TURN OFF POWER BY REMOVING POWER 
FUSE OR TURNING OFF CIRCUIT BREAKER 
BEFORE INSTALLATION.

•  Total lighting load must not exceed: 

500W LED SMSLES13 at 120 Volts 
5 Amps, 450 Watts LED at 120 Volts with 
0.8pF driver 
5 Amps, 300 Watts LED at 120 Volts with 
0.5pF driver.  
To switch more wattage, an electrician 
can install an additional relay.

•  Line Carrier Remote Control Systems 

such as X-10, Leviton or Radio Shack are 
incompatible with sensors and cause false 
activations.

•  Do not install on circuits feeding motor 

loads such as kitchen appliances, HVAC 
equipment, washer/ dryer or garage door 
openers.

•  Sensor functions best when movement is 

across its detection pattern, not towards 
the sensor.

•  Mount 6’-10’ high for optimum range  

and direction. 

(fig. 1.)

Less Sensitive

More Sensitive

Black

Black

Red

   

Red 

(pigtail)

Ground

Ground

Power In

White

White

Fig: 3

Fig: 1

Fig: 2

Two LESLIE13 heads come pre-wired and assembled on 

CU4 plate

, allowing for 

mounting on round, rectangular or octagonal surface or recessed junction boxes. Apply 
weatherproof silicone sealant around the edge of the 

Junction Box

 

(not supplied)

. This is 

especially important with an uneven wall surface. 

1.  Attach the 

Universal Mounting Bar

 with the screws provided to the 

Junction Box 

(fig. 3.)

 In case of surface mount junction box, use with the 

Metal Surface Plate

.

2.  Use the ‘S’ shaped hands free 

Hanging Hook

 to hold the 

CU4 plate

 during wiring.

3.  Bring power leads and 

LESLIE13

 head leads into 

Junction Box

.

4.  Strip off atleast 1/2” of insulation from all leads, and insert through openings in 

Metal Surface Plate

 

(if used)

.

5.  Attach ground wire to grounding screw on 

Junction Box

. Complete wiring as 

shown in wiring diagram section.

6.  Align 

Gasket, CU4 Plate

 and 

Metal Surface Plate

 

(for use with surface mounted 

junction boxes)

 to ensure proper seal. 

7.  Tighten 

Center Screw

 

(make sure 

O-Ring Gasket

 is on the screw)

 to attach 

CU4 plate

 

to the box. Check that the 

Gasket

 is fully sealed.

8.  Insert plastic 

Finishing Cap

 in the center of the 

CU4 plate

 for a weatherproof seal. 

Use silicone sealant on all plugs and unused conduit entries.

9.  Aim LESLIE13 heads in the desired direction and tighten locknut and arm screw.

Two SMSLES13 heads come pre-wired 
and assembled along with SMS500 sensor 
on CU4 plate, allowing for mounting on 
round, rectangular or octagonal surface or 
recessed boxes. 

1.  Connect the black fixture lead to the 

(+) LINE supply lead. 

(fig. 2.)

2.  Connect the white fixture lead to the 

(-) COMMON supply lead.

3.  Connect the GROUND wire from 

fixture to supply ground. 

4.  Red pigtail is only used to switch 

remote or additional fixtures.

O-Ring 

Gasket

CU4 

plate

Gasket

Plug

Center 

Screw

Finishing 

Cap

Metal Surface 

Plate

Hanging 

Hook

Universal 

Mounting Bar

Bar 

Screws

Junction Box

(not supplied)

FIXTURE MOUNTING

ASSEMBLY AND WIRING

Summary of Contents for SMSLES2X13

Page 1: ...red promptly sales rablighting com Free Lighting Layouts Answered online or by request 2019 RAB LIGHTING Inc Northvale New Jersey 07647 USA RAB WARRANTY RAB s warranty is subject to all terms and conditions found at rablighting com warranty PATENT Patent information can be found at rablighting com ip SMSLES2X13 INSTALLATION MANUAL 73493 RAB ...

Page 2: ...ent 5 seconds to 15 minutes Quick Test Time 5 second test time for fast installation Works day or night Detection Zone Full 180º by 30 No Hands Auto Testing Auto mode starts after 3 minutes of testing No adjustment needed Built for Severe Conditions Double weatherproofing for long life Wire Nuts 3 Adjustment Tool Lens Mask SMSLES2X13 IMPORTANT READ CAREFULLY BEFORE INSTALLING FIXTURE RETAIN THESE ...

Page 3: ...llowing for mounting on round rectangular or octagonal surface or recessed junction boxes Apply weatherproof silicone sealant around the edge of the Junction Box not supplied This is especially important with an uneven wall surface 1 Attach the Universal Mounting Bar with the screws provided to the Junction Box fig 3 In case of surface mount junction box use with the Metal Surface Plate 2 Use the ...

Page 4: ...r operation in low level lights turn the knob all the way clockwise to the sun symbol Adjust counterclockwise to have the sensor come on later at dusk clockwise to have it come on earlier Turning photocell control will show when the sensor thinks the current ambient light level night because the lights will turn on Factory setting Night Only Sensitivity Increases or decreases the responsiveness an...

Page 5: ...ver the sensor Put sensor into Test Mode After the initial 30 seconds of the lights being on lights should stay off Wave your hand inside the bag in front of sensor Lights should go on and then time out If sensor operates properly when covered check items 2 6 Problem Sensor is triggered by unwanted movement or heat source Solution Tilt sensor Pg 9 or mask lens in the direction of the source Move s...

Page 6: ... lamps and fixtures work Compare wiring to the Wiring Diagram in this manual Check that the power is on 2 If installing during daylight remember that the sensor will provide a 3 minute Test Period after power is turned on After 3 minutes the sensor will switch to Automatic Mode and will not work during daylight if the Photocell Control is turned to or near the night only position fully counter clo...

Page 7: ...he sensor is detecting changes in temperature If this is a constant problem mount the sensor in a more protected area 2 Tilt the sensor lower it may be seeing distant objects moving 3 You may not be aware that animals have triggered sensor Check sensor aiming to reduce nuisance triggering or mask the lower part of the lens with opaque weatherproof tape 4 The sensor may turn on occasionally during ...

Page 8: ...product has been installed the entire installation was performed by a licensed electrician or under the supervision of a licensed electrician and the product was in its original unopened and new condition at the time of installation RAB LIGHTING DISCLAIMS ALL REPRESENTATIONS AND WARRANTIES WITH RESPECT TO ALL OTHER PRODUCTS INCLUDING WITHOUT LIMITATION PRODUCTS THAT HAVE BEEN PURCHASED FROM ANY PE...