ActiveScale™ OS X100 Rackless Installation Guide
252
20.5.2 3-phase delta, 208V, 48A, NA
Table 20
-
40. Input power configuration
Number PDUs required by system including redundancy 2 each
Input configuration:
Three-phase delta
Nominal input voltage (line-to-line):
208VAC
Input voltage operating range:
180VAC-220VAC
Nominal frequency:
60Hz
Table 20
-
41. Input current/power
Input current, steady state available:
48A, North American de-rated
Input current, peak available:
60A
Input power available:
17.3KW
Table 20
-
42. Input connector and wiring
Input wire connections:
3P+PE (3-poles plus protective Earth), 4-wire
Input plug compliant to:
IEC 60309-1, IEC-60309-2
Input plug color code:
Blue (rated operating voltage of 200 to 250)
Input plug ground socket position:
3 hour position, mates with female in 9 hour position.
Input cord wire gauge:
6 AWG or equivalent
Table 20
-
43. Output voltage
Nominal:
208VAC, balanced
Operating range:
180VAC-220VAC, balanced
Table 20
-
44. Branch circuit characteristics
Number of branches:
6
Total available steady state current (per branch):
13.9A, North American de-rated
Short term peak (per branch):
17.3A
Table 20
-
45. Output connector ratings
C13 steady state current:
12A, North America de-rated
C13 short term peak current:
15A
C19 steady state current:
16A, North America de-rated
C19 short term peak current:
20A
Table 20
-
46. Dimensions and weights
Width
2.2 in. / 55 mm
Summary of Contents for ActiveScale X100
Page 28: ...ActiveScale OS X100 Rackless Installation Guide 28...
Page 34: ...ActiveScale OS X100 Rackless Installation Guide 34...
Page 59: ...ActiveScale OS X100 Rackless Installation Guide 59 Figure 3 14 Installing the I O module...
Page 68: ...ActiveScale OS X100 Rackless Installation Guide 68...
Page 76: ...ActiveScale OS X100 Rackless Installation Guide 76...
Page 91: ...ActiveScale OS X100 Rackless Installation Guide 91 Figure 6 36 Cabling Storage Node 4...
Page 92: ...ActiveScale OS X100 Rackless Installation Guide 92 Figure 6 37 Cabling Storage Node 5...
Page 94: ...ActiveScale OS X100 Rackless Installation Guide 94 Figure 6 39 Cabling System Node 1...
Page 95: ...ActiveScale OS X100 Rackless Installation Guide 95 Figure 6 40 Cabling System Node 2...
Page 98: ...ActiveScale OS X100 Rackless Installation Guide 98...
Page 108: ...ActiveScale OS X100 Rackless Installation Guide 108...
Page 110: ...ActiveScale OS X100 Rackless Installation Guide 110...
Page 127: ...ActiveScale OS X100 Rackless Installation Guide 127 Figure 10 19 Post Login Storage Policy...
Page 155: ...ActiveScale OS X100 Rackless Installation Guide 155 Figure 10 47 Post Login Durability Policy...
Page 162: ...ActiveScale OS X100 Rackless Installation Guide 162...
Page 234: ...ActiveScale OS X100 Rackless Installation Guide 234...
Page 238: ...ActiveScale OS X100 Rackless Installation Guide 238...
Page 240: ...ActiveScale OS X100 Rackless Installation Guide 240...
Page 244: ...ActiveScale OS X100 Rackless Installation Guide 244...
Page 260: ...ActiveScale OS X100 Rackless Installation Guide 260...
Page 264: ...ActiveScale OS X100 Rackless Installation Guide 264...