BOILER SYSTEM DIAGNOSTICS - Oil Burner Will Not Fire 

PROBLEM 

POSSIBLE CAUSE 

SOLUTION 

Not reaching rated pressure 
flow 

Not activating boiler controls 

Correct the fluid problem first - See fluid systems diagnostics 

Thermostat on low setting 

Thermostat set too low 

Set thermostat to an output temperature requiring heating. 

No or low fuel in tank 

Burner no getting adequate fuel 

Check fuel and bring to proper levels. Inspect fuel tank for water or debris. 

Low fuel shut-off control activated.  Full featured equipment may have a shut off if fuel is low. 

No air movement through 
stack 

No air being supplied 

Ensure that the blower is working and that the air band or damper is properly adjusted and in 
good repair. 

Thermal reset tripped 

Press the thermal reset button on burner motor. If the reset trips again an additional problem 
must be sought. 

Burner motor or capacitor is bad 

If motor does not turn, first check thermostat/press switch, the motor starting capacitor and 
finally the burner motor itself. 

Fuel in the fuel tank 

Contaminated fuel in the tank 

Ensure that the proper clean fuel is being used. If not, siphon any debris or water from the tank. 

Improper fuel in the tank 

If the improper fuel is found in the tank, drain and rinse the tank, then fill with proper fuel. 

Low fuel shut-off sensor stuck or 
faulty 

Check the sensor. The assembly may need to be removed to un-stick the float or to replace it 
completely. 

Water in the fuel filter bowl 

Water in fuel supply 

Drain water from the tank promptly to prevent rusting. If fuel delivery problems persist, check the 
fuel pump for rust. 

Debris in the fuel filter bowl 

Clogged strainer 

If the fuel strainer or in-line filter is clogged, clean or replace. 

Clogged fuel nozzle 

Replace if there is any evidence of clogging or debris. 

Clogged fuel line 

Check lines for clogging and clear if necessary. 

Water comes out drain at 
bottom of tank 

Water in fuel supply 

Check only if no fuel in the filter bowl - Drain the tank and check for rust. If problem persists, fuel 
pump should be checked for rust. 

Cannot smell or see fuel at 
stack 

No fuel being supplied 

Check fuel delivery and correct any problems. 

No fuel to bleed valve 

Air leak to pump 

Ensure that air is not entering through the lines or connections. 

Broken fuel line 

Ensure that the fuel line is connected and is not broken/punctured. 

Clogged fuel filter 

Check any clogging that exists in the fuel filter 

Clogged fuel inlet line 

Check any clogging that exists in the fuel inlet line. 

Frozen fuel pump 

If the fuel pump is frozen it will need replaced. 

Broken fuel pump coupling 

Check pump coupling if direct or belt driven. Replace or tighten or replace the drive belts if 
needed. 

Summary of Contents for EZO2703G

Page 1: ...Commercial and Industrial Hot Water Gas and Diesel Driven Oil Fired OWNER S MANUAL MODEL PK0702 Call 1 800 344 3371 Email service qvtools com Website www qvtools com...

Page 2: ......

Page 3: ...structions could result in personal injury and or property damage Table of Contents IMPORTANT SAFETY INFORMATION 3 SPECIFICATIONS 7 INTRODUCTION 9 OPERATING INSTRUCTIONS 10 CHEMICAL APPLICATION 12 WIN...

Page 4: ...OPERATORS AND MUST ALWAYS BE ATTENDED DURING OPERATION WARNING To reduce the risk of injury read operating instructions carefully before using WARNING Use protective eyewear and clothing when operati...

Page 5: ...ts Do not touch electrical components while standing in water or when hands are wet Always make sure machine is disconnected from power source before servicing WARNING Risk of asphyxiation Use this pr...

Page 6: ...times WARNING Protect from freezing WARNING Trigger gun kicks back Hold with both hands 10 It is important to keep your machine from freezing in order to keep it in its best working condition Failure...

Page 7: ...f alcohol prescription medications or drugs 16 Some of the maintenance procedures involved in this machine require a certified technician these steps are indicated throughout this manual Do not attemp...

Page 8: ...d Gas Diesel Rev 4 7 2016 SPECIFICATIONS Commercial Hot Water Gas Oil Fired MODEL GPM PSI BURNER OIL PRESSURE PSI BTU HP ENGINE DRIVE ELECTRIC START BURNER EZO2703G 3 2700 130 300 000 6 5 KOHLER DIREC...

Page 9: ...8 Oil Fired Gas Diesel Rev 4 7 2016...

Page 10: ...manual They know what information the end user needs in order to get the optimum performance from their pressure washer Please read carefully This manual contains information that will be specific for...

Page 11: ...Gas Engine Oil level The engine is a 4 cycle and uses 10W30 detergent oil Refer to Glossary or engine manual Diesel Engine Refer to engine operation manual included with your pressure washing unit fo...

Page 12: ...coil and the burner is firing condensation may form at times on the coil and drip down into the burner compartment This can be particularly noticeable on cold humid days giving the false appearance o...

Page 13: ...ure washer for any damage or required maintenance If your machine is to be exposed to cold weather please refer to winter pump coil instructions found in this manual If possible do not allow unit to r...

Page 14: ...it is stored at temperatures below freezing 1 All water must be drained or blown via compressed air from system Connect a short piece of male fitted garden type hose on to the female inlet on the pump...

Page 15: ...in the previous section Alternate methods may not completely protect the components Damage from freezing is not a warrantable item Water Condition Use a softener on your water system if local water is...

Page 16: ...s or leaks Replace accordingly Recommendation for Oil Changes and Component Replacement 1 Change the oil in the pump after the first 50 hours and every 500 hours after the initial oil change Use SAE 3...

Page 17: ...placements 1 Change engine oil after first 5 hours and every 100 hours after the initial oil change Use 10w 30 engine oil 2 Replace Spark Plug every 100 hours 3 Change air cleaner element every 100 ho...

Page 18: ...opriate lubricant Use 10W30 detergent oil BURNER The burner heats the water in hot water pressure washers It is located under the coil and may be powered by furnace oil or diesel fuel BACK FLOW PREVEN...

Page 19: ...18 Oil Fired Gas Diesel Rev 4 7 2016 COMPONENT IDENTIFICATION Commercial Model 10 Gallon Poly Fuel Tank Burner Switch and Thermostat Gasoline Engine Coil Skin...

Page 20: ...ired Gas Diesel Rev 4 7 2016 Direct Driven Pump Assembly Chemical Injector Water Inlet Unloader Burner Control Pressure Switch Safety Relief Valve Temperature probe Hot Water Outlet Quick Connector Wa...

Page 21: ...nk Interior Top Cover Removed Pressure Wand Assembly Wand Nozzles Black Nozzle for Downstream Chemical Application Nozzle Quick Coupler Spray Gun High Pressure Hose Trigger Coil Coil Skin outer stainl...

Page 22: ...e not using soap use a different color Pressure too high Wrong nozzle size Make sure you have the right nozzle size Unloader adjusted improperly or damaged Check pressure of pump with a pressure gauge...

Page 23: ...above the part that attaches directly into pump If burner comes on replace pressure switch If burner does not come on make sure there is current going through switch consult a professional for this i...

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...r improper installation and operation will automatically void this warranty All labor repairs are to have an PowerKing pre authorized repair number PARN In order to receive a PARN please email a copy...

Page 29: ...of issues with pressure washers This manual is not intended for use by non technical personnel It is advised to always refer to competent technical personnel when repairs are advised to avoid equipme...

Page 30: ...er If electric start try starting using the recoil starter Bad plug Check spark plug and replace if necessary Carbon deposits can indicate a fouled plug or too much fuel Plug does not fire Poor connec...

Page 31: ...replace if gauge is faulty Pump packings bad If low pressure persists pump packings may need replaced Low pressure low flow Volume Improperlyadjusted If unit has volume adjustment it may need readjust...

Page 32: ...n a gravity fed system Float valve stuck optional If float valve is stuck in the up position water can not enter the float tank Unstick valve if possible of replace if necessary Turbulence in floattan...

Page 33: ...cale prevention Pump not delivering the rated pressure See low pressure or low flow diagnostics High water supplypressure Check inlet water supplyfor excessive pressure Unloader flow cycleswith system...

Page 34: ...verting flow to bypass readjust using the pressure gauge Nozzle too large Ensure the proper sized nozzle is being used Unloader pressure leaks from main spring or adjusting bolt Shaft O ring in valve...

Page 35: ...e Weep gun optional If a weep gun has been installed check the gun valve seat to ensure it is functioning properly Damage gun valve ball or seat Inspect trigger gun valve assemblyfor damage or ware to...

Page 36: ...am side of the pump Check fittings connections and ensure the inlet line is fully submerged into the chemicaljug Chemical dried up in the injector Inspect and clean as necessary Chemical foot strainer...

Page 37: ...tank then fill with proper fuel Low fuel shut off sensor stuckor faulty Check the sensor The assemblymay need to be removed to un stick the float or to replace it completely Water in the fuel filterb...

Page 38: ...on transformer with a volt meter Ignition transformer bad Using a volt meter ensure that the transformer is supplying the proper voltage Electrode gap improperlyset Check the gap and readjust if neces...

Page 39: ...ntilation if the original system is inadequate Flame has yellowtip Flame speed improper Check for proper gas pressure while burner is operating Flame comes out from under burnerhousing Insufficient ai...

Page 40: ...still no current flow when activated switch may need replacement Switch does not activate Plunger fouled orstuck Check pressure plunger to see if it will travel freely If not the passage may need cle...

Page 41: ...ler fires whenthermostat jumped but will not fire with thermostat in circuit Thermostat bad Replace Thermostat Boiler will not firewhen thermostat jumped Problem elsewhere insystem Continue with boile...

Reviews: