background image

 

                  

 

Qubino 

The

 INNOVATIVE 

and 

SMALLEST

       

                                                                               

 

 

Flush Heat & Cool Thermostat 

 

ORDERING CODE 

Z-WAVE FREQUENCY 

ZMNHKD1 

868,4 MHz 

ZMNHKD2 

921,4 MHz 

ZMNHKD3 

908,4 MHz 

ZMNHKD4 

869,0 MHz 

ZMNHKD5 

916,0 MHz 

ZMNHKD8 

865,2 MHz 

This  Z-Wave  module is used to regulate temperature  in 
heating and cooling mode. Module can be controlled either 
through Z-Wave network or through the wall switch.

 

The module is designed to be mounted inside a “flush 
mounting box” and is hidden behind a traditional wall switch. 
Module measures power consumption of connected device. 
It is designed to act as repeater in order to improve range 
and stability of Z-wave network.

                       

 

Supported switches 

Module supports 

mono-stable

 switches (push button) and 

bi-stable

 switches. The module is factory set to operate 

with bi-stable switches.  

Installation 

  To prevent electrical shock and/or equipment damage, 

disconnect electrical power at the main fuse or circuit 
breaker before installation or any servicing.  

  Make sure, that no voltage is present in the installation.  

  Prevent the disconnecting device from being switched on 

accidentally. 

  Connect the module according to electrical diagram.  

  Locate the antenna far from metal elements (as far as 

possible).  

  Do not shorten the antenna. 

Danger of electrocution!  

  Module installation requires a great degree of skill and 

may be performed only by a qualified and licensed 
electrician. 

  Even when the module is turned off, voltage may be 

present on its terminals. 

 

Note! 

Do not connect the module to loads exceeding 
recommended values. Connect the module only in 
accordance to  the below diagrams. Improper connections 
may be dangerous. 

Electrical installation must be protected by directly 
associated over current protection fuse 4A, gG or Time 
lag T, rated breaking capacity 1500A (ESKA 522.723) 
must be used according to wiring diagram to achieve 
appropriate overload protection of the module

. The fuse 

must be installed in fuse holder: Adels contact 503 Si / 1DS

 

Package contents: 

  Flush 

Heat & Cool 

Ther Temperature sensor 

Electrical diagram 230VAC

 

 
 
 

 
 
 
 
 
 
 
 
 

 
Notes for the diagram: 
N

 

Neutral lead

 

 

 

L

 

Live lead

 

 

 

Q1

 

Output for Heating valve

 

 

 

Q2

 

Output for Cooling valve

 

 

 

I2

 

Input for switch /push button or sensor*

 

 

 

I1

 

Input for switch /push button or sensor*

 

 

 

TS

 

Terminal for digital temperature sensor (only for 
Flush Heat & Cool thermostat module compatible 
digital temperature sensor).

 

 

 

*

For details please check parameters 11 and 12 

Electrical diagram 24VDC 

 

 
 
 
 
 

 
Notes for the diagram: 
N

 

+ VDC

 

 

 

L

 

- VDC

 

 

 

Q1

 

Output for Heating valve

 

 

 

Q2

 

Output for Cooling valve

 

 

 

I2

 

Input for switch /push button or sensor*

 

 

 

I1

 

Input for switch /push button or sensor*

 

 

 

TS

 

Terminal for digital temperature sensor (only for 
Flush Heat & Cool thermostat module compatible 
digital temperature sensor).

 

 

 

*For details please check parameters 11 and 12 

WARNING: Service button S 

must NOT be used

 when 

module is connected to 110-230V power supply. 
Durability of the device depends on applied load. For 
resistive load (light bulbs, etc.) and 4A current consumption 
of each individual electrical device, the durability exceeds 
70.000 switches of each individual electrical device.

 

Module Inclusion (Adding to Z-wave network) 

  Connect module to power supply (with  

temperature sensor connected), 

  auto-inclusion (works for about 5 seconds after 

connected to power supply) or 

  press push button I1 three times within 3s (3 times 

change switch state within 3 seconds) or 

  press service button 

S

  (only applicable for 24 V SELV 

supply voltage) for more than 2 second. 

NOTE1: For auto-inclusion procedure, first set main 
controller into inclusion mode and then connect module to 
power supply. 
NOTE2: When connecting temperature sensor to module 
that has already been included, you have to exclude 
module first. Switch off power supply, connect the sensor 

and re-include the module

.

 

Module Exclusion/Reset (Removing from Z-
Wave network) 

  Connect module to power supply  

  bring module within maximum 1 meter (3 feet) of the 

main controller, 

  enable add/remove mode on main controller, 

  press push button 

I1 

five times within 3s (5 times change 

switch state within 3 seconds) in the first 60 seconds 
after the module is connected to the power supply or 

  press service button 

S

  (only applicable for 24 V SELV 

supply voltage)  for more than 6 second. 

By this function all parameters of the module are set to 
default values and own ID is deleted. 
If push button I1 is pressed three times within 3s (or service 
button S is pressed more than 2 and less than 6 seconds) 
module is excluded, but configuration parameters are not 
set to default values.  

NOTE: If the module is included with parameters 100 or 
101 with value different to default and module reset is done, 
wait at least 30s before next inclusion.

 

Association 

Association enables Flush 

Heat & Cool 

thermostat module 

to transfer commands inside Z-Wave network directly 
(without main controller) to other Z-Wave modules. 

Associated Groups:

  

Group 1: Lifeline group (reserved for communication with 
the main controller), 1 node allowed. 
Group 2: basic on/off (triggered at change of the output Q1 
or Q2 state and reflecting its state) up to 16 nodes. 
Group 3: SENSOR_MULTILEVEL_GET (triggered once per 
minute if parameter 121 is not 0) up to 16 nodes. 
Group 4: basic on/off (triggered by Too high temperature 
limit, it send 0x00, triggered by To Low temperature, it send 
0xFF) up to 16 nodes. 
Group 5: THERMOSTAT_SETPOINT_GET (triggered once 
per minute if parameter 121 is not 0) up to 16 nodes. 
Group 6: basic on/off (trigged by change of I1 if window 
sensor functionality is selected by parameter no. 11) up to 
16 nodes.

 

Group 7: basic on/off (trigged by change of I2 if condense 
sensor functionality is selected by parameter no. 12) up to 
16 nodes.

 

Group 9: sensor multilevel report (trigged by change of 
temperature) up to 16 nodes. 

Configuration parameters 

Parameter no. 1 – Input I1 switch type 

Available config. parameters (data type is 1 Byte DEC): 

  default value 1 

  0 - mono-stable switch type (push button) 

  1 - bi-stable switch type  

Parameter no. 2 – Input I2 switch type 

See parameter 1 (valid for I2 instead of I1) 

Parameter no. 4 – Input 1 contact type 

Available config. parameters (data type is 1 Byte DEC): 

  default value 0 

  0 - NO (normally open) input type 

  1 - NC (normally close) input type 

NOTE:  This parameter has influence only when parameter 
no. 11 is set to the value “2”. After setting this parameter, 
switch the window sensor once, so that the module could 
determine the input state. 

Parameter no. 5 – Input 2 contact type 

See parameter 4 (valid for I2 instead of I1) 
NOTE:  This parameter has influence only when parameter 
no. 12 is set to the value “2000”. After setting this 
parameter, switch the condense sensor once, so that the 
module could determine the input state. 

Parameter no. 10 - Activate / deactivate functions ALL 
ON/ALL OFF 

Available config. parameters (data type is 2 Byte DEC): 

  default value 255 

  255 - ALL ON active, ALL OFF active. 

  0 - ALL ON is not active ALL OFF is not active 

  1 - ALL ON is not active ALL OFF active 

  2 - ALL ON active ALL OFF is not active 

Flush 

Heat & Cool 

thermostat module responds to 

commands ALL ON / ALL OFF that may be sent by the 
main controller or by other controller belonging to the 
system.  

Parameter no. 11- I1 Functionality selection 

Available config. parameters (data type is 2 Byte DEC): 

  default value 1 

  32767  –  input I1 doesn’t  influence on the Heat & Cool 

process 

  1 - input I1 changes the mode of the thermostat between 

Off and Auto. In this case function on window sensor is 
disabled 

  2  -  input I1 influences on cooling and heating valves 

according to status of window  sensor. In this case 
function of Off and Auto selection by I1 is disabled.

 

NOTE: If "Window Sensor" selected (value set to "2"), 
parameter 100 (enable/disable endpoint) must be set to 
non-zero value and module re-included! 

Parameter no. 12 – I2 Functionality selection 

Available config. parameters (data type is 2 Byte DEC): 

  default value 32767 

  32767  -  input I2 does not influence on the Heat & Cool 

process 

  From 0 to 990 -  Temperature set point from 0.0 °C to 

99.0 °C. When I2 is pressed, it automatically set Heat 
and Cool temperature setpoints  according to value 
defined here. In this case function of condense sensor is 
disabled  

  From 1001 to 1150 - Temperature set point from -0.1 °C 

to  -15.0 °C.  When I2 is pressed, it automatically set 
temperature setpoint according to value defined here. In 
this case function of condense sensor is disabled 

  2000 - Input I2 influences on the cooling valve according 

to status of condense sensor, In this case function of 
setpoint selection with I2 is disabled 

NOTE: If "Condense Sensor" selected (value set to "2000"), 
parameter 101 (enable/disable endpoint) must be set to 
non-zero value and module re-included! 

Parameter no. 40 – Power reporting in Watts on power 
change 

Set value means percentage, set value from 0 - 100=0% - 
100%. Available configuration parameters (data type is 1 
Byte DEC):  

  default value 0 

  0 - reporting disabled 

  1-100 = 1%-100% Reporting enabled. Power report is 

send (push) only when actual power in Watts in real time 
changes for more than set percentage comparing to 
previous actual power in Watts, step is 1%. 

NOTE

:

 If power changed is less than 1W, the report is not 

send (pushed), independent of percentage set. 

Parameter no. 42 – Power reporting in Watts by time 
interval 

Set value means time interval (0 – 32767) in seconds, 
when power report is send. Available config. parameters 
(data type is 2 Byte DEC): 

  default value 0 (power report is disabled) 

  0 - reporting disabled 

  1  -  32767  = 1 second -  32767  seconds. Reporting 

enabled. Power report is send with time interval set by 
entered value.  

Parameter no. 43 – Hysteresis

 

Heating

 

On 

This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
heating on. Available configuration parameters (data type is 
2 Byte DEC):  

  default value 1010 (-1.0 °C) 

  0 - 255  =  0,0°C to 25,5 °C   

  1001 - 1255  =  - 0,1°C to - 25,5 °C 

Parameter no. 44 - Hysteresis

 

Heating

 

Off 

This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
heating off. Available configuration parameters (data type is 
2 Byte DEC):  

  default value 2 (+0.2 °C) 

  0 - 255  =  0,0°C to 25,5 °C   

  1001 - 1255  =  - 0,1°C to - 25,5 °C 

Parameter no. 45 – Hysteresis Cooling

 

On 

This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
cooling on. Available configuration parameters (data type is 
2 Byte DEC):  

  default value 5 (+0.5 °C) 

  0 - 255  =  0,0°C to 25,5 °C   

  1001 - 1255  =  - 0,1°C to - 25,5 °C 

Parameter no. 46 – Hysteresis Cooling Off 

This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
cooling off. Available configuration parameters (data type is 
2 Byte DEC):  

   default value 1002 (-0.2 °C) 

  0 - 255  =  0,0°C to 25,5 °C   

  1001 - 1255  =  - 0,1°C to - 25,5 °C 

Parameter no. 47 – 

Antifreeze

 

Set value means at which temperature the device will be 
turned on even if the thermostat was manually set to off. 
Available config. parameters (data type is 2 Byte DEC):  

  default value 50 (5,0 °C) 

  0 - 127  =  0,0°C  to 12,7 °C   

  1001 - 1127  =  - 0,1°C to - 12,7 °C 

  255 - Antifreeze functionality disabled 

NOTE: Antifreeze is activated only in heating mode. It uses 
a hysteresis determined in parameters no. 43 and 44. 

Parameter no. 60 – Too low temperature limit 

Available config. parameters (data type is 2 Byte DEC): 

  default value 50 (too low temperature limit is 5.0°C) 

  1 - 1000 = 0.1°C - 100.0°C, step is 0.1°C.  

  1001 – 1150 = - 0.1°C to -15.0°C 

NOTE:  Too  low  temperature limit is used  with Association 
Group 4. 

Parameter no. 61 – Too high temperature limit 

Available config. parameters (data type is 2 Byte DEC): 

  default value 700 (too high temperature limit is 70.0°C) 

  1  -  1000 = 0.1°C -  100.0°C, step is 0.1°C. Too high 

temperature limit is used with Association Group 4. 

Parameter no. 64 – Output Switch selection Q1 

Set value means the type of the device that is connected to 
the Q1 output. The device type can be normally open (NO) 
or normally close (NC).  
Available config. parameters (data type is 1 Byte DEC): 

  default value 0  

  0 - When system is turned off the output is 0 V. 

  1 - When system is turned off the output is 230 V. 

Parameter no. 65 – Output Switch selection Q2 

Set value means the type of the device that is connected to 
the Q2 output. The device type can be normally open (NO) 
or normally close (NC).  
Available config. parameters (data type is 1 Byte DEC): 

  default value 0  

  0 - When system is turned off the output is 0 V. 

  1 - When system is turned off the output is 230 V. 

Parameter no. 70 – Input 1 status on delay  

Available config. parameters (data type is 2 Byte DEC): 

  default value 0 

  1 - 32000 seconds 

If the value of parameter is different to 0, means that the 
Influence of this input to heating or cooling will react after 
inserted time. This parameter has influence only when the 

S

 

Service button (used to add 
or remove  module from the 
Z-Wave network in case of

 

24 V SELV power supply)

.

 