R1CR 24 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX

_

P

ref

azione

_

EN

1.     

INTRODUCTION

WARNING

Before starting any operation it is mandatory to 
read this instruction manual, in relation to the 
activities  to  be  carried  out  as  described  in  each 
relevant section. Proper operation and optimal 
performance of the boiler are ensured by strict 
compliance with all the instructions given in this 
manual.

The installation, use and maintenance manual is 
an integral and essential part of the product and 
must be delivered to the user.

MANUAL USERS

The manual users are all those who install, use 
and maintain the boiler.

The  boiler  must  be  used  and  accessed  only  by 
qualified operators that fully read and understood 
the use and maintenance manual, paying particular 
attention to the warnings.

READING AND SYMBOLS OF THE MANUAL

To ease the understanding of this manual, 
recurrent symbols where used, in particular:

 

› On the outer margin of the page is placed a 

thumb index indicating the type of user to which 
the instructions in that section address.

 

› The titles are differentiated by thickness and 

size in accordance with their hierarchy.

 

› The images contain important parts described 

in the text, marked with numbers or letters.

 

› (See chap “chapter name”): this entry indicates 

another section in the Manual that you should 
refer to.

 

› Device: this term is used referring to the boiler.

 DANGER

It identifies an information related to a 

general danger that if not complied with, may cause 
serious personal damage or even death.

 ATTENTION

It identifies an information that if not 

complied with may cause small or medium level 
lesions to the person or serious deterioration to the 
boiler.

 WARNING

It identifies a precaution information that 

must be observed in order to avoid damaging the 
machine or parts of it.

MANUAL STORAGE

The manual must be carefully stored and replaced 
in case of deterioration and/or low legibility.

If you misplace the use and maintenance manual, 
you can request it from the Technical Support 
Centre giving the serial number and model of the 
boiler indicated on the plate placed on the right 
side of its casing.

As an alternative, the use and maintenance manual 
can be downloaded free from the on-line site www.
radiant.it, accessing the “download” section and 
entering the boiler model.

 INTRODUCTION 

Summary of Contents for R1CR 24

Page 1: ...R1CR 24 RAD ING Manual 1807 1_SK 2_MIAB3013_R7_PDX Installation Use and Maintenance Manual for model 0476 Condensing boiler R1CR 24...

Page 2: ...1 13 GAS CONNECTION 19 1 1 14 OPTIONAL ELECTRICAL CONNECTIONS 20 1 1 15 FUME EXHAUST FITTINGS 21 1 1 16 INSTALLATION MODES 22 1 1 17 TYPES OF FUME EXHAUST SYSTEMS 24 2 SUPPORT CENTRE SECTION 27 2 1 FI...

Page 3: ...3 1 1 GENERAL USE WARNINGS 60 3 1 2 CONTROL PANEL 61 3 1 2 DISPLAY ICONS 62 3 1 3 INFO MENU DISPLAY DATA 63 3 1 4 START UP 64 3 1 5 OPERATING MODE 64 3 1 6 INFORMATIONAL NOTE ON ANTI FREEZE FUNCTION...

Page 4: ...are differentiated by thickness and size in accordance with their hierarchy The images contain important parts described in the text marked with numbers or letters See chap chapter name this entry ind...

Page 5: ...tion without any obligation to third parties neither will the company be held responsible for any inaccuracies in this handbook deriving from printing or translation errors the material and intellectu...

Page 6: ......

Page 7: ...be performed only by qualified personnel having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water productio...

Page 8: ...and performance The location must be properly vented through an air vent The air vent must be placed at floor level to prevent it from being obstructed protected by a grid that does not hamper the us...

Page 9: ...the temperature in the boiler installation location goes below 10 centigrades please fill the plant with anti freeze liquid and insert and electrical resistances kit see chapter ANTI FREEZE PROTECTIO...

Page 10: ...woodencrate nails fasteners plasticbags expanded polystyrene etc must be kept out of the reach of children as they may be dangerous Therefore they should be dismantled suitably differentiating them in...

Page 11: ...3013_R7_PDX 1 Dimensioni_R1KR 24_28_R7_PDX_EN 1 INSTALLATION INSTALLER 1 1 5 OVERALL DIMENSIONS 1 1 6 JIG 307 410 690 64 157 301 64 136 151 82 65 54 62 65 82 R C G F A 123 A HEATING FLOW 3 4 C HOT 1 2...

Page 12: ...a vertical solid wall able to sustain its weight In order to allow the access inside the boiler for maintenance operations you have to respect the minimum technical spaces indicated in figure 1 It is...

Page 13: ...machine positioning proceed as follows see fig 3 1 Trace a line using a spirit level min length 25 cm on the installation wall 2 place the top of the jig along the traced line respecting the distances...

Page 14: ...perly inclined being levelled see fig 1 so as to allow the condense to drain 1 1 8 CIRCULATOR PREVALENCE FLOW DIAGRAM Appliance Loss fig 1 Wilo Yonos PARA MSL 12 6B 0 0 4 0 8 1 2 1 6 2 0 2 4 0 0 1 0 2...

Page 15: ...ve opening in case of plant overpressure DOMESTIC CIRCUIT In order to prevent limestone build up and damages to the domestic water heat exchanger the hardness of the domestic supply water should not e...

Page 16: ...ating circuit from the domestic circuit Before powering up the boiler fill the system as follows 1 slightly loosen the cap of the circulator jolly valve 1 fig 1 to release the air from the system 2 sl...

Page 17: ...ding tap R until the pressure gauge indicates the value of 1 2 bar fig 4 1 1 11 FILLING THE CONDENSATE COLLECTION SIPHON Before starting the boiler you have to fill the condensate collection siphon in...

Page 18: ...goes below 5 C automatically starting the burner until the water reaches the temperature of 30 C The system starts even if on the display appears OFF as long as the boiler is connected to the power 23...

Page 19: ...TRANSFORMATION the gas supply pressure falls within the values indicated on the data plate ELECTRICAL CONNECTION DANGER The equipment is electrically safe only if it is properly connected to an effic...

Page 20: ...use the electronic board placed inside the control panel as follows DANGER Cut off the voltage from the main switch remove the boiler s front casing refer to chapter ACCESSING THE BOILER remove the cr...

Page 21: ...so as to favour the reflux of the condensate towards the combustion chamber suitably realized to collect and drain acid condensate For all air suction ducts with regard to the air path you should pro...

Page 22: ...and certificated separately C83 Discharge in single or common fume exhaust duct and wall suction system C93 Discharge through an intubated conduct to a vertical terminal The technical compartment in w...

Page 23: ...entire length a section equal to or greater then that of the connection of the device discharge tube have no shut off devices shutters for direct external discharge there must be no more than two cha...

Page 24: ...ke for combustion through co axial ducts the external one for air intake the plastic internal one for fumes discharge PLEASE SEE THE MAXIMUM DISCHARGE LENGTH IN THE TABLE IN CHAPTER TECHNICAL DATA The...

Page 25: ...discharging fuel gas and air suctioning for combustion through two separated ducts PLEASE SEE THE MAXIMUM DISCHARGE AND INTAKE LENGTH IN THE TABLE IN CHAPTER TECHNICAL DATA The maximum discharge and i...

Page 26: ...through co axial ducts the external one for air intake the plastic internal one for fumes discharge PLEASE SEE THE MAXIMUM DISCHARGE LENGTH IN THE TABLE IN CHAPTER TECHNICAL DATA The maximum discharg...

Page 27: ...s described below relative to first start up maintenance and replacement should be performed only by qualified personnel and authorized by RADIANT BRUCIATORI S p A 1 SUPPORT CENTRE SECTION 2 SUPPORT C...

Page 28: ...rect make sure that the grounding system works properly make sure that the combustion air adduction and fumes and condensate discharge take place properly in compliance with the Local and National Law...

Page 29: ...te the circulating pump automatic reset again further 3 minutes and switch off the power supply and switch it on again Open the gas tap Use the button to select the desired operation mode If the symbo...

Page 30: ...cated in chapter Technical data otherwise adjust using a 40 Torx wrench the screw 2 fig 2 of the Off Set adjuster To increase the CO2 value turn the screw clockwise and vice versa if you want to decre...

Page 31: ...AND PROGRAMMING THE PARAMETERS To access the parameters menu and adjust their values follow the procedure below 1 Press the button to select the OFF mode 2 Press and hold both the and domestic circuit...

Page 32: ...ametri_MIAB_R7_EN 2 FIRST START UP SUPPORT CENTRE 4 Keep the button pressed until the parameter value is displayed 5 Use the and buttons of the domestic circuit to change the parameter value 6 Keep th...

Page 33: ...1CR 24 RAD ING Manual 1807 1_SK 2_MIAB3013_R7_PDX 2 Accesso e programmazione dei parametri_MIAB_R7_EN 2 FIRST START UP SUPPORT CENTRE 7 To quit the parameters menu press the button until OFF is displa...

Page 34: ...NEOUS WITH D H W PLATES EXCHANGER 02 ACCUMULATION 03 HEATING ONLY P02 GAS TYPE SELECTION ATTENTION READTHEINSTRUCTIONINCHAPTER GASTRANSFORMATION BEFORE CHANGING THIS PARAMETER 00 01 00 METHANE 01 LPG...

Page 35: ...RTER VALVE IN DOMESTIC POSITION FOR A PERIOD OF TIME EQUAL TO THE POST CIRCULATION SEE PARAMETER P09 SO AS TO MAINTAIN THE SECONDARY EXCHANGER HOT 00 01 00 DISABLED SET BY DEFAULT 01 ENABLED P07 HEATI...

Page 36: ...METER P00 AND ON THE GAS TYPE SEE PARAMETER P02 VALUE SET FOR PARAMETER P10 250 THE VALUE IS EXPRESSED IN HERTZ 1HZ 30 RPM P12 HEATING FAN MINIMUM SPEED ADJUSTMENT THROUGH THIS PARAMETER YOU CAN SET T...

Page 37: ...FOR STORAGE BOILERS ONLY THROUGH THIS PARAMETER YOU CAN ACTIVATE DEACTIVATE THE ANTILEGIONELLA HEAT TREATMENT OF THE STORAGE TANK AND SET THE DAYS AFTER THAT THIS FUNCTION CAN BE AUTOMATICALLY ACTIVA...

Page 38: ...E THE VALUES OF THE DELIVERY TEMPERATURES TM REFER TO STANDARD SYSTEMS 30 80 C OR FLOOR SYSTEMS 25 45 C THE SYSTEM TYPE CAN BE SET FROM PARAMETER P03 00 30 SET BY DEFAULT AT 25 THE NUMBERING OF THE VA...

Page 39: ...ED IN PERCENTAGE P20 CONTROL PERIOD T DELIVERY RETURN ONLYWITHMODULATINGPUMPANDRETURNPROBECONNECTED THROUGH THIS PARAMETER YOU CAN SET THE RESPONSE TIME TO THE PUMP MODULATION 20 100 THE VALUE IS EXPR...

Page 40: ...2 FIRST START UP SUPPORT CENTRE 2 1 6 ELECTRIC FAN FREQUENCY HEAT CAPACITY DIAGRAM GAS TYPE MINIMUM FREQUENCY MAXIMUM FREQUENCY G20 Hz 53 268 G30 Hz 53 250 G31 Hz 53 260 G30 G20 G31 0 2 4 6 8 10 12 14...

Page 41: ...itably adjusted and if required proceed as indicated in section CO2 VALUE CHECK AND CALIBRATION remove and clean the burner from oxidation check the integrity and the position of the sealed chamber se...

Page 42: ...1_SK 2_MIAB3013_R7_PDX 2 Avvertenze generali per la manutenzione_combinata_cond_EN 2 MAINTENANCE SUPPORT CENTRE check that the liquid flow is not obstructed and that there are no combustion gas reflu...

Page 43: ...at capacity C 80 26 Fumes temperature at minimum heat capacity C 65 7 CO2 at nominal heat capacity G20 9 3 9 1 CO2 at minimum heat capacity G20 9 8 8 CO2 at nominal heat capacity G30 11 2 11 CO2 at mi...

Page 44: ...rt Co ax m 10 Max discharge length 80 125 Vert Co ax m 12 Max discharge length 50 50 Vert Split m 26 Max discharge length 60 60 Vert Split m 60 Max discharge length 80 80 Vert Split m 100 Max discharg...

Page 45: ...with supplementary heater disabled PCHP100 Sup0 kW At rated heat output of cogeneration space heater with supplementary heater enabled PCHP100 Sup100 kW RU FRJHQHUDWLRQ VSDFH KHDWHUV OHFWULFDO H FLHQ...

Page 46: ...c kWh 0 146 Annual electricity consumption AEC kWh 53 DWHU KHDWLQJ HQHUJ H FLHQF wh 81 Daily fuel consumption Qfuel kWh 23 929 Annual fuel consumption AFC GJ 18 Contact details Tel 39 0721 9079 1 fax...

Page 47: ...EXCHANGER 3 BURNER UNIT 4 DETECTION ELECTRODE 5 VENTURI 6 CONDENSATE COLLECTION SIPHON 7 DHW PLATES EXCHANGER 8 DOMESTIC CIRCUIT PROBE 9 DIVERTER VALVE 10 AIR RELIEF VALVE 11 SAFETY THERMOSTAT 12 HEA...

Page 48: ...RNER UNIT 4 ELECTRIC FAN 5 DHW PLATES EXCHANGER 6 BY PASS 7 DIVERTER VALVE 8 DOMESTIC CIRCUIT PROBE 9 FLOW SWITCH 10 AIR RELIEF VALVE 11 SAFETY THERMOSTAT 12 HEATING PROBE 13 AIR SUCTION TUBE 14 PROPO...

Page 49: ...G PUMP MF MICRO FLOW SWITCH AR ORANGE VG GAS VALVE SR HEATING PROBE L LINE GI YELLOW TRA START UP TRANSFORMER SS DOMESTIC CIRCUIT PROBE N NEUTRAL BI WHITE TF FUMES THERMOFUSE 102 C EV ELECTRIC FAN NE...

Page 50: ...ront panel To intervene on the front of the boiler proceed as follows remove the fastening screws 1 fig 1 placed on the lower edge of the front panel grab the front panel from the bottom and remove it...

Page 51: ...er ot intervene on the wirings of the control panel please proceed as follows DANGER Cut off the voltage from the main switch Grab at the same time the support brackets of the control panel fig 1 loos...

Page 52: ...outlet and connect the other end of the tube to a suitable discharge turn the discharge tap of the system RS fig 1 open the relief valves of the radiators starting from the one at the top and continui...

Page 53: ...JUST MINIMUM OR SLOW LIGHT UP VALVE INFEED PRESSURE TOO HIGH ONLY FOR GPL BOILERS CHECK THE MAXIMUM ADJUSTMENT PRESSURE WITH FLAME LIGHT UP NEUTRAL AND PHASE INVERTED POWER SUPPLY PROPERLY CONNECT THE...

Page 54: ...SYSTEM AUTOMATIC WATER PRESSURE SWITCH CABLE DISCONNECTED CHECK THE WIRING WATER PRESSURE SWITCH BROKEN REPLACE IT E05 HEATING PROBE BROKEN OR INCORRECTLY CALIBRATED PROBE RESISTANCE VALUE 10 KOHM AT...

Page 55: ...UAL RESET CUT OFF THE TENSION E31 REMOTE CONTROLLER INCOMPATIBLE INDICATES THAT THE REMOTE CONTROLLER CONNECTED TO THE BOILER IS NOT COMPATIBLE WITH THE CIRCUIT BOARD REPLACE IT WITH A COMPATIBLE MODE...

Page 56: ...TS A TEMPERATURE OF 30 C F09 D H W CIRCUIT ANTI FREEZE THE FUNCTION IS AUTOMATICALLY ENABLED WHEN THE D H W SENSOR DETECTS A TEMPERATURE OF 5 C THE BOILER OPERATES AT MINIMUM GAS PRESSURE WITH THE DIV...

Page 57: ...2 and re tighten the coupling 3 see fig 1 CONVERSION TO NATURAL GAS Remove the diaphragm 1 and re tighten the coupling 3 see fig 1 Remount the components following the demounting operations in reverse...

Page 58: ......

Page 59: ...are addressed to all those who will use the machine The machine must be used and accessed only by qualified operators that fully read and understood the User section paying particular attention to th...

Page 60: ...roperty due to incorrect use DANGER The boiler should not be used by persons including children with reduced physical sensory or mental capacities or without suitable knowledge or experience unless th...

Page 61: ...lo comandi_combinata_MIAB_R7_EN 3 USE USER 3 1 2 CONTROL PANEL KEY 1 DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT KEYS 2 OPERATING MODE SELECTION KEY SUMMER HEATING ONLY WINTER OFF 3 RESET KEY ANOMALY RE...

Page 62: ..._EN 3 USE USER 3 1 2 DISPLAY ICONS KEY 1 INDICATION OF PARAMETER NUMBER OR DISPLAYED INFO CODE 2 FLAME PRESENT SIGNALLING 3 ERROR DISPLAY THAT CAN BE RESET 4 OPERATION IN HEATING MODE ENABLED 5 PARAME...

Page 63: ...t for 2 seconds It will be displayed the info code alternated to the associated value Use keys and of the heating circuit to scroll through the list of displayed data To exit display mode press the ke...

Page 64: ...led Whenever heating energy is needed to heat the rooms the automatic start up system will start the burner this is indicated by displaying the symbol blinking WINTER MODE In this mode the boiler meet...

Page 65: ...roceed as follows contact the Technical support centre that will empty the water system where no anti freeze is intended and will cut off the power water and gas supply Or leave the boiler in OFF oper...

Page 66: ...e sure using pressure gauge M fig 1 that the system pressure reaches 1 2 bar see fig 2 After performing this operation make sure that the loading tap R fig 1 is properly closed After the water pressur...

Page 67: ...AL SUPPORT CENTRE E03 FUMES SAFETY THERMOFUSE 102 C CONTACT THE TECHNICAL SUPPORT CENTRE E04 WATER MISSING IN THE SYSTEM IF THE SYSTEM PRESSURE IS BELOW 1 2 BAR FILL THE SYSTEM AS DESCRIBED IN CHAPTER...

Page 68: ..._combi_MIAB3013_EN 3 USE USER CODE FAULT INTERVENTION E99 GENERAL INTERNAL BOARD ERROR CUT OFF THE POWER SUPPLY FROM THE MAIN SWITCH AND THEN RESTORE IT AS SOON AS THE ERROR CODE DISAPPEARS THE BOILER...

Page 69: ...N ACTIVATE D E A C T I V A T E D IT BY HOLDING SIMULTANEOUSLY AND FOR 7 SECONDS THE RESET AND OF THE HEATING CIRCUIT 3 1 10 FAST H2O FUNCTION The Fast H2O function keeps a constant temperature in the...

Page 70: ...of the device using a wet cloth and come neutral soap WARNING DONOTuseabrasiveorpowderdetergents as they might damage the plastic cover and control elements 3 1 13 DISPOSAL The boiler and all its acce...

Page 71: ......

Page 72: ...RADIANT BRUCIATORI s p a Via Pantanelli 164 166 61025 Loc Montelabbate PU Tel 39 0721 9079 1 fax 39 0721 9079279 e mail info radiant Internet http www radiant it...