INSTALLATION

INSTALLATION SITE

Install the battery charger as close as possible to the batteries in a dry and airy 

spot, to allow the correct operation of the device at full power. 

The battery charger can be installed on a horizontal surface or vertical wall paying 

attention that the output connector faces downwards.

In case of battery chargers connected in parallel (current sharing mode), install-

ing one next to the other.

The battery charger must be fixed to the support surface with screws strong 

enough to support its weight, paying attention that they do not weaken or cause 

cracks to the boat structure.

Vertical installation is recommended since the natural convection of the heat will 

favour the cooling of the device.

The perimeter of the battery charger (excluding the support base) must be kept at 

a distance from walls or objects by a minimum of 5 cm.

WARNING: 

the battery charger must be used only with re-chargeable lead/liquid electrolytic batteries (open or 

sealed), Gel, AGM, Optima

® 

, Li-Ion.

WARNING: 

the battery charger can not be used to recharge non rechargeable batteries.

NECESSARY EQUIPMENT FOR INSTALLATION 

Depending upon model, use the batteries and cables on the output terminals as specified in the following table:

MODEL

SBC 1100 NRG+ FR

SBC 1200 NRG+ FR

SBC 1450 NRG+ HR

SBC 1950 NRG+ HR

SBC 2450 NRG+ HR

Battery voltage

12 V

24 V

Battery capacity

360 ÷ 600 Ah

450 ÷ 1000 Ah

270 ÷ 600 Ah

360 ÷ 800 Ah

450 ÷ 1000 Ah

Minimum output cable size

25 mm

2

35 mm

2

25 mm

2

35 mm

2

35 mm

2

Number of battery cells

6

12

MODEL

SBC 1100 NRG+ FR

2 units in parallel

SBC 1200 NRG+ HR

2 units in parallel

SBC 1450 NRG+ HR

2 units in parallel

SBC 1950 NRG+ HR

2 units in parallel

SBC 2450 NRG+ HR

2 units in parallel

Battery voltage

12 V

24 V

Battery capacity

720 ÷ 1200 Ah

900 ÷ 2000 Ah

540 ÷ 1200 Ah

720 ÷ 1600 Ah

900 ÷ 2000 Ah

Minimum output cable size 

(battery charger-junction “J”)

25 mm

2

35 mm

2

25 mm

2

35 mm

2

35 mm

2

Minimum output cable size 

(junction “J” - battery)

50 mm

2

95 mm

2

50 mm

2

70 mm

2

95 mm

2

Number of battery cells

6

12

MODEL

SBC 1100 NRG+ FR

3 units in parallel

SBC 1200 NRG+ HR

3 units in parallel

SBC 1450 NRG+ HR

3 units in parallel

SBC 1950 NRG+ HR

3 units in parallel

SBC 2450 NRG+ HR

3 units in parallel

Battery voltage

12 V

24 V

Battery capacity

1080 ÷ 1800 Ah

1350 ÷ 3000 Ah

810 ÷ 1800 Ah

1080 ÷ 2400 Ah

1350 ÷ 3000 Ah

Minimum output cable size

(battery charger-junction “J”)

25 mm

2

35 mm

2

25 mm

2

35 mm

2

35 mm

2

Minimum output cable size 

(junction “J” - battery)

95 mm

2

150 mm

2

95 mm

2

120 mm

2

150 mm

2

Number of battery cells

6

12

For the single battery chargers, the wires connected to the output terminals must have a maximum length of 4 meters.

For the length of the output wires in case more battery chargers are connected in parallel (current sharing mode) refer to the diagram of Fig. 2B.

5 cm

5 cm

5 cm

5 cm

CONNECTOR

Summary of Contents for SBC 1200 NRG+ FR

Page 1: ...High Quality Nautical Equipment SBC NRG HIGH POWER SBC 1100 NRG FR SBC 1200 NRG FR SBC 1450 NRG HR SBC 1950 NRG HR SBC 2450 NRG HR REV 000b...

Page 2: ...the batteries 1 sensor supplied more sensors optional INSTALLATION The installation of the battery charger must be carried out by qualified personnel BEFORE USING THE BATTERY CHARGER CAREFULLY READ T...

Page 3: ...950 NRG HR SBC 2450 NRG HR Battery voltage 12 V 24 V Battery capacity 360 600 Ah 450 1000 Ah 270 600 Ah 360 800 Ah 450 1000 Ah Minimum output cable size 25 mm2 35 mm2 25 mm2 35 mm2 35 mm2 Number of ba...

Page 4: ...re it is disconnected by bipolar switch Before connecting or disconnecting the DC wires from the battery charger s output terminals please ensure that the device is disconnected by means of bipolar sw...

Page 5: ...battery area whilst charging WARNING before connecting the batteries check the polarity of the cables from the battery Reversing the polarity could seriously damage the battery charger even if protec...

Page 6: ...ative terminal of the battery charger is to be connected to junction JCN junction JCN is to be connected to the negative terminal of the battery or group of batteries fig 2A The lengths of cables that...

Page 7: ...of problems is located Fig 4 CAN OUT 4 5 FIG 4 BATTERY 12V 24V KTBRJ TEMPERATURE SENSOR BATTERY SENSOR CONNECTOR BATTERY TYPE SELECTION Select the type of battery to be charged by turning the selecto...

Page 8: ...mode CAN IN CAN OUT 8 1 8 1 CAN IN CAN OUT 1 8 1 8 SBC NRG HI POWER SBC NRG HI POWER SBC NRG HI POWER SBC NRG HI POWER SBC NRG HI POWER RDS 1562 RDS 1562 TERMINATION CONNECTOR TERMINATION CONNECTOR TE...

Page 9: ...GREEN PULSE Active Stand by mode LED COLOUR DESCRIPTION OFF No problem FLASHING Problem with manual reset see code page errors table RED Problem with automatic reset fault see code page errors table...

Page 10: ...the device are present FLOAT phase maintenance The battery charger charges the batteries at constant FLOAT voltage when the current required is less than the transition threshold between ABSORTPTION a...

Page 11: ...orrect setting of the group and the priority of the battery chargers connected to the network by means of the RDS 1562 terminal optional 10 Internal temperature sensors fault Both internal temperature...

Page 12: ...as maximum value the 70 of the output maximum rated current thus reducing the current absorption from the AC mains The supply of the maximum output current will start again once the network voltage i...

Page 13: ...2 Vdc EL open 28 4 Vdc Li Ion 28 8 Vdc EL sealed Gel AGM 29 4 Vdc Optima Charge FLOAT voltage 13 4 Vdc EL open 13 5 Vdc Li Ion 13 6 Vdc AGM 13 8 Vdc EL sealed Gel Optima 26 8 Vdc EL open 27 Vdc Li Ion...

Page 14: ...DIMENSIONS mm inch 443 17 7 16 461 18 5 32 481 18 15 16 110 4 21 64 170 6 11 16 81 5 3 13 64...

Page 15: ...SBC NRG SERIES SBC NRG 12V SBC NRG 24V Learn more about GPS navigation on our website...

Reviews: