background image

Installation Manual 

 

DOMESTIC HOT WATER WITH STORAGE CYLINDER  –  TA05A027.A0504

 

14

 

check the pressure in the system: if this has gone down, comes on restore 

pressure

;

 

AIR VENT VALVE CAP

CIRCULATING PUMP

RS

AIR VENT VALVE

PUMP CAP

 

close the tap on the filling loop once this operation is completed

 
Starting up the boiler 

 

turn on the gas cock situated under the boiler grill; 

 

set the ON/OFF button (1) (see fig.1 pag. 12) to ON position 

;  

Fig. 1

 

make sure that no flashing value is on the display (14); if value 04 is flashing 
and no.8 light is ON it means water deficiency in the system: open the filling 

tap  on the filling loop and fill the system

 

until a pressure of 1.5 bar has been 

reached (light no.11 ON) and then 

close the tap on the filling loop

 

the automatic ignition system will turn the burner on; 

 

should the boiler fail to ignite: if the display (14) shows value 04 flashing, it is 
necessary to repeat the procedure of filling the system; if the display (14) 

shows value 01 flashing 

wait 3 minutes; 

set the ON/OFF button (1) to OFF 

position 

 and then ON position 

 (fig.1). It may be necessary to repeat 

the procedure a few times to purge air from the pipes; 

 

set ON/OFF switch (1) in OFF position 

 (fig.1 page 12), insert a gauge 

into the pressure point no.4 (fig.2 page 14). Turn ON the boiler and check the 
minimum and maximum gas pressure setting in accordance with values 

stated on the gas data plate (to check maximum gas pressure value, turn ON 

a hot water tap and check that the maximum pressure is equal to that stated 

on the gas data plate; to check the minimum gas pressure, close the hot 
water tap, and select WINTER mode, the pressure gauge will show the minimum gas pressure value for 10 seconds. If the pressure 

values are not the same as those stated on the gas data plate, calibrate pressure again; 

Fig. 2

 

once the calibration procedure has been completed, unplug the mains lead or turn off the mains switch, close the gas cock and remove 
the gauge from the pressure point; tighten the screw making sure there are no gas leaks; 

 

after carrying out this operation, return the panel to its correct position and put the front casing back. 

CHECK 

the maximum heating power. 

For procedure regarding regulation of the heating system thermal capacity 

see «BOILER ADJUSTMENTS». 

 

EMPTYING THE CENTRAL HEATING SYSTEM 

Whenever it is necessary to empty the system, proceed as follows: 

 

set ON/OFF switch in OFF position 

  (fig.1 page 12); 

 

wait for the boiler to cool down; 

turn the system drain tap 

RS

 (see fig. 2) and use a container to collect the water that runs out; 

 

EMPTYING THE DOMESTIC HOT WATER SYSTEM 

Whenever there is danger of freezing, the hot water system should be emptied in the following way: 

 

shut off the water at the mains; 

 

open all hot and cold water taps; 

 

empty from the lowest point (where possible).

 

 

WARNING 

Please ensure that the boiler in commissioned in line with all BENCHMARK BOOKLET REQUIREMENTS. Failure to do this may in validate 

the guarentee. 

Summary of Contents for RSF 30 E

Page 1: ...504 Technical Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH INSTALLATION AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS models RSF 20 E RSF 24 E RSF 30 E TYPE C ROOM SEA...

Page 2: ......

Page 3: ...BOILER INSTALLATION page 10 ELECTRICAL CONNECTIONS page 12 BOILER CONTROL PANEL page 13 STARTING UP THE BOILER FOR THE FIRST TIME page 13 MULTIGAS OPERATION page 15 GAS TABLE REGULATING THE GAS PRESSU...

Page 4: ...9 336 EEC Electromagnetic compatibility GAS DIRECTIVE 92 42 ECC requirements for new hot water boilers fired with liquid or gaseous fuels All RADIANT boilers are constructed according to UNI CIG EC no...

Page 5: ...to the constructor s instructions Whenever the device is to be put out of service secure all potentially hazardous parts to prevent accidents or damage If the device is sold or transferred to another...

Page 6: ...ect the operation of the boiler 3 GENERAL WARNINGS BASED ON TYPE OF POWER SUPPLY POWER SUPPLY Electrical safety is achieved only when the device is correctly and efficiently earthed as per current saf...

Page 7: ...1 bar litres 10 10 10 Continuous hot water drawing with Dt 30 litres min 11 33 13 04 15 25 Max working pressure water bar 6 6 6 Min working pressure water bar 0 3 0 3 0 3 Width mm 410 450 450 Height m...

Page 8: ...st and the air intake directly to an external wall To insert a bend reduce total flue length by 0 8 m KEY R RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW Kit B Double exhaust emission twin flue...

Page 9: ...ORIES AND FLUE DIAPHRAGMS ONLY FLUE KIT 100 60 A F G C R 55 5 65 5 70 78 80 102 720 80 85 280 85 82 286 82 190 35 55 5 G 65 5 R 78 70 C 80 F 102 A 80 130 320 800 198 320 130 720 85 82 280 85 286 82 45...

Page 10: ...intake directly to an external wall To insert a bend reduce total flue length by 0 8 m KEY R RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW kit B Double exhaust emission twin flue system with 3...

Page 11: ...22 mm ininterrupted supply from meter to the isolation cock of the boiler The complete installation must be tested for soundness as described in the above code BS 6400 1985 BS6891 IMPORTANT BOTH THE U...

Page 12: ...ted less than 2m 6 6ft above a balcony above ground or above a flat roof to which people have access the terminal MUST be protected by a purpose designed guard Where the terminal is fitted within 850m...

Page 13: ...RACKET MOD 1 CON STAFFA MOD 1 MOD 2 KIT H MOD 1 MOD 2 MOD 1 KIT A 82 53 R HEATING RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW FIXING KIT Fig 3 Fig 1 WATER CONNECTIONS To facilitate installati...

Page 14: ...r in accordance with law no 46 of 5th March 90 see p 18 mod RSF 20 E RSF 24 E ANTI FREEZE SYSTEM ANTI FROST SYSTEM Radiant boilers are equipped with an Anti Freeze system which comes into operation wh...

Page 15: ...cated in the instrument panel as follows A Turn off the electrical power supply at the mains B Remove the boiler front casing C Undo the two screws on the panel and turn it to the position shown in fi...

Page 16: ...lied is the same as the type for which the boiler has been tested and approved see plate data make sure the unit is properly earthed make sure there are no flammable liquids or materials in the immedi...

Page 17: ...the gas data plate to check maximum gas pressure value turn ON a hot water tap and check that the maximum pressure is equal to that stated on the gas data plate to check the minimum gas pressure close...

Page 18: ...no 7 spanner The jets must be fitted with new gaskets reassemb Fig 2 mod RSF 24 E le the entire d new max e gas setting g plate and replace it with the new one pplied in the conversion kit burner uni...

Page 19: ...Main burner 17Jets jet mm 1 20 0 75 0 75 Consuption 15 C 1013 mbar m3 h 3 65 Consuption 15 C 1013 mbar kg h 2 72 2 68 REGULATING THE GAS PRESSURE Maximum and minimum modulation pressures N B The follo...

Page 20: ...pacity in kW mod RSF 20 E For 27 kW output boilers G20 G30 31 L P G NATURAL GAS 0 5 10 15 20 25 30 35 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 Gas pressure in mbar Output capacity in kW mod RS...

Page 21: ...proval with non toxic characteristics and is unaffected by hard water In addition a filter is fitted before the flowswitch and at the cold water inlet which eliminates any water impurities These featu...

Page 22: ...7 1 PWM 12 light blue 10 11 grey black RS light blue brown 13 14 16 15 L 12 11 9 10 8 7 6 5 4 3 2 N 56 1 5 bar PAC brown black M3 55 brown brown light blue black 59 57 58 60 61 PWM CONNECTOR FOR SM654...

Page 23: ...rol fig 5 or to the terminal block fig 3 dotted line on the terminals marked SE SE he remote control connection cable must pass through a channel which is separate from any system supplied with power...

Page 24: ...imit safety sensor for pressure limit Check the exhaust flue safety device Check the max and min modulation pressures and the modulation Check that the electrical connection conforms to the descriptio...

Page 25: ...Check the flue pipe n Check cable connection 04 Water deficiency in the system o Water pressure in the system insufficient stop below 0 5 bar p Water pressure switch cable disconnected q Water pressur...

Page 26: ...066LA GAS VALVE VK4105 G1112 EL MIDY S13 SF16 VENTED 37016LA EXHAUST FAN ES 30 108 G00 0416 43157LP SEALING CLIPS KIT FOR MULTIPLEX GROUP 58012LP MAIN HEAT EXCHANGER 20K 2003 58015LP MAIN HEAT EXCHANG...

Page 27: ...RSF 24 E 43002LA WASHER D 18 5x10 2x2 1 2 AFM34 43135LA 3 WAY VALVE FLANGE WASHER MPLEX 43139LA PLATE EXCHANGER O RING MULTIPLEX 43145LA 3 WAY VALVE MOTOR O RING MULTIPLEX 43150LA EPDM O RING FOR BRA...

Page 28: ...T HAVE BEEN CAREFULLY PREPARED BUT WE RESERVE THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS IN OUR PRODUCTS WHITCH MAY AFFECT THE ACCURANCY OF THE INFORMATION CONTAINED IN THIS LEAFLET E OE ALL RIGHTS RE...

Reviews: