CHARGING CHARACTERISTICS

Charging procedure takes place in 3 phases:

BULK phase (constant current)

The batteries need more current than the battery charger can supply. Current is limited to the maximum rated output or 
to a lower value if factors which determine a power reduction of the device are present. The battery charger can enter 
this phase during start-up, when the batteries are low or when a high load is connected.

ABSORPTION phase (constant voltage)

The battery charger charges the batteries at a constant ABSORPTION voltage supplying the current needed when the 
current requested is greater than the transition threshold between ABSORPTION and FLOAT and less than the maximum 
output value or at a lower value if factors which determine a power reduction of the device are present.

FLOAT phase (maintenance)

The battery charger charges the batteries at constant FLOAT voltage when the current required is less than the transition 
threshold between ABSORTPTION and FLOAT. In this phase, as the batteries reach maximum capacity, they will tend to 
absorb increasingly low current. This float phase will allow the batteries to be on charge without risking overload.

(V)

V ABSORPTION *

(I)

IMAX**

ITH ABSORPTION-FLOAT***

BULK

ABSORPTION

FLOAT

NEW CYCLE

TIME

TIME

V FLOAT *

Depending on the type of charge selected.

**  In case the battery chargers are connected in parallel (current sharing mode) the IMAX value must be multiplied by 

the number of battery chargers (2 or 3).

***  In case the battery chargers are connected in parallel (current sharing mode) the ITH value must be multiplied by the 

number of battery chargers (2 or 3).

The factory setting of the transition threshold between ABSORPTION and FLOAT is equal to 20% of the maximum nominal 
value of the output current. 

Summary of Contents for SBC 1200 NRG+ FR

Page 1: ...High Quality Nautical Equipment SBC NRG HIGH POWER SBC 1100 NRG FR SBC 1200 NRG FR SBC 1450 NRG HR SBC 1950 NRG HR SBC 2450 NRG HR REV 000b...

Page 2: ...the batteries 1 sensor supplied more sensors optional INSTALLATION The installation of the battery charger must be carried out by qualified personnel BEFORE USING THE BATTERY CHARGER CAREFULLY READ T...

Page 3: ...950 NRG HR SBC 2450 NRG HR Battery voltage 12 V 24 V Battery capacity 360 600 Ah 450 1000 Ah 270 600 Ah 360 800 Ah 450 1000 Ah Minimum output cable size 25 mm2 35 mm2 25 mm2 35 mm2 35 mm2 Number of ba...

Page 4: ...re it is disconnected by bipolar switch Before connecting or disconnecting the DC wires from the battery charger s output terminals please ensure that the device is disconnected by means of bipolar sw...

Page 5: ...battery area whilst charging WARNING before connecting the batteries check the polarity of the cables from the battery Reversing the polarity could seriously damage the battery charger even if protec...

Page 6: ...ative terminal of the battery charger is to be connected to junction JCN junction JCN is to be connected to the negative terminal of the battery or group of batteries fig 2A The lengths of cables that...

Page 7: ...of problems is located Fig 4 CAN OUT 4 5 FIG 4 BATTERY 12V 24V KTBRJ TEMPERATURE SENSOR BATTERY SENSOR CONNECTOR BATTERY TYPE SELECTION Select the type of battery to be charged by turning the selecto...

Page 8: ...mode CAN IN CAN OUT 8 1 8 1 CAN IN CAN OUT 1 8 1 8 SBC NRG HI POWER SBC NRG HI POWER SBC NRG HI POWER SBC NRG HI POWER SBC NRG HI POWER RDS 1562 RDS 1562 TERMINATION CONNECTOR TERMINATION CONNECTOR TE...

Page 9: ...GREEN PULSE Active Stand by mode LED COLOUR DESCRIPTION OFF No problem FLASHING Problem with manual reset see code page errors table RED Problem with automatic reset fault see code page errors table...

Page 10: ...the device are present FLOAT phase maintenance The battery charger charges the batteries at constant FLOAT voltage when the current required is less than the transition threshold between ABSORTPTION a...

Page 11: ...orrect setting of the group and the priority of the battery chargers connected to the network by means of the RDS 1562 terminal optional 10 Internal temperature sensors fault Both internal temperature...

Page 12: ...as maximum value the 70 of the output maximum rated current thus reducing the current absorption from the AC mains The supply of the maximum output current will start again once the network voltage i...

Page 13: ...2 Vdc EL open 28 4 Vdc Li Ion 28 8 Vdc EL sealed Gel AGM 29 4 Vdc Optima Charge FLOAT voltage 13 4 Vdc EL open 13 5 Vdc Li Ion 13 6 Vdc AGM 13 8 Vdc EL sealed Gel Optima 26 8 Vdc EL open 27 Vdc Li Ion...

Page 14: ...DIMENSIONS mm inch 443 17 7 16 461 18 5 32 481 18 15 16 110 4 21 64 170 6 11 16 81 5 3 13 64...

Page 15: ...SBC NRG SERIES SBC NRG 12V SBC NRG 24V Learn more about GPS navigation on our website...

Reviews: