TROUBLESHOOTING
1. Check that the line voltage at fixture is correct. Refer to
wiring directions.
2. Is the fixture grounded properly?
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to
touch. Do not clean or maintain while fixture is ener-
gized.
1. Clean glass lens with non-abrasive glass cleaning
solution.
2. Do not open fixture to clean the LED. Do not touch the
LED.
LIGHT
FIXTURE
(+)LINE
BLACK
(-)COMMON
WHITE
GROUND
GROUND
WIRING
Universal voltage driver permits operation at 120 to 277VAC,
50 or 60Hz.
1. Connect the black fixture lead to the (+)
LINE supply lead.
2. Connect the white fixture lead to the (-)
COMMON supply lead.
3. Connect the bare copper Ground wire from fixture to
supply ground.
Easy Installation & Product Help
Tech Help Line
Call our experts 888 RAB-1000
©2012 RAB LIGHTING Inc.
Northvale, New Jersey 07647 USA
rabweb.com
Visit our website for product info
Answered promptly [email protected]
ALED5T52
ALED5T78
ALED5T78 IN-0514
Fig. 2
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru
277V, 50 or 60 Hz. 0-10V control wires must be rated for 300V
minimum. For 0-10V Dimming, follow the wiring directions as
in fig. 2.
1. Connect the black fixture lead to the (+) LINE supply lead.
2. Connect the white fixture lead to the (-) COMMON supply
lead.
3. Connect the GROUND wire from fixture to supply ground.
Do NOT connect the GROUND of the dimming fixture to
the output.
4. Connect the purple fixture lead to the (V+) DIM lead.
5. Connect the gray fixture lead to the (V-) DIM lead.
6. Cap the yellow fixture lead. Do NOT connect.