background image

Page 3

Leaving the RTM300 sensor connected whilst conducting a 500v insulation
(Megger) test will damage the sensor’s internal electrical components
rendering it unusable and invalidating any existing warranty.

6

INSTALLATION

CAUTION Ensure that all proper safety precautions are taken. Observe all
National and Customer codes of conduct and procedures whilst working on
any street furniture. Provisions should be made to ensure safe operation of
the crossing/junction at all times.

Confirm the operational modes required and set the front panel switches and
jumpers J1-4 of the RTM500 interface card accordingly.

Jumper Function

Fitted

Not Fitted

Notes

1

Output mode

Low
power

Fail safe
(TR2512)

Issue 3
and below

2

Not used

3

Not used

4

Not used

RTM500 Sensitivity & Presence Time Switch Settings

Sensitivity

Presence Time

S1

S2

P1

P2

0

0

LOW

0

0

CH OFF

1

0

MED LOW

1

0

3s

0

1

MED HIGH

0

1

4min

1

1

HIGH

1

1

35min

NOTE: This equipment is fitted with overvoltage protection to minimise the
disruption that may be caused by induced voltages from lightning or other
environmental effects.

6.1 INSTALLATION OF THE RTM300 SENSOR

6.1.1 The installation of the RTM300 sensor presumes that a suitable duct has

been installed, has sufficient capacity and is accessible. Where more than
one sensor is to be installed in the same duct, install the furthest sensor first
and work progressively to the nearest sensor.

Further information on the installation of ducts can be found in Appendix 3.

6.1.2 Attach a sufficiently long and suitable (e.g polypropylene) draw cord to the

attachment point on the sensor. Using the site plans or by measurement
along the kerb at 90° and at 45° (see figure 1 below) find the distance to the
white line. Half of this is the mid lane distance. Add on the set back of the
duct end in the pit from the kerb line to get the distance that the sensor has to
be pushed out. Measure off this distance on the draw cord and mark it using
suitable tape.

Summary of Contents for RTM300

Page 1: ...sub surface locations for vehicle detection as an alternative to inductive loop or similar technologies CONTENTS 1 DESCRIPTION 2 SPECIFICATIONS EU DIRECTIVES 3 MODIFICATIONS 4 REPAIRS 5 WARNINGS 6 INSTALLATION 7 TESTING 8 DECLARATION OF INCORPORATION 9 TECHNICAL DATA Document No TAMPRTM DOC Issue 4 Date 23 MARCH 2015 Written BPC Checked LS Approved BPC ...

Page 2: ... a two wire link which may be either new or legacy loop feeder cable 2 SPECIFICATIONS EU DIRECTIVES This Equipment has been designed to conform to Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC BS 7671 2001 AMD 9781 BS EN 50293 2001 TR 2512A TRG 0600B 3 MODIFICATIONS There are no approved modifications 4 REPAIRS The RTM300 and RTM500 are entirely self contained ...

Page 3: ...MED HIGH 0 1 4min 1 1 HIGH 1 1 35min NOTE This equipment is fitted with overvoltage protection to minimise the disruption that may be caused by induced voltages from lightning or other environmental effects 6 1 INSTALLATION OF THE RTM300 SENSOR 6 1 1 The installation of the RTM300 sensor presumes that a suitable duct has been installed has sufficient capacity and is accessible Where more than one ...

Page 4: ... end of the duct A recess is provided in the potting of the sensor to help locate the push rod When the sensor is in place withdraw the push rod and make the draw cord off within the pit preferably attaching it to the pit wall or other fixed location 6 1 5 Check the bottle joint to ensure that it is watertight and make the pit tidy before closing it 6 1 6 When all sensors are installed return to t...

Page 5: ...d 7 TESTING 7 1 Set presence time switches P1 and P2 to the off left position for all unused channels that will not have an RTM300 sensor connected to them The required presence time normally 4 minutes for UK traffic control applications for all active channels should also be set When the RTM500 Interface Cards are installed and powered for the first time the yellow and red LEDs on the front panel...

Page 6: ...ty settings should be adjusted to improve vehicle detection The sensitivity settings are adjusted using switches S1 and S2 on the front panel and the settings indicated on the product label or in section 6 above Once a new sensitivity has been selected for the channel of interest a full reset must be performed by pushing and holding in the reset button for greater than 3 seconds Reset Button Short...

Page 7: ...her back towards the kerb line 7 4 If necessary the presence time can be adjusted using switches P1 and P2 then following the same full reset process as described in section 7 3 above 7 5 Use a handset to verify that the controller is responding to the outputs 7 6 Perform any other acceptance testing as required in their procedures by the local authority responsible for the site NOTE To simplify c...

Page 8: ...Page 8 8 DECLARATION OF INCORPORATION ...

Page 9: ...en and close to detect i e these are joined at the interface card Jumper position 1 top two horizontal pins on the card can then be used to invert the output signal to get either open to detect OR close to detect but not both at the backplane If the RTM500 is to be powered by a 24v AC power supply the AC connections must be made to pins 19 20 the same as 24v DC supply If left at pins 23 24 the car...

Page 10: ...sent these will show a dc voltage of about 15V The low side of each feeder can be commoned and the high side should be treated as a separate core Where a phase has either X Y Z detection or for MOVA IN X SL then all three detectors may be connected back to the controller on a four core feeder This has to be broken into at the Z location and extended to the Y and then two cores run to the X It is s...

Page 11: ... we therefore recommend an absolute minimum internal diameter of a 20mm duct for easy passage of the sensor If smaller diameter ducts are used then care should be taken that re instatement of the carriageway does not distort the duct as this may prevent easy passage of the sensor If more than one sensor is to be fitted inside a cross carriageway duct allow adequate clearance for the cable and draw...

Page 12: ... a chamber or pit using spring clips fastened to the chamber or pit wall Certain kerb materials are designed with a bore and may accept an RTM300 sensor Users are strongly advised to trial any mounting location before committing to the final deployment Electrical Interference As the RTM300 sensor detects changes in the earth s magnetic field it is recommended that the sensor is not installed insid...

Page 13: ...eliable detection in the lane of interest using just the sensitivity switches on the RTM500 Interface Card it may be possible to re position the sensors off centre i e either towards the kerb or further out from the kerb to achieve better results and lane discipline Multiple sensors per lane In rare situations it may be desirable to install two or more sensors per lane and then connect their outpu...

Page 14: ...RTM300 Standard Cable Length 8 0m Interface Card Dims 3U x 5HP 160mm Eurocard to TR2512 RTM300 Weight unpackaged 475g RTM500 Weight unpackaged 200g ENVIRONMENTAL Operating Temperature Range 15ºC to 70ºC Storage Temperature Range 20ºC to 80ºC RADIX TRAFFIC LIMITED D3 Premier Centre Abbey Park Romsey Hampshire SO51 9DG England Tel 01794 511388 email info radixtraffic co uk web www radixtraffic co uk...

Reviews: