RADIUS
Product
Description
PDR 121
iom_pdr121_04_r02.doc
Rev 02
Page 58 (67)
13.3 Network Menu Configurations – IEC870 / RP570
The master radio network menu shall contain the remote IEC870 / RP570 RTU addresses; the
radio ID connected to the RTU and eventual repeater radio ID’s.
The slave radio network menus shall contain
the connected IEC870 / RP570 RTU address
, the
radio ID connected to the control system and eventual repeater radio ID’s.
Radio 99 (Master):
Radio 01:
Radio 02:
Radio 03:
Radio 04:
Radio 05:
RTU Id Radio Id R1 R2 R3 R4 R5 R6
01. 00001 01 -- -- -- -- -- --
02. 00002 02 -- -- -- -- -- --
03. 00003 03 -- -- -- -- -- --
04. 00004 04 03 -- -- -- -- --
05. 00005 05 03 04 -- -- -- --
06. ----- -- -- -- -- -- -- --
…
RTU Id Radio Id R1 R2 R3 R4 R5 R6
01. 00001 99 -- -- -- -- -- --
02. ----- -- -- -- -- -- -- --
…
RTU Id Radio Id R1 R2 R3 R4 R5 R6
01. 00003 99 -- -- -- -- -- --
02. ----- -- -- -- -- -- -- --
…
RTU Id Radio Id R1 R2 R3 R4 R5 R6
01. 00004 99 03 -- -- -- -- --
02. ----- -- -- -- -- -- -- --
…
RTU Id Radio Id R1 R2 R3 R4 R5 R6
01. 00002 99 -- -- -- -- -- --
02. ----- -- -- -- -- -- -- --
…
RTU Id Radio Id R1 R2 R3 R4 R5 R6
01. 00005 99 04 03 -- -- -- --
02. ----- -- -- -- -- -- -- --
…