General Operation
Normal
In the normal operating mode only the green POWER LED is lit. If any other LEDs are lit and/or the
buzzer is sounding there is an abnormal condition present.
Access Levels and Soft Keys
In normal operation the panel controls are inoperable, to prevent unauthorised operation (ACCESS
LEVEL 1 – Normal Level).
In order to operate the panel following a fire or fault alarm, or for routine testing, the controls must be
enabled by entering ACCESS LEVEL 2 (User level).
2 and 4 Zone Panels
Press the ALT button and then enter the access level 2 code (514).
N o t e . The 3-digit access code is advised at handover - ensure that it is known to all personnel who
may be required to operate the panel.
The CONTROLS ENABLED LED is lit and the controls are enabled.
Note. The panel reverts to normal operation (access level 1) if no button is pressed for 5 minutes - or
enter access code again to immediately revert to access level 1.
8 Zone Panel
Set the key-switch to ON.
The CONTROLS ENABLED LED is lit and the controls are enabled.
Note. Turning the key-switch OFF reverts to access level 1
There is a third access level which is used by engineers to access engineering functions and
configuration options, but is not required for general functions and is therefore not described in this
guide.
Fire Alarm
A fire alarm is annunciated when a detector detects smoke or heat, a manual call point is operated, or an
input is active. The subsequent actions depend on the actual configuration but generally:
- the alarms sound
- the FIRE LEDs are lit
- the buzzer pulses quickly
- the relevant zone LED is lit
The panel indicates if the activated device is a detector or a call point.
http://www.firealarmengineers.com
Summary of Contents for Twinflex
Page 1: ...1 Twinflex and Multipoint User Guide 26 0340 Issue 1 http www firealarmengineers com ...
Page 16: ...Twinflex and Multipoint User Guide 16 http www firealarmengineers com ...
Page 19: ...Twinflex and Multipoint User Guide 19 Date Comment Initials http www firealarmengineers com ...
Page 20: ...Twinflex and Multipoint User Guide 20 Date Comment Initials http www firealarmengineers com ...
Page 21: ...Twinflex and Multipoint User Guide 21 Date Comment Initials http www firealarmengineers com ...
Page 22: ...Twinflex and Multipoint User Guide 22 Modifications http www firealarmengineers com ...
Page 24: ...Twinflex and Multipoint User Guide 24 http www firealarmengineers com ...