Section 4 - Installation
Quantech
63
Form QTC4-NM2
Issue date: 05/12/2023
4
Table 7 -
EBM condenser fans, dual point electrical lug data
Field wiring lugs
EBM condenser fans
Terminal block
Circuit breaker
Non-fused
disconnect switch
QTC4 model
Evap.
Input V
Input
freq.
Wires
per
phase
Lug wire
range
Wires
per
phase
Lug wire
range
Wires
per
phase
Lug wire
range
0495
2605
200
60
–
–
–
–
–
–
230
60
–
–
–
–
–
–
380
60
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
400
60
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
400
50
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
460
60
2
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
575
60
2
#2 – 600
kcmil
2
#1 ~ 500
kcmil
2
#1 ~ 500
kcmil
0395
2205/2605
200
60
–
–
–
–
–
–
230
60
–
–
–
–
–
–
380
60
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
400
60
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
400
50
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
460
60
2
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
575
60
2
#2 – 600
kcmil
2
#1 ~ 500
kcmil
2
#1 ~ 500
kcmil
0450
2605
200
60
–
–
–
–
–
–
230
60
–
–
–
–
–
–
380
60
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
400
60
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
400
50
3
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
460
60
2
#2 – 600
kcmil
3
3/0 ~ 400
kcmil
3
3/0 ~ 400
kcmil
575
60
2
#2 – 600
kcmil
2
#1 ~ 500
kcmil
2
#1 ~ 500
kcmil
Summary of Contents for QTC40160
Page 22: ...Quantech 22 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 94: ...Quantech 94 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...