FORM QCC3-EG1 (517)
QUANTECH
17
Selection Data (Cont'd)
TABLE 4 -
REFRIGERANT LINE CONNECTIONS
MODEL
NUMBER
QCC3
TONS
SYSTEM
NUMBER
REFRIGERANT LINE
CONNECTION
SUCTION LINE
LIQUID LINE
COPPER
TYPE L
INCHES OD
VELOCITY
@ NOMINAL
CAPACITY
IN FPM
NOMINAL
TONS
UNLOADED
COPPER
TYPE L
INCHES OD
SUCTION
LIQUID
080CZE
81.3
1
2.7
1.1
2-5/8
1656
13.5
1-1/8
2
2.7
1.1
2-5/8
1656
3.5
1-1/8
085CZE
84.3
1
2.7
1.1
2-5/8
1818
14.9
1-1/8
2
2.7
1.1
2-5/8
1572
13.2
1-1/8
090CZE
91.1
1
2.7
1.1
2-5/8
1812
14.9
1-1/8
2
2.7
1.1
2-5/8
1896
14.9
1-1/8
100CYE
98.5
1
2.7
1.1
2-5/8
1896
14.9
1-1/8
2
2.7
1.1
2-5/8
1896
14.9
1-1/8
110CYE
111.5
1
2.7
1.1
2-5/8
1812
14.9
1-1/8
2
2.7
1.1
2-5/8
2598
33.6
1-1/8
130CZE
131.5
1
2.7
1.1
2-5/8
2658
32.8
1-1/8
2
2.7
1.1
2-5/8
2658
32.8
1-1/8
145CZE
145.3
1
3.1
1.4
3-1/8
2790
31.3
1-3/8
2
2.7
1.1
2-5/8
1926
14.9
1-1/8
160CZE
158.3
1
3.1
1.4
3-1/8
2658
30.7
1-3/8
2
2.7
1.1
2-5/8
2556
33.1
1-1/8
1. Based on R-410A at the nominal capacity of the unit or system, an ambient temperature of 95°F (35°C) and a suction temperature of 45°F
(7.2°C).
2. Suction line sizes were calculated based on a nominal maximum pressure drop to 3 PSI/100 ft. (20.7 kPa/30.5 m). When calculating suc-
tion line pressure drop for a specific application, it should be noted that system capacity decreases as suction line pressure drop increases.
3. Nominal Tons (KW) Unloaded is based on one compressor (per system) operating at design conditions.
4. Based on minimum compressor staging for the given pipe size, a double suction riser should be used to ensure proper oil return to the
compressor on all vertical suction risers. Oil returning up the riser moves up the inner surface of the pipe and depends on the mass velocity
of the refrigerant vapor at the wall surface to move the oil up the vertical rise.
5.
Hot gas bypass lines are typically 7/8” for lines up to 40 feet and 1-1/8” for lines over 40 feet in length (12 meters). The field connections siz
-
es are 7/8” for the optional factory mounted hot gas bypass valve. Note: Hot gas bypass is only available for refrigerant system number 1.
6. For more information, please refer to either the YORK DX Piping Guide (Form 050.40-ES2) or the ASHRAE Refrigertion Handbook.
Refrigerant Piping Notes
Summary of Contents for QCC3
Page 4: ...QUANTECH FORM QCC3 EG1 517 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 39: ...FORM QCC3 EG1 517 QUANTECH 39 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...QUANTECH FORM QCC3 EG1 517 40 Electrical Drawings LD22075a...
Page 41: ...FORM QCC3 EG1 517 QUANTECH 41 Electrical Drawings Cont d 035 21583 101 REV O LD22075b...
Page 42: ...QUANTECH FORM QCC3 EG1 517 42 Electrical Drawings Cont d LD22195a...
Page 43: ...FORM QCC3 EG1 517 QUANTECH 43 Electrical Drawings Cont d LD22195b 035 21583 114 REV J...