Chapter 3: FRU Removal and Replacement Procedures
Replacing Node Power Supplies
Quantum DXi6900 G2 Field Service Manual
81
Figure 42:
Removing and Installing a Node Power Supply
1
2
3
4
5
Item
Description
1
Release latch
2
Cable connector
3
Power Supply
4
Connector
5
Handle
Installing a Replacement Power Supply in the Node
To install the replacement power supply in the DXi6900 G2 Node:
1. Slide the replacement power supply into the chassis until the power supply is fully seated and the
release latch snaps into place (see
).
2. Connect the power cable to the power supply and plug the cable into a power outlet.
3. Secure the power cable with the strap.
Allow several seconds for the system to recognize the power supply and determine its status. The power
supply status indicator turns green to signify that the power supply is functioning properly.
4. In the remote management console, delete any administrative alerts and close any service tickets.