Setting the date and time
1. In access level O, press
HMI
in the menu and se-
lect
Date Time Setpoint
.
2. Set the date and time and press
Confirm
.
Setting a schedule
1. In access level O or S, press
Schedule
in the
menu.
2. Press the
+
icon to add a new item.
3.
Configure the settings using the icons on the right.
• Press the - icon to delete an item.
See the following figure for an example of the screen.
Figure 9:
Setting a schedule
Setting the water temperature control using
entering water temperature (EWT) or leaving water
temperature (LWT)
1. In access level O, press
System Setpoints
in the
menu.
2. Select
Cooling/Heating Control Select
.
Setting a setpoint
1. In access level O, press
System Setpoints
in the
menu.
2.
Configure the target liquid temperature setpoints
in
Cool/Heat EWT Setpoint
or
Cool/Heat LWT
Setpoint
.
3. Set according to cooling/heating control selection.
• For setpoint temperature less than 40°F
(4.4°C), see
.
Setpoint temperature less than 41ºF (5ºC)
:
To work with setpoints between 40ºF (4.4ºC) and 14ºF
(-10ºC), use glycol liquid with the correct concentra-
tion in the water system and configure the micro DIP
switches SW302-3 and SW302-4 on the control board
in the control panel to glycol mode. See
for more details. If you need year-round
cooling in low ambient temperature less than 41℉
(5℃), Quantech suggests using glycol liquid.
Figure 10:
Setpoint temperatures less than 41ºF (5ºC)
Condition
SW302-3
SW302-4
Note
Glycol
Off
Off
–
Standard
Off
On
Default
48ºC
COOLING MODE
-10ºC 4.4ºC 20ºC
Leaving water cooled temperature
Ambient temperatur
e
-20ºC