background image

Specifications

Coverage:

1000 square feet,

up to 32’ from the sensor

Detection Zone:

180

º

in 18 zones

32’ range

Detection Pattern:

Note:

Detection of sedentary small move-

ment (desk work) within 18’

Time Adjustment:

8 seconds to 15 minutes

after motion stops (approximate)

Detection Indicator:

Red LED

Energy Codes:

Complies with California Title 24

Switching Capacity:

120v: 800w Incandescent & 

Fluorescent

277v: 1200w Incandescent & 

Fluorescent

Minimum Load:

None

Power Consumption:

Negligible

Wiring:

Replaces single pole wall switch, 

3 wire system where neutral & hot

are present.

Temperature Range:

-4

º

F to +104

º

F

(-20

º

C to +40

º

C)

Humidity Range:

93% relative humidity

Approvals:

UL Listed Photocontrol

UL Standard 773A

Weight:

3.3 oz. (no box)

Parts List:

LOS800 Sensor

Matching Wall Plate

2 matching wall plate screws

2 sensor mounting screws

Dimensions:

A

=4.06” (103mm)  

B

=1.69” (43mm)

C

=2.25” (57mm)    

D

=2.56” (65mm)

E

=1.25” (32mm)    

F

=.5” (13mm)

G

=1.68” (43mm)

A D

B

E

C

G

F

5’

32’

Side View                 

32’

Locate the LOS800 where it has

an unobstructed view of the room,

particularly the areas normally

occupied by people. Ideal mount-

ing height is 3.5 to 4.5 feet above

the floor.

If people cannot see the sensor

lens from their normal positions in

the room, the sensor will not detect

their presence.

High cabinets, walls, doors and

other obstructions may limit the

sensor’s view of the entire room. If

obstructions can be moved the

sensor will have a better view. If

the areas obstructed are not areas

normally occupied, the sensor will

still be able to see normal occupancy.

Cabinet obstructs sensor’s

view of active area

Obstruction moved, sensor

has full view

If the room is L shaped or the sensor’s

view is badly obstructed from the

door switch location, use the

LOS2500 ceiling mounted sensor

instead of the LOS800.

Ceiling mounted LOS2500

sensor with 360º detection

Do not locate sensor over or looking

at heating vents, baseboard

heaters, hanging plants or air 

conditioners.

Do not locate sensor where it will

view direct sunlight.

If the sensor’s location gives it a

view of the other rooms or hallways,

lights will be turned on when

movement is detected in these

adjacent areas. If this is undesirable,

the sensor’s detection zone may

be restricted by covering a portion

of the lens with a white paper label

or tape.

Sensor has view of

adjacent area

Selecting A Location

1

Sensor

Sensor

Sensor

Top View                            50’

50’

2

3

Summary of Contents for LOS800

Page 1: ...ltiple sensors Superb small movement sensitivity within 18 feet Great for sedentary office use No dead spots with 18 sensing fingers Easy Installation Works with electronic ballasts No minimum load requirement Replaces single pole wall switches without additional wiring Decorator style rectangular switchplate included Only 1 2 protrusion from switch plate No adjustments required for most installat...

Page 2: ...eight is 3 5 to 4 5 feet above the floor If people cannot see the sensor lens from their normal positions in the room the sensor will not detect their presence High cabinets walls doors and other obstructions may limit the sensor s view of the entire room If obstructions can be moved the sensor will have a better view If the areas obstructed are not areas normally occupied the sensor will still be...

Page 3: ...efore installing All wiring should comply with local electrical codes and requires a qualified electrician Make sure the total lighting load connected to the LOS800 does not exceed the following 120v 800w Incandescent Fluorescent 277v 1200w Incandescent Fluorescent Exceeding the wattage limits may damage the unit To switch more wattage an electrician can install a relay to handle the load Do not u...

Page 4: ...screwdriver for more time delay Hole for Coverplate screw Over tightening screw will strip threads 5 6 Lights do Not Turn On 1 Check that the lamps and fixtures work wiring exactly matches the wiring diagram wiring polarity is correct power is on sensor has warmed up for 3 minutes off auto switch is not OFF 2 Make sure sensor s view of the room is not blocked Lights do Not Turn Off 1 Check that th...

Page 5: ...lem If your unit is out of warranty or the damage is unrelated to its original manufacture return your unit directly to RAB with a check for 20 00 payable to RAB Lighting We will repair or replace the unit Under no circumstances shall we be liable for any incidental or con sequential damages arising out of or in connection with the use or performance of this product or other indirect damages with ...

Reviews: