Table 1:
Electrical cable connections
Model
Max.
FLA
(A)
Voltage
(V)
MCA
(A)
Max. dual
elem.
fuse/CB
(Max OP,
A)
Screw/nut
Recommended conductor size
Phase,
recommended
torque
PE,
recommended
torque
Phase
(AWG)
Number of
conductors
per phase
PE
(AWG)
Number
of PE
conductors
0035PJS 84
460
92
110
M8, 15N.M
M8, 18N.M
2
1
6
1
0070PJS 151
159
175
M10, 38N.M
M10, 25N.M
2/0
2
0105PJS 262
270
300
1/0
2
4
2
0140PJS 328
336
350
3/0
1/0
0035PJP 75
83
110
M8, 15N.M
M8, 18N.M
2
1
6
1
0070PJP 142
149
175
M10, 38N.M
M10, 25N.M
2/0
2
0105PJP 230
238
250
1/0
2
4
2
0140PJP 296
304
300
3/0
1/0
Notes
:
• The hydraulic kit is considered in the data of this table.
• The maximum distance is calculated taking the cable diameters shown in this table. For longer lengths, and for cables laying with other
cables, the minimum cable diameter must be recalculated to a higher value to allow for any electromagnetic or harmonic effects.
Refer to the dimensions of any power cable connectors to ensure the correct fitting to the specified
power cables and circuit breaker. Due to the high risk of electrical shock and in compliance with
electrical regulations, cable and power terminals must be protected. Any accessories to adapt allow-
able cable connections can be sourced at he relevant manufacturer's site. The number of options
are too numerous to list here.
Hydro kits,
SPC breakers, and 575 V panel breaker are from Siemens, 460 V control panel breakers
are from Schneider Electric.