Default = 300 (min. 0, max. 8190)
The Repeat timeout parameter controls how long the unit waits for an acknowledgement
frame (see Retries parameter description). The timeout is started when the original frame
received from the Radio channel is transmitted to the connected device (over the serial
channel). Transmission of any other frame to the connected device is temporarily blocked,
whilst Repeat timeout is active. Repeat timeout = 0 disables this feature.
■
PR2000
PR2000 is an abbreviation for the PROTEUS 2000 SCADA protocol. This protocol is used in Master-
Slave applications.
The PR2000 protocol is implemented in a fully transparent manner. The original protocol frames
are transported over the RipEX network in their entirety.
The PR2000 protocol configuration uses the following parameters as described in
Sync Word (Hex)
Two protocol synchronization bytes (SYNC1 and SYNC2) concatenated.
The typical value is AA80
■
Profibus
RipEX supports Profibus DP (Process Field Bus, Decentralized Periphery) the widest-spread version
of Profibus. The Profibus protocol configuration uses all parameters described in
.
■
RDS
RDS protocol is a protocol used in MRxx networks. It supports network communication; any node
in the network can talk to any other (unlike Master-Slave type of protocols). The RDS protocol should
only be used when combining RipEX and MRxx networks or SCADA networks adapted to MRxx
networks.
Frames are received from the Radio channel and sent to COM1, COM2 or Terminal server 1-5 ac-
cording to UDP port settings and vice versa - from wire to radio channel.
Italicised
parameters are described in
.
RipEX Radio modem & Router – © RACOM s.r.o.