background image

ENGLISH

 

 

8 - Edition 10/2014 Cod. 2200780133  00 - 

13.0 DIMENSIONS AND TECHNICAL DATA (QPNC1600) 

MODD. 

WEIGHT 

Kg. (lb) 

Freon 

R404A Kg. (lb)

 

 

Bar (psi) 

MAX.

 

60 Hz 

60 Hz 

60 Hz 

QPNC1600 

380 (837) 

6,600 (14,55) 

9740 (13,06) 

1250 (1,67) 

bar 13 (188) 

Reference conditions: 

Limit conditions:

 

V460-3-60 

V460-3-60 

Ambient temperature 

38 °C (100 °F) 

Max. ambient temperature 

45 °C (113 °F) 

Inlet air temperature 

38 °C (100 °F) 

Min. ambient temperature 

5 °C (41 °F) 

Working pressure 

7 bar (101 psi) 

Max. inlet air temperature 

55 °C (131 °F) 

Dew point in pressure 

4 °C (39 °F)

 

Max. working pressure

 

13 bar (188 psi) 

14.0 MACHINE ILLUSTRATION 

14.1 GENERAL LAY-OUT  

(QPNC0750 - QPNC1000 - QPNC1250 - QPNC1600)

 

Refrigerant compressor 

Freon filter 

Condenser 

Capillary 

Motor fan 

Pressure switch of motor fan 

Evaporator 

10 

Pressure switch of the high pressure 

Condensate drain 

11 

Liquid separator 

Hot gas by pass valve 

12 

Pressure switch of the min. pressure 

Nominal

 

Power 

W (hp)

 

Nominal

 

Power 

W (hp)

 

FIG. 8 

11 

10 

12 

(A)

 

AIR INLET

 

(B)

 

AIR OUTLET

 

ELECTRICAL CABLE 

CONDENSATE 
DRAINING  

Refrigerant gas 

(1)

 

GWP 

100  (2)

 

R-404A

3800 

(1)

According to ISO 817

(2)

According to EN-378-1

MODD. 

L  

(mm / in) 

W  

(mm / in) 

H  

(mm / in) 

QPNC1600 

1020 (40,1) 

1123 (44,2) 

1551 (61) 

MODD. 

QPNC1600 

FLANGED 

" DN 125 " 

FLANGED 

" DN 125 " 

Summary of Contents for QPNC1600

Page 1: ...200780133 00 Edition 10 2014 1 INSTRUCTION AND MAINTENANCE MANUAL DRYERS QPNC1600 QPNC1800 QPNC2500 QPNC3000 Code 2200780133 01 Edit 10 2014 READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER ...

Page 2: ...anual is an integral part on the dryer Read this manual carefully before carrying out any operations on the dryer The installation of the dryer and all operations involving it must be performed in conformity with the regulations in force concerning electric plants and personal safety CHARACTERISTICS AND SAFETY PRECAUTIONS BEFORE REMOVING THE PROTECTIVE GUARDS TO CARRY OUT ANY MAINTENANCE ON THE MA...

Page 3: ...tube 7 and goes back to the evaporator where it produces the refrigerating effect Due to the heat exchange with the compressed air which passes through the evaporator against the stream the refrigerant evaporates and goes back to the compressor for a new cycle The circuit is equipped with a bypass system for the refrigerant this intervenes to adjust the available refrigerating capacity to the actu...

Page 4: ...PTION OF DANGER SIGNALS 1 Dangerous electricvoltage 2 Air not fit for breathing 3 High pressure 4 Fan rotating 5 Hot parts 6 0 DANGER ZONES 6 1 DANGER ZONES 1 2 3 4 Risks present on the whole machine FIG 2 4 1 1 4 4 1 1 2 3 1 1 3 1 1 1 3 3 2 3 3 1 2 3 1 1 ...

Page 5: ...ENGLISH Cod 2200780133 00 Edition 10 2014 5 7 0 SAFETY DEVICES 7 1 SAFETY DEVICES 1 Cooling fan shield 3 Earth 2 Shield FIG 3 1 3 1 1 3 2 ...

Page 6: ... temperature 3 C 37 4 F Max room temperature 45 C 113 F compulsory Max inlet allowed temperature 55 C 131 F Max temperature of incoming air 55 C 131 F Max working pressure 13 bar 188 F 10 0 TRANSPORT AND HANDLING The machine must be transported as shown in the following figures 11 0 UNPACKING CUTTING THE METAL STRAPPING IS A DANGEROUS OPERATION DO NOT ABANDON THE CUT PIECES IN THE ENVIRONMENT Afte...

Page 7: ...AVE ACCESS TO THE ELECTRIC PANEL SWITCH OFF THE POWER BEFORE OPENING THE DOOR OF THE ELECTRIC PANEL COMPLIANCE WITH THE REGULATIONS IN FORCE CONCERNING ELECTRIC PLANTS IS FUNDAMENTAL FOR OPERATOR SAFETY AND FOR THE PROTECTION OF THE MACHINE 12 3 CONNECTION TO THE COMPRESSED AIR NETWORK Fit a manual interception valve Ref 1 between the machine and the compressed air network so that the dryer may be...

Page 8: ...working pressure 13 bar 188 psi 14 0 MACHINE ILLUSTRATION 14 1 GENERAL LAY OUT QPNC0750 QPNC1000 QPNC1250 QPNC1600 1 Refrigerant compressor 7 Freon filter 2 Condenser 8 Capillary 3 Motor fan 9 Pressure switch of motor fan 4 Evaporator 10 Pressure switch of the high pressure 5 Condensate drain 11 Liquid separator 6 Hot gas by pass valve 12 Pressure switch of the min pressure Nominal Power W hp Nomi...

Page 9: ...g pressure 13 bar 188 psi 14 1 GENERAL LAY OUT QPNC1800 QPNC2500 QPNC3000 Nominal Power W hp Nominal Power W hp 1 Refrigerant compressor 7 Freon filter 2 Condenser 8 Capillary 3 Motor fan 9 Pressure switch of the high pressure 4 Evaporator 10 Pressure switch of the min pressure 5 Condensate drain 11 Liquid separator 6 Hot gas by pass valve 12 Pressure switch of motor fan 1 9 10 12 11 5 7 8 4 FIG 8...

Page 10: ...en indicator of voltage Running Ref 10 Red indicator of alarm for Condensate drain Ref 11 Red indicator of alarm for High Low pressure Fan motor protection ICON MODE FUNCTIONS ALARM OFF No active alarms ON Probe failure alarm High Low temperature alarm COMPRESSOR OFF Dryer off FLASH Maintenance warning ON Dryer on FAN OFF Fan off FLASH n a ON Fan on 2 Alarms 3 Power ON 4 Fan ON 5 PDP temperature 6...

Page 11: ...Close the cock Ref 1 Fig 10 Remove the panel Ref 5 Fig 10 Release the pressure in the dryer by pressing the condensate drain TEST pushbutton locate on the steam trap Ref 2 Fig 10 Switch off the machine Turn the switch in position STOP Ref 3 Fig 10 Turn on the supply automatic differential switch Ref 4 Fig 10 HOT PARTS INSIDE Remove the stopper Ref 6 Remove the filter Ref 7 Clean the filter Ref 7 w...

Page 12: ...e dryer is working under bad conditions of condensation Clean the filter from the condensate drain Check the condensate drain Check the flow rate of treated air Check the room temperature Check the air temperature at the drier inlet Clean the condenser Check the operation and the calibration of the press switch Check the good operation of the fan 3 The compressor head is very hot 55 C 131 F Make r...

Page 13: ...rning icon NOT fashing label H1 flashing High PDP call for service refrigerant leak flow rate inlet temperature exeeding the limit Warning icon NOT fashing label L1 flashing Low PDP call for service hot gas by pass valve out of order ambient temperature lower then limits EE ALARM EE alarm is shown when internal EPROM errors happens if this warning will appear the dryer will stop running The error ...

Page 14: ...SH 14 Edition 10 2014 Cod 2200780133 00 SE ALARM After 4000Hrs the controller will issue a SE warning This is the maintenance due warning How to reset the maintenance warning follow steps 1 to 6 1 2 3 4 5 6 ...

Page 15: ...arts running and stop it after the air compressor has been stopped The compressed air piping will be free of condensate only by doing so The drier must be kept running during all the time the air compressor is running WARNING if the drier is switched off before starting it again wait at least 5 minutes in order to allow the pressure balancing BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATO...

Page 16: ...nt A dew point different from the rated one generally depends on causes which are not attributable to their operation Ref 1 Closing cap Ref 2 Adiusting screw WORKING PRESSURES AND TEMPERATURES OF R404A SUCTION SIDE OF REFRIGERATION COMPRESSOR Evaporat Temperat C F Evaporating Pressure bar psi RATED VALUES Temperat 20 C 68 F 2 3 35 6 37 4 R404A 5 4 5 6 78 3 81 2 1 2 ...

Reviews: