INSTRUCTIONS

EZPAN® HE INSTALLATION

RAB Lighting is committed to creating high-quality, aff ordable, well-designed and energy-effi  cient LED lighting and controls that make it easy for electricians to install

and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]

RAB WARRANTY:

 RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty    

WIRING

OPERATION

MAINTENANCE

TROUBLESHOOTING

CAUTION: FOR BATTERY BACKUP FIXTURE. 

Voltage can be present

in 

BATTERY.

To prevent high voltage from being present on

output leads, Inverter connector must be open. Do not join 

BATTERY

 connector until installation is complete and AC 

power is supplied to the emergency driver.

(

Fig. 6

)

NOTE:

Make sure that the necessary branch circuit wiring

is available. An UNSWITCHED AC source of power is required.

The emergency driver must be fed from the same branch

circuit as the LED driver. 

CAUTION:

Do not use any supply voltage other than 120-277V

50/60 HZ.

Although no routine maintenance is required to keep the 
emergency driver functional, it should be checked periodically to 
ensure that it is working. The following schedule is recommended:
1.  Visually inspect the charging indicator light monthly. It should 

be illuminated.

2.  Test the emergency operation of the fi xture at 30-day intervals 

for a minimum of 30 seconds.

3.  Conduct a 90-minute discharge test once a year. Fixture will 

operate at reduced illumination for a minimum of 90 minutes.

1.  Is the fi xture grounded properly?
2.  If the charging indicator light does not illuminate after pressing 

the test button, check if battery is connected properly. 

3.  Is the Battery Backup Dip Switch Position set to the correct 

position?

1.  Connect 

UNSWITCHED HOT

fi xture lead to 

HOT AC

 supply line.

2.  If using an 

UNSWITCHED 

circuit, connect 

UNSWITCHED

 and 

SWITCHED

 lines together.

3.  If using a 

SWITCHED

 circuit, connect 

SWITCHED HOT

 AC fi xture 

lead to the external. 

4.  Connect the pink 

(or gray) 

fi xture lead to the (V-) DIM lead.

5.  For 0-10V Dimming, connect 

DIM

 (+) and 

DIM

 (-) to the supply

ground. Do not connect 

GROUND

 to the output leads.

6.  All unused leads must be capped and insulated. 

7. 

After installation is complete, supply AC power to the fi xture and 

connect the 

BATTERY.

8.  When power is on, the fi xture should be on and the Charging

Indicator Light should illuminate to indicate the battery is 

charging.

9. 

Once the BATTERY has charged for at least one hour, a short
duration test may be performed by pressing the test button.

10.  After the battery has charged for 24 hours, a long duration test 

can be performed by shutting power to the fi xture.

1.  When AC power is applied, the charging indicator light is 

illuminated, indicating that the 

BATTERY

 is being charged.

2.  When power fails, the standby power automatically switches 

to emergency power 

(internal battery)

, operating at reduced 

illumination. The emergency driver supplies power in standby 
power for a minimum of 90 minutes.

3.  When AC power is restored, the emergency driver 

automatically returns to charging mode.

LIGHT

FIXTURE

INSIDE FIXTURE

BATTERY

Pink (or Gray)/DIM–

Black/Switched Line

Green/Ground

White/Neutral

Black/Unswitched Line

Purple/DIM+

BACKUP

DRIVER

BATTERY

CONNECTOR:

CONNECT

ONLY AFTER

AC SUPPLY

POWER IS

CONNECTED

FIG. #6

Easy Answers

rablighting.com

Visit our website for product info

Tech Help Line

Call our experts: 888 722-1000

e-mail

Answered promptly - [email protected]

Free Lighting Layouts

Answered online or by request

© 2022 RAB LIGHTING Inc.

BATTERY BACKUP MODELS

73613-RAB

EZPAN HE - IN - 0522

Battery Backup Setting

PRODUCT

WATTAGE

DIP SWITCH

POSITION (12W)

EZPANHE 1X4

12

EZPANHE 1X4

23,  30

EZPANHE 2X2

12

EZPANHE 2X2

23,  30

EZPANHE 2X4

23,  30,  46

1 = Off

2 = On

Reviews: