Quest Engineering 506 Installation, Operation And Maintenance Manual Download Page 6

1-877-420-1330

 

Quest 506 

Installation, Operation and Maintenance Instructions

6

www.QuestHydro.com

[email protected]

4.4 Hanging Diagram

 

  

Hanging installation must meet all state and local codes.
Installation should be done by a qualified agency in accordance with 

these instructions. The qualified service agency installing this high 

efficiency refrigeration system is responsible for the installation.
Check the supporting structure to be used to verify that it has sufficient 

load carrying capacity to support the weight of the unit. Suspend the 

unit only from the threaded nut retainers. Do NOT suspend from the 

cabinet. Recommended maximum hanger rod is 6 feet (1.8m)

1 - Check ball style trap

2 - 2 1/2” x 3/4” sch40 pvc pipe

1 - 5” x 3/4” sch40 pvc pipe

2 - 90° glue in elbow 3/4”

1 - Barb adapter

Parts Needed:  4 pieces 3/8” threaded rod 

 

4 - 3/8” threaded jam nuts

Instructions:  

Thread jam nut onto threaded rod 

 

Screw threaded rod into handles 

 

Tighten jam nuts to handle to prevent movement

Summary of Contents for 506

Page 1: ...nstallation Operation and Maintenance Instructions 4201 Lien Rd Madison WI 53704 Toll Free 1 877 420 1330 www QuestHydro com info QuestHydro com Read and Save These Instructions Specifications subject...

Page 2: ...tions 4 4 Installation 5 4 1 Location 5 4 2 Electrical Requirements 5 4 3 Condensate Removal 5 4 4 Hanging 6 5 Controls 7 5 1 Humidity Control 7 5 2 24VAC Wiring 7 5 2A Deh 3000R 8 5 2B Honeywell Remo...

Page 3: ...r table DO NOT place the device directly on structural members Provide vibration isolation in order to minimize operational vibration and or noise A drain pan MUST be placed under the unit if installe...

Page 4: ...and air infiltration problems should be addressed or noted in calculations 2 Registrations The Quest 506 Dehumidifier units conform to unified standard UL 60335 2 40 3 Specifications 80 F 60 RH Unit...

Page 5: ...conditions are listed on page 4 A ground fault interrupter protected circuit is required Install the remote control panel in a central area of the structure where it will sense the relative humidity...

Page 6: ...the installation Check the supporting structure to be used to verify that it has sufficient load carrying capacity to support the weight of the unit Suspend the unit only from the threaded nut retaine...

Page 7: ...nect before beginning installation 5 2 24VAC Wiring The terminal block circuit breaker and power switch are located on the intake side of the unit FLOAT External low voltage float switch Use a normall...

Page 8: ...t could become clogged and require disassembly to clean Filter non compliance invalidates the product warranty 24VAC COMP FAN HONEYWELL REMOTE HUMIDISTAT WIRING DIAGRAM QUEST DEH 3000R CONTROL WIRING...

Page 9: ...ar to an air conditioner s to remove heat and moisture from incoming air and add heat to the air that is discharged Hot high pressure refrigerant gas is routed from the compressor to the condenser coi...

Page 10: ...28 BLU WHT 19 BRN BRN 29 BLK GRN RH PROG AUX TEMP EVAP FLOAT THERMISTOR PROBE CONTROL BOARD SERIAL 3A BREAKER XFMR COM COM COMPRESSOR CONTACTOR CORD INPUT POWER BLU 6 GRN 4 YEL 5 RED 3 ORG 7 BLK 8 DE...

Page 11: ...04 COIL EVAP Item Part No Description 15 4037704 02 COIL CONDENSER 16 4037707 TXV 3 TON 17 4037708 FAN MOTORIZED IMPELLER 18 4037728 CORD 19 4038135 HANDLE POCKET 20 4038136 BEZEL HANDLE 21 4038178 WI...

Page 12: ...user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or i...

Reviews: