2. FIRST START-UP
SUPPOR
T
C
ENTRE
2.1.5. MIAB3013 PARAMETERS TABLE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P00
BOILER MODEL SELECTION
00 - 03
00 = 24 kW
01 = 25 kW (HEAT.) / 28 kW
(DOMESTIC)
02 = 34 kW
03 = 50 kW
04 = 24 kW - WITH
HONEYWELL GAS VALVE
P01
BOILER TYPE SELECTION
00 - 03
00
=
ISTANTANEOUS
WITH INTEGRATED HEAT
EXCHANGER FOR D.H.W.
SIDE
01 = ISTANTANEOUS
WITH D.H.W. PLATES
EXCHANGER
02 = ACCUMULATION
03 = HEATING ONLY
P02
GAS TYPE SELECTION
ATTENTION:
READ THE INSTRUCTION IN CHAPTER ‘GAS TRANSFORMATION’
BEFORE CHANGING THIS PARAMETER.
00 - 01
00 = METHANE
01 = LPG
P03
SETTING THE HEATING TEMPERATURE
IN CASE THE BOILER IS INSTALLED AS PART OF A LOW
TEMPERATURE CIRCUIT, PLEASE INSTALL A SAFETY
THERMOSTAT ON THE HEATING FLOW, WHICH CAN STOP
THE BOILER ACTIVITY IN CASE OF HIGH HEATING FLOW
TEMPERATURE. THE COMPANY ASSUMES NO LIABILITY FOR
DAMAGE CAUSED TO PERSONS OR FOR FAILURE TO COMPLY
WITH THESE INSTRUCTIONS.
00 - 01
00 = STANDARD (30-80 °C)
(SET BY DEFAULT)
01 = REDUCED (25-45 °C)
FOR FLOOR SYSTEMS