Rain Bird ESP-LXIVM Troubleshooting Manual Download Page 34

34

ESP-LXIVM Controller Troubleshooting Guide

Table of 

Contents

Category

Issue

Potential Cause

Solution

Master 

Valves

The Master 

Valve will not 

open when 

stations are 

operating.

2-wire device or 

valve wires are not 

spliced correctly.

Turn dial to Diagnostics / Diagnostics / Select 

Ping MV and ping the MV address. If the ping 

test fails

check the decoder and valve wire splices and 

repeat the ping test.

IVM-Device is not 

functioning or 

damaged.

Turn dial to Diagnostics / Diagnostics / Ping 

Valve or Sensor, then ping the MV address. If the 

ping test fails swap the device, enter the new 

address and repeat the ping test.

IVM 2-Wire 

Interface 

Module

No output 

from the 

module.

Fuses in the module 

have blown due to 

short or secondary 

power connected to 

the 2-wire path.

Find the source of the short or power 

connected to the 2-wire path and address 

the problem. A replacement 2-wire Module is 

available for purchase.

Module is in 

Automatic Short 

Finding Mode due to 

short or secondary 

power connected to 

the 2-wire path.

Find the source of the short or power 

connected to the 2-wire path and address 

the problem. 

Pump Start 

Relays

The controller 

cannot close 

the pump 

start relay that 

is connected 

to a IVM-OUT.

Amp draw of the 

pump start relay 

is more than the 

Device can provide.

Use a Rain Bird PSR-Series Pump Start Relay 

that incorporates an ice-cube relay, double 

relay system. You can also add an ice-cube 

relay to the existing pump start relay. Contact 

Rain Bird Technical Services or Global Support 

Plan for relay model and wiring diagram.

Controller 

LCD Display

The controller 

display is either 

too light or too 

dark.

The display contrast 

needs to be 

adjusted.

Turn dial to Off, press Co/- buttons to 

adjust display contrast.

Controller 

display is 

blank.

Controller LCD 

display is damaged.

Plug in a 9V battery into the battery slot 

on the back of the controller front panel. If 

information is now visible on the display it 

is not damaged and working correctly. See 

other potential causes. If no information is 

displayed, remove the 2-wire module. If the 

alarm light on the front panel turns on after 1 

minute but no information is in the display, the 

LCD is damaged and the front panel should 

be replaced. A replacement panel is available 

for purchase.

Primary power to 

the controller has 

been lost or turned 

off.

This can be verified by checking the status 

lights on the 2-wire module. If both status 

lights on the module are dark the primary 

power is likely off. Find primary power source 

to the controller and turn it on. If the power 

breaker is tripped or fuse is blown, find source 

of problem, fix the issue, and turn the power 

back on.

Controller ribbon 

cable is not 

connected or 

damaged.

Check to make sure the ribbon cable is securely 

connected to both the controller backplane and 

the front panel. If the cable has broken wires or 

connectors, replace it.

Summary of Contents for ESP-LXIVM

Page 1: ...ESP LXIVM Controller Troubleshooting Guide...

Page 2: ...e visit www rainbird com esplxivm For free professional support for programming and troubleshooting please call 1 866 544 1406 Local Rain Bird Contact Information Distributor Mgr Email Phone Area Spec...

Page 3: ...res 6 Front Panel 6 2 Wire Settings 7 Diagnostics 7 Cabinet Components 8 Basic Programming 9 Troubleshooting Flow Charts 10 Getting Started 10 2 Wire Mapping 11 No Water Days No Run Times 13 Shorted P...

Page 4: ...37 2 Wire Path Status 37 Individual Path Status 37 Tools Recommended MAXI Cable 2 Wire communications cable Rain Bird WC20 splice kits for ALL electrical wiring connections Rain Bird genuine Wire Stri...

Page 5: ...ves connecting and troubleshooting can be found here PGA Series https www rainbird com products pga series PEB Series https www rainbird com products pebpesb series EFB CP Series https www rainbird co...

Page 6: ...Controller Troubleshooting Guide Table of Contents Controller Features Front Panel PROGRAMMING DIAL BACK BUTTON PROGRAM SELECT BUTTON DISPLAY PROGRAMMING KEYS ALARM LIGHT INFORMATION BUTTON LANGUAGE S...

Page 7: ...7 ESP LXIVM Controller Troubleshooting Guide Table of Contents 2 Wire Settings Diagnostics...

Page 8: ...8 ESP LXIVM Controller Troubleshooting Guide Table of Contents Cabinet Components TRANSFORMER JUNCTION BOX IVM 2 WIRE INTERFACE MODULE CONNECTOR...

Page 9: ...up process It s most effective to use the 2 Wire Settings in the order they appear in the 2 Wire Settings menu as follows 1 Master Valves 2 Weather Sensors if present 3 Station Setup 4 Flow Sensors if...

Page 10: ...4 1406 NoWater Days No RunTimes No StartTimes No PGM will More Exit Shorted Paths Duplicate Address Device Not Responding Flow Alarm END Job Well Done What does the screen display Is the LX IVM front...

Page 11: ...tings screen press the Down Arrow key to select 2 Wire Mapping then press Next 2 At the 2 Wire Device Mapping screen press the and keys to set the desired hour from 0 to 23 then press the Right Arrow...

Page 12: ...ping will begin Done Cancel The following pictures show the List Not responding screen without and with 2 wire mapping done Without 2 wire mapping With 2 wire mapping LIST NOT RESPONDING AT 01 01 18 T...

Page 13: ...te Time and ensure time and date are correct Is the LX IVMsystem working Check the display for Alarms see page 10 Troubleshooting END Job Well Done NO YES Test LX IVM system using Manual Watering or A...

Page 14: ...stics from the menu then press Next Press the Down Arrow button to select the Path 1 4 to test then press Next Next Page Press and hold the Yes button to energize the selected path Note Irrigation wil...

Page 15: ...his indicates that the controller put the module in Short Finding Mode If there are more than one 2 wire paths connected disconnect the first 2 wire path Did the controller exit Short Finding Mode and...

Page 16: ...ng new fence sign tree etc Wires damaged or found repairs of the Maxi Cable Repair damaged Maxi Cable using Maxi Cable and DRB Y connectors What does the display show Go back to Troubleshooting page 1...

Page 17: ...alf of the 2 wire path The problem is downstream between this point and the end of the 2 wire path Re connect the 2 wire path and go to an IVM device approx 50 between this point and the end of the 2...

Page 18: ...Quantity of other IVM SEN X 6 mA Approximate total system amperage in mA If there is a mismatch follow a process similar to page 10 to disconnect 50 of devices and redo calculation above Continue todi...

Page 19: ...d to repeat this process until all of the duplicates have been addressed Test LX IVM system using Manual Run or Auto Run Check the display for Alarms see page 10 Trouble shooting END Job Well Done NO...

Page 20: ...xceed your High or Low Flow settings Press the Down Arrow button to select Flow Alarms then press Next Turn the dial to Alarms History Press the Down Arrow button to select Station Flow Alarms then pr...

Page 21: ...GO BACK TO PREVIOUS PAGE 20 Flow Alarms cont Check the Alarms screen to see if previous alarm cleared END Job Well Done Run all zones manually Alarm is cleared on the display NO YES After fixing any...

Page 22: ...n press Ping The controller will ping the selected device and report a voltage reading if the device responds Interpreting Ping Results If the device does not respond verify the address and check the...

Page 23: ...1 0 mA milliamp Wire tracing and fault finding equipment Spare system components and tools including spare IVM SOL IVM SEN device WC20 Splice Kits and wire strippers Total System Milliamp Draw Before...

Page 24: ...the location of the 2 wire devices that are not responding and check all wire splices 2 Wire Path Diagnostics 1 Note the List Not Responding displays and corresponding wire paths If you notice that a...

Page 25: ...check for signs of recent construction digging 3 Find a device location about half way down the 2 wire path cable Disconnect the splices See if the controller is still in Short Finding Mode If the Sho...

Page 26: ...t a time from the controller IVM 2 Wire Interface Module Recheck the Control Output to isolate which segment of the 2 wire path has the ground fault 4 Find a device location about half way down the 2...

Page 27: ...o connect to a LX IVM controller In the event a compatible DC latching solenoid is not available you can use the Rain Bird Pump Start Relay with following modifications to power the AC Solenoid 1 Conn...

Page 28: ...ssistance with sourcing Choke and Capacitor Components VFD Filter Connection Connecting a VFD Pump in the same power circuit as the LX IVM Controller makes it prone to electrical noise having undesira...

Page 29: ...ve been entered Note the duplicate Device Addresses posted in the alarm screen verify and enter the correct Device addresses Controller alarm Short Finding Mode 2 wire path is shorted and the controll...

Page 30: ...tion Turn dial to Alarms History Flow Alarms and review the posted Station and or FloZone mainline flow alarms Note the station s or FloZone s that were identified If you configured FloWatch to Diagno...

Page 31: ...e it is firmly connected to the backplane and front panel 2 Wire Path Issues Communication with 2 wire devices is intermittent 2 wire cable or splices are leaking to ground or between conductors Turn...

Page 32: ...iple start times on an individual program In some cases users mix up start times and stations and can inadvertently program the system to start multiple times per day Water Windows have been configure...

Page 33: ...ation for opening a valve solenoid The LX IVM Valve Types are preconfigured for Rain Bird commercial valve models Information for configuring Valve Types to work with other valves can be found in the...

Page 34: ...porates an ice cube relay double relay system You can also add an ice cube relay to the existing pump start relay Contact Rain Bird Technical Services or Global Support Plan for relay model and wiring...

Page 35: ...remote is allowed regardless of the weather sensor state To see the current state of a weather sensor turn the dial to Weather Sensors The status of each sensor is displayed Wireless weather sensor is...

Page 36: ...ler Troubleshooting Guide Table of Contents IVM Interface Module This section explains the LED Status indicators on the IVM 2 Wire Interface Module LED Indicators MODULE STATUS 2 WIRE PATH STATUS 1 IN...

Page 37: ...is the Normal up and running state Solid GREEN SHORT ADDRESS CONFIGURATION During the Normal state there are devices in the field that have not yet been programmed with short addresses All other norm...

Page 38: ...essional Support Line at 1 866 544 1406 or else visit our web site at www rainbird com esplxseries Rain Bird Rewards www rainbird com rewards Phone 1 888 370 1814 Global Service Plan www rainbird com...

Reviews: