56
While bringing the boiler into the boiler room, it is very frequent that the entire boiler
cannot fit through the existing door or some other object in the boiler room represents an
obstacle. In such situations, it is very easy to disassemble the boiler into three basic assemblies:
-
water exchanger with furnace;
-
pellets transport mechanism;
-
silo.
Also, the position of the silo is assembled in the wrong way, it is very easy to disassemble
and reassemble three aforementioned assemblies and achieve the desired structure of the boiler.
Basic requirements that should be met while assembling:
-
While setting up the boiler pay attention to its side and rear side’s distance from possible
obstacles. That way, it will be possible to approach in order to clean ash from the boiler
or to, eventually, disassemble the pellet feeder.
-
The boiler can be connected to the open vented central heating system, but to the sealed
central heating system as well. If we are talking about the sealed central heating system,
it is recommended to install a thermal leakage protection valve, which is regulated by
appropriate laws of each county where the boiler is being installed. To install these
valves on the boiler itself, there are corresponding connections.
-
If there are frequent power outages in the potential boiler room, use additional
measures for the safety and protection of the boiler. If there are installation parts that
are ‘submerged’, that is on a lower level of the boiler and some heating bodies, it is
suggested to choose an open vented central heating system. The boiler has to be placed
at a safe distance from highly flammable materials.
-
The electric power supply for the boiler is 3x380V (except for TKAN80 Integra – all
power consumers are single-phase) and 50Hz, and the connection of all included parts
priključenje should be done according to all valid regulations and is done by a person
with appropriate permission.
-
Connection to a chimney is also done according to obligatory regulations as well as
recommendations from a manufacturer as it is written in the following text.
3.2 Boiler room
The boiler room must be secured against freezing.
The boiler base in the boiler room has to be made of inflammable material.
Recommended distances of all four sides of the boiler in relation to the walls of the boiler room
or some other rigid bodies (storage boiler, etc.) are shown in picture 3.
These distance values enable a safe approach while firing, sufficient space for cleaning,
and free approach to the fan, pellets feeding mechanism, electric heater for ignition, and valve
for charging and discharging. The space for handling the ash box should be provided.
From the silo’s side, there should be a distance from 400mm to 900mm (measured from
a wall) depending on the boiler's power. Those measures are given in the following text in the
Summary of Contents for TKAN Integra Series
Page 25: ...25 Slika 14 Brzi pristup nekim funkcijama sistema Slika 15 Rad sistema bez gre ke...
Page 27: ...27 Slika 18 Prikaz funkcija ekrana...
Page 71: ...71 Picture 14 Quick access to some system functions Picture 15 System operating without error...