START-UP AND OPERATION

 

PRELIMINARY CONTROLS

 

Before starting the dryer, check for:

1.

The correct connection to the compressed air piping: 
remember to remove end caps on the dryer inlet and 
outlet.

2.

The correct connection to the condensate drainage 
system.

3.

The correct power supply.

 

STARTING AND STOPPING

 

Always start the dryer at least 5 minutes before the air 
compressor starts running and stop it after the air 
compressor has been stopped in order to keep the 
compressed air piping free of condensate. The dryer must 
be kept running while the air compressor is running. 

 

PRESSURE DISCHARGE PROCEDURE

 

See Figure 13 on Page 10.

1.

Isolate the dryer from the air system (1).

2.

Release the pressure in the dryer by pressing the 
condensate drain “TEST” pushbutton located on the 
auto drain (2).

3.

Switch off the machine by turning the STOP button to 
position “0 OFF” (3).

4.

Turn off the power supply by opening the circuit 
breaker or fused disconnect switch (4).

 

CALIBRATIONS

 

HOT GAS BYPASS VALVE

 

These valves have already been calibrated and they do 
not require any adjustment. A dew point different from the 
rated one generally is caused by factors which are not 
attributable to their operation. Figure 10 shows:

1.

Closing cap

2.

Adjusting screw

This valve maintains the 
refrigerant suction pressure in 
varying load conditions. The 
dryer will run from no load to 
full load conditions without 
freeze-up. The operation of this 
valve is automatic. If the valve 
needs adjustment, turn the 
adjusting stem clockwise to 
raise the suction pressure, and 

counterclockwise to lower the suction pressure. This 
adjustment should be made under a no-load condition if 
possible. When the adjustment is made, turn one quarter 
of a turn at a time, and wait 3 to 5 minutes between 
adjustments. Careful adjustment of this valve is necessary 
for normal operation of the air dryer. Hot gas bypass 
valve adjustment may be made by maintenance 
personnel. (See Figure 10.)

 

Table 2 — WORKING PRESSURES AND 
TEMPERATURES OF R134A

Before making any change to the machine,
ensure that the electric power supply has
been disconnected. Wait at least two hours
before starting up after any machine
movement (transport or handling).

The following procedure must be per-
formed by skilled personnel approved by
the manufacturer.

 

If the dryer is switched off, before starting
it again, wait at least 5 minutes to allow
for pressure balancing.

SUCTION SIDE OF

REFRIGERATION COMPRESSOR

 

Evaporating 
Temperature

 

°F (°C)

 

Evaporating 

Pressure

 

psi (bar)

 

RATED VALUES 

AT AMBIENT 

TEMPERATURE 

+68 °F (+20 °C)

33.8 - 35.6

(1 - 2)

 

R134A

 

29 - 31

(2.1 - 2.3)

2

1

FIGURE 10 — 
BYPASS VALVE

Summary of Contents for QPNC 10

Page 1: ...NON CYCLING REFRIGERATED AIR GAS DRYERS QPNC 10 to QPNC 50 OPERATOR S MANUAL ...

Page 2: ...DATE OF PURCHASE MODEL SERIAL NO Record above information from nameplate Retain this information for future reference ...

Page 3: ...tions 5 Locating the Dryer 5 Positioning 5 Electrical Connection 5 Connection to the Compressed Air System 6 Dimensions and Technical Data 6 Start Up and Operation 8 Preliminary Controls 8 Starting and Stopping 8 Calibrations 8 Controls 9 Operation 9 Maintenance 10 Maintenance Schedule 10 Cleaning Automatic Condensate Drain Filter 10 Cleaning the Condenser 10 Air Dryer Service Checklist 11 Trouble...

Page 4: ...eathing Air Other special precautions must also be taken Refer to OSHA 29 CFR 1910 134 DISCLAIMER OF WARRANTY If this unit is used to produce breathing air the special equipment and precautions expressed in OSHA 29 CFR 1910 134 for specifications of the necessary equipment and special precautions to make Breathing Air MUST BE used or any warranties are VOID and manufacturer disclaims any liability...

Page 5: ...chnical assistance center approved by the manufacturer and insist on the use of original spare parts Failure to comply with the above may cause damage to the machine Before removing the protective guards to perform any maintenance on the machine switch off the electric power supply and discharge the residual pressure inside the unit All work on the unit however slight must be performed by professi...

Page 6: ...ng 1 READ ALL INSTRUCTIONS FULLY 2 WIRING BREAKERS Wiring breakers and other electrical equipment must conform to local and national electrical codes Do not operate this unit with damaged wiring or after the unit or air handling parts have been dropped or damaged in any manner Notify authorized service facility for examination repair or other adjustments 3 USE SUITABLE PARTS ACCESSORIES Do not use...

Page 7: ...Ensure that the operator can see the whole machine from the control panel and can check for the presence of unauthorized persons in the machine s vicinity ELECTRICAL CONNECTION 1 Check that the supply voltage is the same as the value indicated on the machine s identification plate 2 Check the condition of the line leads and ensure that there is an efficient earth ground lead 3 Dryer must be wired ...

Page 8: ...CONDENSATE PIPE DIMENSIONS AND TECHNICAL DATA FIGURE 7 DIMENSIONS FIGURE 8 CONNECTION 1 ATTENTION Dryer must be wired to the power supply through a fused disconnect switch or circuit breaker in accordance with national and local electrical codes Minimum 24 in 0 6 m on all sides 2 Type L in mm W in mm H in mm QPNC 10 13 78 350 20 09 510 19 05 484 QPNC 15 13 78 350 20 09 510 19 05 484 QPNC 25 13 78 ...

Page 9: ...Hz V115 60Hz V230 60Hz V115 60Hz V230 60Hz V115 60Hz QPNC 10 41 9 19 0 397 0 180 0 161 120 0 164 122 0 040 30 0 040 30 0 201 150 0 204 152 232 16 QPNC 15 44 1 20 0 463 0 210 0 205 153 0 212 158 0 040 30 0 040 30 0 245 183 0 252 188 232 16 QPNC 25 55 1 25 0 639 0 290 0 312 233 0 306 228 0 040 30 0 040 30 0 353 263 0 346 258 232 16 QPNC 35 59 5 27 0 970 0 440 0 390 291 0 386 288 0 040 30 0 040 30 0 ...

Page 10: ...peration Figure 10 shows 1 Closing cap 2 Adjusting screw This valve maintains the refrigerant suction pressure in varying load conditions The dryer will run from no load to full load conditions without freeze up The operation of this valve is automatic If the valve needs adjustment turn the adjusting stem clockwise to raise the suction pressure and counterclockwise to lower the suction pressure Th...

Page 11: ...o the actual cooling load This is achieved by injecting hot gas under the control of the valve 9 This valve keeps the refrigerant pressure constant in the evaporator and therefore keeps the dew point from decreasing below 32 F 0 C in order to prevent the condensate from freezing inside the evaporator The dryer runs completely automatically it is calibrated at the factory for a dew point of 39 F 4 ...

Page 12: ...TOP button to position 0 OFF 3 4 Turn off the supply by opening the circuit breaker or fused disconnect switch 4 5 Remove the panels 5 6 Remove the stopper 6 7 Remove the filter 7 8 Clean the filter 7 with a jet of air working from inside to outside 9 Install the filter and affix the plug 7 6 10 Close the panels 5 FIGURE 13 MAINTENANCE CLEANING THE CONDENSER The condenser must be cleaned every mon...

Page 13: ..._______________________ 5 Air out temperature F ________________________________________________________________________________ 6 Air in pressure PSIG __________________________________________________________________________________ 7 Air out pressure PSIG ________________________________________________________________________________ 8 Refrigerant suction pressure when unit is operating PSIG _...

Page 14: ... The dryer is working under bad conditions for air cooled condenser 1a Clean the condensate drain filter 1b Check the condensate drain 2a Check the flow rate of treated air 2b Check the room temperature 2c Check the air temperature at the dryer inlet 3a Clean the condenser 3b Check the operation and the calibration of the fan cycling press Switch 3c Check the operation of the fan C The compressor ...

Page 15: ...The motor hums and does not start 1 The line voltage is too low 2 The machine was switched off and on again without leaving enough time for pressure balancing 3 The starting system of the motor is defective 1a Contact the electric power company 2a Wait a few minutes before starting the machine again 3a Check the running and starting relays and condensers if installed F The machine compressor has s...