7.7 Water pump logic
Option 1: Water pump is related to compressor’s operation to start or stop. (Parameter
P3=0)
When heat pump turns on, filtration pump will start first and then fan motor and compressor.
Mode
Condition
Example
Water pump working logic
Heating
mode
T1≥Tset-0.5
℃
,
last for 30 minutes
T1≥27.5
℃
,
last for 30
minutes
Filtration pump will enter standby mode
for 1 hours(old version: 2 hours) and will
not start except after manual power off
and restart. Compressor and fan motor
stops first and filtration pump will
stop after 5 mins.
Cooling
mode
T1
≦
Tset+0.5
℃
,
last for 30 minutes
T1
≦
28.5
℃
,
last for 30
minutes
Note: If the water volume of the swimming pool is small, water temp reaches T1≥Tset+1
℃
and last for 5 mins, heat pump will stop first and then filtration pump stops, but it will not
entry standby mode for 1 hour. If water temp drops to T1≤Tset-1, heat pump will start again.
Option 2: When the heat pump is on (running or standby), filtration pump will always be on.
(Parameter P3=1)
When turn on heat pump, filtration pump starts first and then fan motor and compressor
start. When reaches to the condition T1≥Tset+1 and last for 3 mins, compressor and fan
motor will stop, filtration pump will always be on.
It will run for 1 minute after turning off the hp.
NOTE :
Tset = Tseting water temperature
For example : Tset = 28
℃
Tseting water temperature in your pool heat pump
Tset-1 = less 1
℃
than Tseting temperature
Tset- 1 = 28-1=27
℃
Tset+1= more 1
℃
than Tseting temperature
Tset+ 1 = 28+1=29
℃
1 hour later Mode
Condition Example
Tset=28
℃
Water pump working logic
Filtration
pump will
start to run
for 5 mins to
detect the
water in
temp.
Heating
mode
T1>Tset-1
℃
T1>27
℃
Filtration pump will enter standby mode for another
1 hours
and will not start except after turning off
the hp and restart.
T1≤Tset-1
℃
T1≤27
℃
Heat pump will start again until it meets the
condition of standby.
Cooling
mode
T1<Tset+1
℃
T1<29
℃
Filtration pump will enter standby mode for another
1 hours
and will not start except after turning off
the hp and restart.
T1≥Tset+1
℃
T1≥29
℃
Heat pump will start again until it meets the
condition of standby.
Summary of Contents for INVERTER 7
Page 1: ...POMPE CHALEUR DE PISCINE D RACER INVERTER NOTICE D INSTALLATION ET D UTILISATION...
Page 2: ......
Page 6: ...3 2 Dimension 2 1 Dimension Mod les RACER INVERTER 7 9 KW...
Page 7: ...4 Mod les RACER INVERTER 11 14 16 KW Mod les RACER INVERTER 19 KW 25KW...
Page 42: ...39 10 Sch ma clat et liste des pi ces d tach es 10 1 Mod le RACER INVERTER 7KW 9KW...
Page 45: ...42 10 2 Mod le RACER INVERTER 11KW 14KW 16KW...
Page 49: ...46 10 3 Mod le RACER INVERTER 19KW 25KW...
Page 53: ...50 Swimming Pool Heat Pump RACER INVERTER...
Page 57: ...54 2 Dimension 2 1 Dimension RACER INVERTER 7 9 KW...
Page 58: ...55 RACER INVERTER 11 14 16 KW RACER INVERTER 19 KW 25 KW...
Page 87: ...84 2 3 The main interface...
Page 93: ...90 10 Exploded Diagram and spares parts list 10 1 RACER INVERTER 7KW 9KW...
Page 96: ...93 10 2 RACER INVERTER 11KW 14KW 16KW...
Page 100: ...97 10 3 RACER INVERTER 19KW 25KW...
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ...CASH PISCINES FRANCE 13 Avenue Neil Armstrong 33700 M rignac A0165RCI02...