5.4 HTTP Request setting
[4.HTTP DESTINATION SETUP MENU.]
A.Set HTTP Host URL [ 100.10.10.112 ]
B.Set HTTP Host Port [ 80 ]
C.Set HTTP NMAC [ 0000D880393E05ED ]
D.Set HTTP DATAIN File[/test.jsp]
Q.Quit.
A. Input the URL of the server that receives the information through the HTTP protocol.
B.
Input the port number of the server.
C.
Input the NMAC to be transmitted to the data server. For an NMAC, add "0000" before the VMAC.
D. Input the name of the page to which the data is to be sent through the GET method. Submit a GET
request to the host on the HTTP protocol. The parameters of the GET request should include the
data values, device IP addresses, and more. For more details, see <8. Definition of the HTTP
protocol>.
5.5 MODBUS TCP setting
From the PLC or the PCs, etc., you may use MODBUS TCP to access the RN172, to find out the
values of CH1 and CH2 inside.
[5.MODBUS TCP SETUP MENU.]
--------------------------------------------------------------
HOLDING REGISTER (16BIT),FUNCTION CODE 3
--------------------------------------------------------------
OFFSET [0] : CH1 FLOATING 32BIT VALUE (16BIT LOW)
OFFSET [1] : CH1 FLOATING 32BIT VALUE (16BIT HIGH)
--------------------------------------------------------------
OFFSET [2] : CH2 FLOATING 32BIT VALUE (16BIT LOW)
OFFSET [3] : CH2 FLOATING 32BIT VALUE (16BIT HIGH)
--------------------------------------------------------------
OFFSET [4] : CH1 INTEGER 16BIT VALUE (16BIT)
--------------------------------------------------------------
OFFSET [5] : CH2 INTEGER 16BIT VALUE (16BIT)
--------------------------------------------------------------
A.Set MODBUS TCP PORT[ 502 ]
B.SetByteReverse [ 0] (1:Reversed,0:None)
Q.Quit.
A. Change the port number used by MODBUS TCP. Normally, the port number is set to 502.
B.
Turn Byte Reverse ON/OFF. Select On(1) to change the sequence of the byte.