PROGRAMMING THE BATTERY CHARGER
BATTERY TYPE SELECTION
BATTERY TYPE
Open Liquid*
* Default value
Sealed Liquid
GEL
AGM
Exit
This function allows to choose the type of battery to charge, in order to optimize their charge.
In case of battery chargers connected in parallel (current sharing mode), the selected option must be the same in all
battery chargers.
CAN GROUP CONFIGURATION
CAN GROUP
Group A*
* Default value
Group B
Group C
Exit
This function allows to choose the network group the battery charger belongs to.
SBC 2450
NRG HR
(PRIORITY 2)
SBC 1200
NRG FR
GROUP A
GROUP B
GROUP U
RDS 1521
RDS 1560
RDS 1521
RDS 1560
INTERFACE
GSM
LCD
TERMINAL
Up to three battery chargers can be present in a group, as long as they are connected in parallel one to the other; oth-
erwise only one battery charger can be present in the group. The other devices making up a group can be terminals,
sensors or interfaces.
A diagram is given below showing an example of a possible network:
SECONDARY MENU
SBC 2450
NRG HR
(PRIORITY 1)
SBC 2450
NRG HR
(PRIORITY 3)
æ
B A T T E R Y T Y P e
P
O P E N L i q u i d
q
CAN NETWORK
ENTRY TO THE SECONDARY MENU
Once you select a function in the main menu through the pressure “ENTER” button you will enter the secondary menu.
The selected options are marked by the symbol “
㾎
“.
Use the keys
p
and
q
(UP and DOWN) to scroll the options inside the secondary menu and to position on the new
desired choice. .
Use the key “ENTER” to select the desired option (the
㾎
symbol will appear).
If “ENTER” is pressed on a selected option, the user exits the secondary menu.
Secondary menu entrance screenful:
1
nd
line: FUNCTION
2
nd
line: OPTION
The symbols
p
and
q
show the scrolling di-
rection (UP and DOWN) for the selection of the
options in the secondary menu.
UNITS IN PARALLEL
KTB4N
KTB4N