Installation Manual 

 

Wall Hung Boiler – Cod. 99817NA – July 2001 

 

 

17 

TECHNICAL DATA 

 

DIFFERENTIAL AIR PRESSURE SWITCH FOR FAN CONTROL 

To guarantee maximum safety in flue exhaust, a differential pressure 

switch is installed on the Room Sealed Combustion Chamber Model (wall-

mounted, room-sealed boilers) and on forced draught boilers. This 
pressure switch automatically controls perfect functioning of the fan and 

the passage of both  external air and exhaust flue pipes. 

FLUE SAFETY THERMOSTAT 

Natural draught boilers model Open Combusion hamber Model are 

equipped with a device (see fig. 1) to control correct exhaust of 

combustion gases. This device guarantees maximum safety of operation if 
the flue should become partially or totally blocked, or if its section is not 

suitable for exhaust of combustion gases. 

 

N.B.

 

It is strictly forbidden to tamper with the device.

 

 

Before resetting the device, check the exhaust flue section and make sure 

there are no blockages obstructing the correct escape of fumes. 

RESETTING: 

before resetting the thermostat, carry out the following operations: 

turn off the main power supply switch; 

turn the summer-winter selector switch to the 

OFF

 position, detach the 

electrical connection (

1

) on the flue safety thermostat (see fig.1), press 

the button (

2

) between the two electrical contacts and then attach the 

electrical connection 

1

 again.; 

turn the main power supply switch on again and set the summer/winter 

selector switch to the position required.

 

 

DIVERTER VALVE VC 6012MG6000 

The diverter valve is the device which controls the boiler switching from 
central heating to d.h. water circuit and vice versa. The diverter valve is 

fitted with a manual command lever 

C

 (see fig. 3) which, when set on the 

top position, towards the valve head, allows the boiler operating on the 

domestic hot water circuit while, when set on the low position, the boiler 

operates on the central heating circuit.  
When the

 C

  lever is set on the central position, it allows the actuator on 

midway. 

In this position, 

to be used only in case of motor failure or damage

, both 

central heating and domestic hot water ports are open and both domestic 

hot water and central heating circuits are operating. 
 
To restore the initial position, separate the actuator and the valve body 

following instructions from no.1 to no.4 (see fig.2). 

To separate the motor from the valve body proceed as follows (see fig.2): 

1. 

Press button 

A

 under the motor. 

2. 

Simultaneously keep the 

A

 button pressed and turn the actuator 

counter-clockwise; 

3. 

Lift off the motor 

4. 

To disconnect the power supply cable press the 

tap located on the pin 

C

 

See fig.4 to perform the electrical wiring of the diverter valve to the main 

printed circuit board.  

Fig. 4

)

A

1

C

2

4

B

3

 

AB

A

B

D.H. WATER  SETTING

CENTRAL HEATING SETTING

MANUAL SETTING

AB

A

B

C

CENTRAL HEATING SETTING

D.H. WATER SETTING

 

LIGHT-BLUE

3 6

5

2
1 4

Light-blue -

 Common

Brown

  

- D.H. Water

Black

        

- Central Heating

M5 TERMINAL

BROWN

BLACK

RAMIRE P.C. BOARD

22

23

24

 

ELECTRICAL CONNECTION

2

1

Fig. 3 

Fig. 2 

Fig. 4 

Fig. 1 

FUMES SAFETY 
THERMOSTAT 75° 
 WITH  MANUAL RESET

 

Summary of Contents for RCM

Page 1: ...Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY By Technical Department INSTALLATION USE AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS Model RCM TYPE B OPEN COMBUSTION CHAMBER Mo...

Page 2: ......

Page 3: ...MENTS page 6 BOILER INSTALLATION page 8 ELECTRICAL CONNECTIONS page 10 11 20 23 BOILER CONTROL PANEL page 12 STARTING UP THE BOILER FOR THE FIRST TIME page 12 BOILER ADJUSTMENTS page 14 MULTIGAS OPERA...

Page 4: ...G AN OPTIONAL TIMER SELF DIAGNOSTIC LEGEND see fig 2 6 OPERATING POWER INDICATOR 7 DOMESTIC HOT WATER OPERATION 8 HEATING OPERATION 9 FLASHING LIGHT DENOTING AIR PRESSURE SWITCH FAILURE 10 FLASHING LI...

Page 5: ...e adjusted from a minimum of 30 C to a maximum of 80 C REGULATING THE HOT WATER TEMPERATURE The hot water temperature is regulated by turning knob 4 see fig 1 pag I turn it counter clockwise to lower...

Page 6: ...ompact homogeneous highly functional unit that is easy to install and simple to operate The wall mounted boiler is equipped with all of the approved accessories required to make it a true independent...

Page 7: ...n constructed to heat the home and to produce hot water The constructor declines all responsibility for incorrect installation and or use of the device Do not leave the device on when it is not being...

Page 8: ...12 8 12 8 17 5 BTU h 43648 43648 59250 Maximum rated output KCal h 20550 20900 23090 Kw 23 9 24 34 26 85 BTU h 81542 82931 91621 Minimum rated output KCal h 9370 9450 12900 Kw 10 9 11 15 BTU h 37180 3...

Page 9: ...th by 0 8 m Kit B Double exhaust emission twin flue system with 360 rotation It allows the flue exhaust into a flue duct and the air intake directly from an external wall To insert a bend reduce total...

Page 10: ...e chimney collective flues with natural draft or multiple combined flues follow the directions set out in the UNI 10640 standard CONNECTION OF FLUE PIPES All boilers must be connected to a duct for di...

Page 11: ...minal dynamic pressure of 20m Bar 8 in wg at the boiler Installation pipes should be fitted in accordance with BS6891 1988 Pipework from the meter to the boiler must be 22mm copper tube The complete i...

Page 12: ...al air infiltration or forced ventilation air conditioning systems If this should occur the appliance MUST BE TURNED OFF IMMEDIATELY and the local gas region consulted Where the lowest part of the ter...

Page 13: ...ves as shown in the picture 5 Position the boiler paying attention to hang it to the hanging bracket do not lean the boiler on the JIG and make final connections WATER CONNECTIONS To facilitate instal...

Page 14: ...ating sensor and 4 C Hot water sensor and protects the boiler down to 2 C external temperature To protect the internal Radiators a room thermostat or remote control must be fitted NOTE The frost syste...

Page 15: ...follows A Turn off the electrical power supply at the mains B Remove the boiler front casing C Undo the two side screws on the panel using the VT screwdriver and turn it to the position shown in fig...

Page 16: ...o the entry point on the electrical control box along with all the other leads on the boiler B Move the bridge PT see fig 1 from terminal TA to the free one next to it C Insert the thermostat wires fi...

Page 17: ...by using a soapy solution and eliminate all eventual leaks The checking procedure for the gas burner attachment is carried out with the boiler working make sure the electrical mains switch is OFF rem...

Page 18: ...s ON see fig 2 pag 12 The automatic ignition system will turn the burner on It may be necessary to repeat the procedure a few times to purge air from the pipes To repeat the ignition procedure press r...

Page 19: ...small screwdriver for any adjustments Turn clockwise to increase gas pressure to the burner at start up by setting the trimmer to maximum calibration pressure of modulator see page 16 Turn counter clo...

Page 20: ...hen converting the boiler to work with a different type of gas remove the existing plate and replace it with the new one supplied in the conversion kit h calibrate the new max and min settings for the...

Page 21: ...g C Slide out the coil 1 located above the gas valve Fig D Tighten plastic screw 3 by turning it clockwise be careful not to break it Fig E Use a no 17 spanner to undo the lock nut 5 which holds the c...

Page 22: ...ctor switch to the position required DIVERTER VALVE VC 6012MG6000 The diverter valve is the device which controls the boiler switching from central heating to d h water circuit and vice versa The dive...

Page 23: ...stic material which has type approval with non toxic characteristics and is unaffected by hard water In addition a filter is fitted before the flowswitch and at the cold water inlet which eliminates a...

Page 24: ...STAT 14 ELECTRONIC GAS VALVE VK4105 A 1001 15 GAS PRESSURE MODULATOR 16 ELECTRONIC IGNITION BOARD 17 EXPANSION VESSEL 18 3 SPEED CIRCULATION PUMP WITH AIR VENT 19 AUTOMATIC AIR VENT 20 HEATING CIRCUIT...

Page 25: ...D2 J3 FA1 C3 R48 C20 R49 R17 R23 R24 R47 R13 C8 J9 C6 C19 C21 C7 R15 R32 C13 R39 R37 R31 41 M9 R62 R61 R57 R16 42 C14 C9 R38 C5 RS1 J20 IC2 R18 IC1 R42 43 GPL 44 J7 46 45 R20 C12 R58 C10 C15 R40 R56 M...

Page 26: ...LB 7 6 9 9 8 11 11 10 10 12 12 8 13 EA ER 14 15 P 6 ELECTRONIC TEMPERATURE INDICATOR 54 50 51 53 52 55 56 58 57 RVB RVA RV 2 1 3 7 23 19 24 17 18 22 IG VD R CY CX L 20 5 21 16 4 NET FILTER CY N THERMO...

Page 27: ...ED5 C6 C7 RS1 R58 R22 R21 4 2 1 3 15 14 22 LED2 LED1 LED3 LED4 RAVI II R31 42 R18 R17 yellow blue R48 FA1 C20 R49 R23 R24 R47 C19 C21 red brown R39 C9 M9 R62 R61 R57 J16 R38 C5 J20 R37 41 R16 C14 IC2...

Page 28: ...19 24 18 22 12 13 12 11 EA 8 ER 6 RPA P 15 PTC2 14 5 20 21 V RVA 16 2 1 3 7 4 PA VD NET FILTER IG R CY CY CX N L AIR PRESSURE SWITCH FAN PUMP RELAY CONTACT D H WATER RELAY CONTACT FAN RELAY CONTACT T...

Page 29: ...erature When dismantling the boiler casing be careful when removing the side panels after having removed the front panel the front panel is removed by undoing the lower and front fixing screws and the...

Page 30: ...a replace it b re connect or replace it c replace it d change over polarity e make earth connection f fit conversion kit 4 Boiler on temperature rises rapidly and extinguishes flame light 2 fig 1 on...

Page 31: ...Installation Manual Wall Hung Boiler Cod 99817NA July 2001 26...

Page 32: ...AIR VENT 12 24028LA CIRCULATING PUMP MOTOR 13 96008LA 3 BAR PRESSURE RELIEF VALVE 1 2 14 59010LA WATER PRESSURE SWITCH 1 8 15 96030LA AUTOMATIC AIR VENT VALVE 5020 3 8 16 95011LA 8 LT EXPANSION TANK W...

Page 33: ...Tel 39 0721 498822 Fax 39 0721 499815 Email italia radiant it tecnico radiant it export radiant it Internet http www radiant it All descriptions and illustrations contained in this leaflet have been c...

Reviews: