2

 

 

 

Channel Disable (DISABLE)  (DIP Switch 1): 

When  the 

DISABLE

  DIP  switch  is  turned 

ON

,  the  channel’s  output  is  continuously  in 

the  No  Call  state  regardless  of  the  presence  or  absence  of  vehicles  over  the  loop.    The 
loop  oscillator  is  not  activated  when  the  channel  is  in  the  disabled  state.    The  factory 
default setting of this switch is 

OFF

NOTE:

  Changing the Channel Disable switch setting will reset the detector channel. 

Frequency (FREQ)  (DIP Switches 2 and 3): 

Each  channel  of  the  Model  222-1  detector  has  four  (4)  frequency  selections  that  allow 
altering  the  resonant  frequency  of  the  loop  circuit.    DIP  switches  2  and  3  are  used  to 
select the frequency for a given channel.  The value (

1

 or 

2

) to the left of the DIP switch 

is assigned to the switch when the switch is 

ON

.  If the switch is 

OFF

, the switch has a 

value  of  zero  (0).    By  adding  the  switch 

ON

  and 

OFF

  values,  the  two  switches  will 

combine  for  values  from  0  to  3  that  indicate  one  of  the  four  frequency  selections.    The 
following table is a reference for the switch settings and associated frequency selections. 

NOTE:

    After  changing  any  Frequency  switch  setting(s),  it  is  necessary  to  reset  the 

detector channel by momentarily changing one of the other switch positions. 

Frequency 

Switch 3 

Switch 2 

Effective Value 

HI 

OFF * 

OFF * 

0 + 0 = 

0

 * 

MED HI 

ON 

OFF 

1 + 0 = 

1

 

MED LO 

OFF 

ON 

0 + 2 = 

2

 

LO 

ON 

ON 

1 + 2 = 

3

 

*  Factory default setting. 

Fail Safe / Fail Secure Mode (FAIL SAFE)  (DIP Switch 4):

 

The Model 222-1 is a version of the Caltrans approved Model 222 that has the Fail-Safe / 
Fail-Secure  DIP  switch  disabled  and  is  defaulted  for  Fail-Safe  operation.    When  DIP 
switch 4 is turned 

ON

 or 

OFF

, the channel’s output maintains a Call state during a loop 

failure condition. 

NOTE:

    Changing  the  Fail-Safe  /  Fail-Secure  switch  setting  will  reset  the  detector 

channel. 

Presence / Pulse Mode (PRES PULS)  (DIP Switch 5):

 

DIP switch 5 controls the output mode of each channel. 

PRESENCE  (

PRES

):    When  the  switch  is  in  the 

ON

  position,  Presence  Mode  is 

selected.  Presence Mode will hold the smallest vehicle for four minutes minimum and 
either a small truck or a car typically for one to three hours.  This is the factory default 
setting and the most common setting. 

PULSE  (

PULS

):    When  the  switch  is  in  the 

OFF

  position,  Pulse  Mode  is  selected.  

Pulse  Mode  will  generate  a  single  125  millisecond  pulse  output  for  each  vehicle 
entering  the  loop  detection  area.    Any  vehicle  remaining  in  the  loop  longer  than  two 
seconds  will  be  tuned  out  providing  full  sensitivity  for  the  vacant  portion  of  the  loop 
detection  zone.    Full  sensitivity  for  the  entire  loop  detection  zone  is  recovered  within 
one  second  following  the  departure  of  any  vehicle,  which  has  occupied  the  loop  for 
longer than two seconds. 

NOTE:

  Changing the Presence / Pulse switch setting will reset the detector channel. 

Sensitivity (SENSE LEVEL)  (DIP Switches 6, 7, and 8):

 

There  are  eight  (8)  selectable  sensitivity  levels  for  each  channel.    The  eight  sensitivity 
levels are selected via DIP switches 6, 7, and 8 on each of the two front panel mounted 
eight-position DIP switch modules.  The value (

1

2

, or 

4

) to the left of the DIP switch is 

assigned  to  the  switch  when  the  switch  is 

ON

.    If  the  switch  is 

OFF

,  the  switch  has  a 

value  of  zero  (0).    By  adding  the  switch 

ON

  and 

OFF

  values,  the  three  switches  will 

combine for values from 0 to 7 that indicate one of the eight sensitivity level selections.  
Choose the lowest sensitivity level that will consistently detect the smallest  vehicle that 
must  be  detected.    Do  not  use  a  sensitivity  level  higher  than  necessary.    The  factory 
default setting is Sensitivity Level 6: -

L/L = 0.02% for detection.  The following table is 

a reference for the switch settings and associated sensitivity selections. 

NOTE:

  Changing the Sensitivity Level setting will reset the detector channel. 

Sense Level 

-

Δ

L/L 

Switch 6 

Switch 7 

Switch 8 

Effective Value 

1.28% 

OFF 

OFF 

OFF 

0 + 0 + 0 = 

0

 

0.64% 

ON 

OFF 

OFF 

1 + 0 + 0 = 

1

 

0.32% 

OFF 

ON 

OFF 

0 + 2 + 0 = 

2

 

0.16% 

ON 

ON 

OFF 

1 + 2 + 0 = 

3

 

0.08% 

OFF 

OFF 

ON 

0 + 0 + 4 = 

4

 

0.04% 

ON 

OFF 

ON 

1 + 0 + 4 = 

5

 

6 * 

0.02% * 

OFF * 

ON * 

ON * 

0 + 2 + 4 = 

6 *

 

0.01% 

ON 

ON 

ON 

1 + 2 + 4 = 

7

 

*  Factory default setting. 

ii.  Front Panel Mounted Pushbutton - Audible Detect Buzzer: 

A front panel mounted pushbutton labeled 

BUZZER

 is used to enable an audible detect 

signal that is emitted any time a given channel’s detection zone is occupied.  To activate 
this feature, press the pushbutton.  Only one channel can have this feature active at any 
given  time.    The  first  time  the  pushbutton  is  pressed,  a  short  (50  millisecond)  audible 
signal  confirms  the  activation  of  the  feature  for  Channel  1.    The  second  time  the 
pushbutton  is pressed,  two  short (50  millisecond)  audible  signals confirm  the  activation 
of the feature for Channel 2.  To deactivate this feature, press and hold the pushbutton for 
one  second.    A  long  (250  millisecond)  audible  signal  confirms  the  deactivation  of  the 
feature.  This feature will automatically turn off 15 minutes after activation. 

NOTE:

  When operating in Pulse mode, the audible detect signal will cease if a vehicle 

occupies the detection zone for more than two seconds. 