61
Installation and Maintenance
Service Manual
8.Remove motor and motor support
8.Remove motor and motor support
Remove the 4 tapping screws
the motor.Pull out the lead-out wire and
remove themotor. Remove the 2 tapping
screws
motor support. Lift motor
support to re-move it.
Procedure
Steps
motor support
motor
Remove the nut
the blade and
thenremove the axial
blade.
axial
blade
9.Remove 4-way valve assy
assyUnscrew the fastening nut of the
4-way ValveAssy coil and remove the
coil. Wrap the 4-way Valve Assy with
wet cotton and unsolderthe 4 weld
spots connecting the 4-way ValveAssy
to take it out.(Note: Refrigerant
shouldbe discharged
Welding
processshould be as quickly as possible
and keepwrapping cotton wet all the time.
Be sure notto burn out the lead-out wire
of compressor.
4-way valve assy