ECOMBO34 RED/GREEN EXIT/EMERGENCY LIGHT
ECOMBO34-RG
M
I PORTANT
CAREFULLY BEFORE INSTALLING FIXTURE. R TAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
READ
E
IMPORTANT SAFEGUARDS:
When using electrical equipment, basic safety precautions should always be followed including the following:
IMPORTANT:
The battery in this unit may not be fully charged. After electricity is connected to the unit for at least (24) hours, normal operation of
unit should
turn on.
In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90
minutes. Refer to your local codes for any additional requirements that may apply.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Note:
UL recommended maximum mounting height is 19.8-ft.
1. Do not use outdoors.
2. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
3. Do not mount near gas or electric heaters.
4. Cap unused wires with enclosed wire nuts or other approved method.
5. Do not use this equipment for other than its intended use.
6. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
7. Disconnect AC power before servicing and installation.
8. Consult local building code for approved wiring and installation.
9. Use caution when servicing batteries.
11. Make sure wire terminations are secure and leads are properly tucked in appropriate wire channels.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
Wall Mount Installation
Fig: 1
Fig: 2
1. De-energize the circuit at the junction box where the exit sign is to be
installed.
2. Remove the exit sign stencil and set aside. Remove the hardware and LED
Lamp heads and set aside. Included plastic canopy and mounting plate are
not required for this installation and can be discarded.
3. Drill out the appropriate mounting pattern and the wire pass hole in the EXIT
back plate to fit the junction box being used.
4. Feed the red, black and white wires through the wire pass hole.
5. Ensure blue and yellow lamp head wires are routed through side lamp head
mounting holes
(Fig 1).
Attach first lamp head to housing by aligning tabs on
lamp head assembly to lamp head mounting slots on frame of housing
(Fig 2)
.
Gently push lamp head down toward bottom of housing to lock into place. An
audible click should be heard. Repeat to install the second lamp head.
6. Route lamp head wires through proper wire channels and connect to the exit
sign lamp board.
7. Reference Wiring Diagram section and make proper electrical connections at
the junction box in the metal housing.
8. Fasten back plate to junction box cover.
9. Connect battery only after continuous AC power can be provided to the unit.
10. Remove proper Chevron(s) on the Exit face plate as required.
11. Secure face plate to housing.
Insert in Slots
Click Down
10. Any service on this equipment should be performed by qualified personnel only.