2. FIRST START-UP
SUPPOR
T
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P14
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED
DURING START-UP
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
VALUE SET FOR
PARAMETER P10
- 250
THE VALUE IS EXPRESSED
IN HERTZ
(1HZ = 30 RPM)
P15
ANTI-LEGIONELLA FUNCTION
(FOR STORAGE BOILERS ONLY)
THROUGH THIS PARAMETER YOU CAN ACTIVATE/DEACTIVATE
THE “ANTILEGIONELLA” HEAT TREATMENT OF THE STORAGE
TANK
AND SET THE DAYS AFTER THAT THIS FUNCTION CAN BE
AUTOMATICALLY ACTIVATED. THE DEFAULT VALUE IS 7 DAYS.
STARTING FROM THAT MOMENT THE WATER TEMPERATURE
INSIDE THE STORAGE
IS HEATED BEYOND 60 °C THUS
GENERATING A BURNING HAZARD. KEEP UNDER CONTROL
SUCH DOMESTICH HOT WATER TREATMENT (AND INFORM THE
USERS) TO AVOID UNFORSEEABLE DAMAGES TO PERSONS,
ANIMALS AND PROPERTY. A THERMOSTATIC VALVE SHOULD
BE INSTALLED AT THE DOMESTIC HOT WATER OUTLET TO
AVOID ANY BURNS.
00 - 15
00 = DISABLED
01-15 =
DAYS AFTER
THAT THE FUNCTION
IS AUTOMATICALLY
ACTIVATED