlet valve can also be applied in installation example A and C Pump Isolating valve Isolat...

Page 20: ...strates a bypass configuration Union fitting Union fitting Pressure gauge Pressure gauge Piston 1 Hydraulic drain valve Union fitting Isolation valve Outlet to irrigation Inlet from pump Drain to drai...

Page 21: ...TFC 10 06 Clamp MTFC 08 Cover MTFC 07 Hydraulic Motor MTFC 10 51 Collector Assembly MTFC 10 51 1 4 Tubing 6mm Plastic Tube MTFC Hex Nipple 1 MTFC Hex Nipple 1 CI010821W Streight Fitting 1 8 x 8mm MTFV...

Page 22: ...22 1 Models 2 Models 1 2 1 2 7 1 8 7 1 4 22 13 16 25 5 8 9 15 16 10 9 16 6 7 1 16 G Dimensions 1 PVC SOCKET CONNECTION PESB SCRUBBER VALVE 12 1 8 REF 5 3 4 7 1 16 6 FILTER SERVICE AREA...

Reviews: