TESTING and MAINTENANCE

NOTE: Emergency lighting systems should be tested in 
accordance with NFPA 101 or as often as local codes 
require, to ascertain that all components are operational.

NOTE:  Allow batteries to charge for 24 hours before initial 
testing.

Manual testing:

If the batteries are sufficiently charged, either press and release 
the “TEST” button or use the ELA LRT (remote tester accessory 
for SDRT units only) on the bottom of the unit to activate a 30-
second test, during which the lamps will turn on. After a unit’s 
first 30-second test is complete, a test in progress may be 
cancelled at any time by pressing and releasing the “TEST” 
button again.

Self-Diagnostics (SDRT feature)

Units with this option automatically perform a 5-minute self-
diagnostic test of the charging electronics, battery, and lamps 
every 30 days, and a 90-minute test every year, indicating 
system status as shown in the table at right. First self test 
occurs after 15 days of continuous AC Power.

Postponing a self-test:

If an automatic self-test occurs at a time when it is not desirable 
for the unit lamps to be on, it can be postponed for 8 hours 
either by pressing and releasing the “TEST” button or by using 
ELA LRT (remote tester accessory).

Cancelling emergency operation:

Press and hold the “TEST” button for several seconds or 
activate using the ELA LRT (remote tester accessory), during 
which the status indicator will flash until the lamps turn off. This 
restores the AC Reset state in which the unit is shipped.

Load-Learning feature:

Self-Diagnostic units automatically ‘learn’ their total connected 
lamp load during the first scheduled self-test (~15 days). The 
load-learning function can also be initiated manually by 
pressing and holding the “TEST” button for 7 seconds (count 
flashes), during this period the lamps will turn on. After 7 
seconds, release the button, the lamps will turn off within 2 
seconds indicating load learn complete. If lamps stay on longer, 
load learn was not successful. This manual load-learning 
feature should be initiated whenever the total connected lamp 
load of the unit is changed, or a lamp is replaced.

NOTE:

Manual load-learning functions cannot be initiated if 

there is inadequate charge in the batteries. If this is so, wait 
until the unit indicates full battery charge (solid green status 
indication) before initiating the manual load-learning function.

Clearing a failure indication:

After a failure condition has been corrected and power is 
restored to the unit, clear the failure indication either by 
pressing the “TEST” button once or by activating remote Test 
option once.

Unit Status Indications

The “TEST” button illuminates to indicate the following conditions:

Indication:

Status:

Off

Unit is off

Flashing green

Unit is in Emergency operation or Test

Solid amber

Battery is charging

Solid green

Battery is fully charged

Flashing R / G

Manual test, battery not fully charged 

(SDRT 

only)

1x red flashing

Battery failure 

(SDRT only)

2x red flashing

Lamp failure 

(SDRT only)

3x red flashing

Charger / electronics failure 

(SDRT only)

Flashing R/Amber Unable to charge

Solid Red

Battery is disconnected

Remote Test (SDRT): 

(ELA LRT sold separately)

Units with the self-diagnostics/remote test feature allows 
manual test activation using a laser pointer. Aim the laser 
beam straight onto the circular area labeled near the “TEST” 
button for a few moments to activate a 30-second test. (See 
also “Manual testing”) A test in progress may be cancelled by 
aiming the beam at the test area again. 

NOTE: 

The remote 

tester should not be used to initiate the Load Learning feature.

IMPORTANT BATTERY INFORMATION:

Batteries are perishable items. For best results, it is 
recommended that the batteries receive an initial charge within 
the first six months of the manufacture date of the fixture. The 
manufacture date can be found on the outside of the unit 
packaging and on the product label as part of the Date Code / 
Series. The first two digits in the date code represent the year 
and the second two digits represent the month. In many cases, 
batteries beyond the initial charge recommendation time frame 
will recover if fully charged soon after installation. If such a 
battery does not recover after a full initial charge, it should be 
replaced.

SDRT: aim laser pointer here

TEST” button

Summary of Contents for ELM2LF

Page 1: ...abrasions when removing from carton handling installing and maintaining this product WARNING The battery used in this device may present a risk of fire or chemical burn if mistreated Do not disassemble heat above 70 C 158 F or incinerate Replace battery only as directed on the battery label and page 5 of these instructions Use of unauthorized battery voids warranty and UL listing of this product a...

Page 2: ...mp Wires If no remote lamps are connected remote lamp leads and low voltage DC should be left capped and dressed in mounting plate as shown Taking care not to pinch wires or connectors dressed inside junction box secure mounting plate to junction box screws NOTE To ensure proper engagement of the mounting plate latches to the housing DO NOT OVER TIGHTEN THE SCREWS At upper center of the mounting p...

Page 3: ...ect the polarized battery plug to the charger board Make certain that the battery cable is routed to avoid interference with the AC input connector or other components Federal Communications Commission FCC Requirements This device complies with Part 15 of the FCC Rules This device may not cause harmful interference battery connector Battery Lamp Lamp Status Indicator LED Remote test Option standar...

Page 4: ...henever the total connected lamp load of the unit is changed or a lamp is replaced NOTE Manual load learning functions cannot be initiated if there is inadequate charge in the batteries If this is so wait until the unit indicates full battery charge solid green status indication before initiating the manual load learning function Clearing a failure indication After a failure condition has been cor...

Page 5: ...essing the assembly toward the inside of the unit Gently bend the snap at each side of the bracket to release the lamp assembly Cut wires near lamp board and strip back 1 4in Connect stripped wires to the replacement lamp following the yellow blue polarity as marked Secure the new lamp assembly onto the lamp bracket and re assemble it into the housing routing the lamp wires to avoid damage by othe...

Page 6: ...Part 912 00026 001 Rev C 1 15 2018 Acuity Brands Lighting Inc 2018 All Rights Reserved LIFE SAFETY SOLUTIONS TEL 800 334 8694 www lithonia com ...

Page 7: ...ararlo ADVERTENCIA La batería utilizada en este dispositivo puede presentar un riesgo de incendio o quemadura química si no se utiliza correctamente No desmontar calentar a más de 70 C 158 F o incinerar Cambie la batería solo como se indica en la etiqueta de la batería y en la página 5 de estas instrucciones El uso de una batería no autorizada anula la garantía y la certificación UL de este produc...

Page 8: ...os y colocados dentro de la placa de montaje como se muestra Teniendo cuidado de no presionar los cables o conductores organizados dentro de la caja de unión fije la placa de montaje a los tornillos de la caja de unión NOTA Para asegurar que los pestillos de la placa de montaje estén correctamente enganchados a la carcasa NO AJUSTE DEMASIADO LOS TORNILLOS En la parte superior del centro de la plac...

Page 9: ...atería polarizado a la placa del cargador Asegúrese de verificar el recorrido del cable para evitar interferencias con el conector de entrada de CA o con otros componentes Requisitos de la Comisión Federal de Comunicaciones FCC Este dispositivo cumple con la Parte 15 de las reglas de la FCC Este dispositivo puede no ocasionar interferencias perjudiciales conector de la batería Batería Lámpara Lámp...

Page 10: ... la lámpara conectada esté totalmente cargada o que una lámpara sea reemplazada NOTA Las funciones de aprendizaje de carga manuales no pueden iniciarse si las baterías no tienen carga suficiente Si esto es así espere hasta que la unidad indique que la batería ha sido totalmente cargada indicador de estado verde fijo antes de iniciar la función de aprendizaje de carga manual Aclaración de indicacio...

Page 11: ... la lámpara y tira hacia atrás 1 4in Conecte los cables pelados a la lámpara de reemplazo siguiendo la polaridad amarilla azul marcada Sujete el nuevo el ensamblaje de la lámpara al soporte de la lámpara y vuelva a montarlo en la carcasa y direccione correctamente los cables de la lámpara para evitar daños de otros componentes Vuelva a ensamblar la unidad consulte también el paso 5 en la página 3 ...

Page 12: ...N º de pieza 912 00026 001 Rev C 1 15 2018 Acuity Brands Lighting Inc 2018 Todos los derechos reservados SOLUCIONES DE SEGURIDAD PERSONAL TELÉFONO 800 334 8694 www lithonia com ...

Reviews: