activated and the error code E05 will be displayed. When the compressor temperature drops below
70
℃
(2
nd
Level L70), and the compressor has not been in operation for at least 10 min (1
st
Level
d10), the compressor will be reactivated.
As the compressor temperature goes above 105
℃
, the compressor will be de activate and the error
code E06 will be displayed. A manual reset is required.
When the current draw is greater than the present value and lasts for 6 seconds, the compressor is
de activated and the error code E04 will be displayed, 10 minutes later the compressor will be re
activated. If the overload occurs again the system is de activated and the error cod E06 will be
displayed. A manual reset will be required or the power to the unit can be switched off and then on
again to reset the system.
10f: Adjusting
To enter any menu, press the
SET
button to select the item to be adjusted. Press Up and Down to
do the adjustment. After finishing the adjustment, press the
SET
button again to confirm. The
screen flashes once to indicate the adjustment has been updated successfully. Press the
SET
button
again to enter the next menu or return.
10f.1: Time Controller
A time control function heat pump water heater can also be supplied by QUANTUM ENERGY
TECHNOLOGIES Pty Ltd.
Fig 5. Picture of time controller
Set: Confirm Key Con: Administrator menu key
Up: Adjustment key Down: Adjustment key
Menu
Function
Range
Default
On01
Power on, time 1
00:00
~
23:59
~
CLOS
CLOS
OFF1
Power off, time 1
00:00
~
23:59
~
CLOS
CLOS
On02
Power on, time 2
00:00
~
23:59
~
CLOS
CLOS
OFF2
Power off, time 2
00:00
~
23:59
~
CLOS
CLOS
On03
Power on, time 3
00:00
~
23:59
~
CLOS
CLOS
OFF3
Power off, time 3
00:00
~
23:59
~
CLOS
CLOS
Notes:
1. CLOS: time is invalid.
2. The method of operation for “SET” “UP” “DOWN” keys can refer to 10a item.
3. In the adjustment process, press the “CON” key can return to the menu item without changing the current time
settings.
4. Clock change: Press "SET+CON" key for 3 seconds to change the system time.
5. Within four hours of the initial power-on, the system is always working. It is not limited by the on/off time.
Four hours later, the system performs start and stop logic by the on/off time.