Release Notes

Document 6-00016-32 Rev A

September 2007

Known Issues

5

Known Issues    

0

This release of Scalar 10K firmware has the following known issues. This list contains 

cumulative information for the previously released versions.

Change 

Request 

Number

Service 

Request 

Number

Description

Workaround

33359

282830

On occasion, the vertical mounting 

of a 3590 tape drive might be higher 

than the vertical window expected 

by the library firmware to 

successfully scan for the drive 

fiducial. As a result, the library 

cannot teach the drive.

Manually adjust the vertical 

placement of the 3590 tape drive or 

the front bezel until the library can 

successfully teach the drive.

40518

When a Teach Current operation is 

performed for a DM, a drive teach 

failure can return an incorrect bay 

number to the Operator Panel.

Physically inspect the drive bay that 

the failure indicated or possibly the 

bay that is located immediately 

before. The bay that is identified by 

the failure might not exist.

41203

When using a data tape instead of a 

FUP tape to update a list of drives, 

the library correctly posts a “BAD 

FIRMWARE MEDIA” operator 

intervention message, but continues 

to the next drive in the list. The 

operation should fail and not 

continue.

No applicable workaround is 

available.

41301

After cleaning cartridges are ejected 

from drives, the View dialog (

Main 

MenuSetupCleaningView

continues to indicate a Valid status 

for the first cleaning cartridge rather 

than clearing the status.

Make sure that cleaning cartridges 

are inserted into the library by using 

the Insert Clean Tape command 

(

Main MenuCommands Insert/

EjectInsert Clean Tape

). This 

operation physically inserts the 

cartridges and also inserts them into 

the library database.
NOTE: Do not use 

Main Menu 

SetupCleaningMedia

 to perform 

this operation. This operation inserts 

the cartridges into the library 

database only.

Summary of Contents for Scalar 10K

Page 1: ...his Release 1 New Features and Enhancements 2 Compatibility Matrix 2 Resolved Issues 3 Known Issues 5 Documentation 6 Contacting Quantum 7 Purpose of This Release 0 The Scalar 10K 320 release includes...

Page 2: ...wing table for information on drive and auxiliary firmware compatibility with the 320 release of Scalar 10K 320A 00004 This information is current as of this product release For the most up to date in...

Page 3: ...r Description Version 320A 00004 1588 Aux trace screen shows tower numbers in hex 1589 Need change to display location of print log port 1727 Inserting AIT 3 tapes always causes retries Handling too h...

Page 4: ...e truncated by 1 character on the operator panel 3038 527016 E_LSC_WFSCRDBF_BAD_READBUFFER_HANDLE is reported with RMU 192 and 304 Library firmware 3041 622572 If a LTO barcode label is printed in the...

Page 5: ...e drive bay that the failure indicated or possibly the bay that is located immediately before The bay that is identified by the failure might not exist 41203 When using a data tape instead of a FUP ta...

Page 6: ...n MenuCommands Insert EjectInsert Clean Tape This operation physically inserts the cartridges and also inserts them into the library database NOTE Do not use Main Menu SetupCleaningMedia to perform th...

Page 7: ...nformation including answers to frequently asked questions FAQs You can also access software firmware and drivers through this site For further assistance or if training is desired contact Quantum For...

Reviews: