Chapter 3: FRU Removal and Replacement Procedures
Replacing Node Power Supplies
Quantum DXi6900 G2 Field Service Manual
82
l
Replacing a Node Cooling Fan below
Obtaining a Replacement Node Cooling Fan
Before beginning the replacement procedure, make sure that you have the required replacement kit. The
appropriate replacement cooling fan will be provided by Quantum Customer Support (see
).
You will need the following items to perform this procedure:
l
Replacement cooling fan kit provided by Quantum Customer Support.
l
ESD grounding wrist strap (included in the replacement kit)
Figure 43:
DXi6900 G2 Node Cooling Fan
Illustration
Description
Replacement cooling fan
Replacing a Node Cooling Fan
This section describes how to remove and replace a cooling fan in the DXi6900 G2 Node. If a cooling fan
fails, you will be notified by an admin alert in the remote management console.
Caution:
Use appropriate ESD precautions, including the use of a grounding strap, when performing
this procedure.
Removing and replacing a cooling fan in the Node includes the following steps:
l
Identifying a Failed Cooling Fan in the Node below
l
Removing a Failed Cooling Fan from the Node on the next page
l
Installing a Replacement Cooling Fan in the Node on page 84
Identifying a Failed Cooling Fan in the Node
The DXi6900 G2 Node contains six cooling fans that provide cooling for the processors, expansion cards,
and memory modules.
To identify the failed cooling fan:
1. Access the remote management console (see
).
2. Navigate to the
Status > Hardware > Details > System Board
page.