ESP-LXIVM Controller Troubleshooting Guide
Check the
controller display to
see if it has exited
Short Finding
Mode
Shorted Path (Manual Method) cont.
YES
NO
The problem is
upstream between this
point and the controller
Re-connect the 2-wire path
and go to an IVM device
approx. 50% between this
point and the controller.
Disconnect the 2-wire splice
to disconnect the second
half of the 2-wire path.
The problem is downstream
between this point and the
end of the 2-wire path
Re-connect the 2-wire path
and go to an IVM device
approx. 50% between this
point and the end of the
2-wire path. Disconnect the
2-wire splice to disconnect the
second half of the 2-wire path.
Next Page
For video instructions on
Automatic Short
Finding Mode
, please visit:
B
NOTE:
Once a small section 2-wire path is identified as having an
issue, use “Energize Path for Testing” and Milliamp Meter to track
for a sharp increase in test current before the location of the short.