Page 7
Once held in, the yellow and red LEDs will cascade down and when they
begin to cascade down for the second time the reset button can be released.
A short flash on the red detect LED will appear on the adjusted channel or
channels only, which confirms that the RTM300 sensor has received the new
sensitivity setting. All other channels which have not been changed are not
reset and will keep detecting even during the reset period.
The sensitivity of the sensor can also be adjusted by moving the sensor
inside the duct either further out into the lane of interest or further back
towards the kerb line.
7.4 If necessary, the presence time can be adjusted using switches P1 and P2,
then following the same full reset process as described in section 7.3 above.
7.5 Use a handset to verify that the controller is responding to the outputs.
7.6 Perform any other acceptance testing as required in their procedures by the
local authority responsible for the site.