![RAB Lighting ND4R Installation Instructions Manual Download Page 3](http://html1.mh-extra.com/html/rab-lighting/nd4r/nd4r_installation-instructions-manual_3119449003.webp)
WIRING
CAUTION: THIS IS AN EMERGENCY BATTERY BACKUP
FIXTURE. Voltage could be present in Battery. To prevent
high voltage from being present on output leads, inverter
connector must be open. Do not join inverter connector
until installation is complete and AC power is supplied to
the emergency ballast.
NOTE:
Make sure that the necessary branch circuit wiring is
available. An unswitched AC source of power is required. The
emergency ballast must be fed from the same branch circuit
as the AC ballast.
Do not use any supply voltage other than those specified
below.
ND4R/E2 or ND4S/E2
120V-277V, 50/60Hz
1. Connect the UNSWITCHED black fixture lead to the HOT
supply lead.
2. Connect red and black lead together, if not using a
switching method.
3. If switching, connect SWITCHED red lead to a switch.
4. Connect the COMMON fixture lead to the COMMON
supply lead.
5. For Lutron system, follow manufacturer’s instructions.
5. Connect the GROUND wire from fixture to supply ground.
Do NOT connect the GROUND of the dimming fixture to
the output.
6. All unused leads must be capped and insulated.
7. After installation is complete, supply AC power to the
emergency ballast and join the inverter connector.
9. At this point, power should be connected to both the
AC ballast and the emergency ballast, and the Charging
Indicator Light should illuminate indicating the battery is
charging.
10. A short-term discharge test may be conducted after the
emergency ballast has been charging for one hour. Charge
for 24 hours before conducting a long-term discharge test.
Refer to OPERATION.
MAINTENANCE
Although no routine maintenance is required to keep
the emergency ballast functional, it should be checked
periodically to ensure that it is working. The following
schedule is recommended:
1. Visually inspect the charging indicator light monthly. It
should be illuminated.
2. Test the emergency operation of the fixture at 30-day
intervals for a minimum of 30 seconds.
3. Conduct a 90-minute discharge test once a year. Fixture
would operate at reduced illumination for a minimum of
90 minutes.
To reduce the risk of electric shock, disconnect both normal and
emergency power supplies and converter connector of the emergency
ballast before servicing. Do not attempt to service the emergency
ballast. The use of accessory equipment may cause an unsafe condition.
Do not use this product for other than intended use. Refer any servicing
indicated by these checks to a Qualified Service Personnel.
Note: These instructions do not cover all details or variations in
equipment nor do they provide for every possible situation during
installation, operation or maintenance.
CLEANING
CAUTION: Be sure fixture temperature is cool enough to
touch. Do not clean or maintain while fixture is energized.
1. Do not open fixture to clean the LEDs. Do not touch the
LEDs.
2. Do not touch reflector, lens, or trim cone.
3. Do not clean any fixture surface with wood base cleaning
material such as paper towels or tissues. Only use micro
fiber cleaning cloth.
Easy Installation & Product Help
Tech Help Line
Call our experts 888 RAB-1000
©2016 RAB LIGHTING Inc.
Northvale, New Jersey 07647 USA
rabweb.com
Visit our website for product info
Answered promptly [email protected]
ND4R ND4S EM NEXTGEN IN-0416
TROUBLESHOOTING
1. Check that the line voltage at the fixture is correct. Refer
to wiring directions.
2. Is the fixture grounded properly?
3. For questions on compatibility of dimmers purchased
separately refer to www.rabweb.com
4. If the LED is blinking the fixture may be overheating.
Remove the Trim assembly and if the fixture is labeled
‘BLINKING LIGHT OF THIS THERMALLY PROTECTED
LUMINAIRE MAY INDICATE OVERHEATING’ allow the
fixture to cool down. Determine cause of overheating and
remove. Fixtures with this label have a thermal protector
that turns fixture off above a certain temperature. It will
automatically restart when cool.
ND4R/ ND4S
LED EMERGENCY BATTERY BACK UP INSTALLATION INSTRUCTIONS
Thank you for buying RAB lighting fixtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: [email protected]