Section VIII - Troubleshooting
Integrated Dryer Troubleshooting
(continued):
Noisy unit:
m
ountings
loose
.
B
ent
fan
Blade
.
f
an
motor
Bearing
worn
.
r
efrigerant
flooding
Back
.
c
omPressor
oil
charge
low
.
Frosted suction line:
e
xPansion
valve
and
/
or
hot
gas
ByPass
out
of
adjustment
.
Unit runs but air temperature is
high:
note: o
utlet
air
temPerature
gauge
may
read
higher
than
actual
temPeratures
at
low
air
flow
conditions
.
r
efrigerant
leak
.
e
vaPorator
controls
set
too
high
.
f
ilter
/
dryer
clogged
.
r
efrigerant
shortage
.
d
irty
condenser
.
a
ir
in
system
.
c
omPressor
inefficient
.
e
vaPorator
control
(
s
)
stuck
.
d
efective
insulation
.
a
ir
overload
.
u
nit
too
small
.
h
igh
amBient
.
e
ntering
air
temPerature
too
high
.
t
ighten
mounting
,
etc
.
s
traighten
or
rePlace
Blade
.
r
ePlace
.
c
heck
exPansion
valve
,
adjust
,
rePair
or
rePlace
. c
heck
crankcase
heater
.
c
heck
oil
level
.
a
djust
the
hot
gas
ByPass
valve
to
Bring
the
suction
Pressure
into
the
ProPer
range
.
l
ocate
with
leak
detector
. r
ePair
or
rePlace
defective
Part
.
c
orrect
setting
.
r
ePlace
.
r
ePair
leak
and
recharge
.
c
lean
condenser
.
c
heck
reason
,
rePair
,
vacuum
,
recharge
.
r
ePair
or
rePlace
.
r
ePair
as
required
,
adjust
.
r
ePair
.
r
educe
load
.
a
dd
unit
or
rePlace
.
r
educe
or
change
location
.
l
ower
entering
air
temPerature
.
82
Quincy Compressor-QGB
™