2

INTRODUCTION

QUANICS

TM

  

is committed to becoming the best water solutions problem solver in the world. We prom-

ise to provide complete engineered water solutions using the latest technology and best products. We 

will provide the best technical assistance and customer service available and we will always deliver 

more than we promise.

In our quest to serve our market, we do not view a technology as the one and only option, but rather 

look to develop a wide variety of technologies that the engineer and/or end user can tailor to their 

individual application. Along this line, we are proud to introduce two NSF Certified treatment systems, 

SCAT

®

 AeroCell

®

 and SCAT Bio-COIR

®

Both systems operate as fixed-film media filters to treat wastewater. The patented SCAT delivery system 

is the same for each system only the media is different. Each media type has its own unique properties 

and both have been tested and listed under NSF International Standard 40 Class 1 requirements. Both 

systems have also been demonstrated to significantly reduce total nitrogen. The following manual will 

explain the differences and similarities of each system.  Before reading this manual determine which sys-

tem you are currently utilizing by examining the data plate attached to the system lid.  Each system will 
be identified by name “AeroCell” or “Bio-COIR

.

This manual covers the following model numbers.

AeroCell Model #’s

Bio-COIR Model #’s

ATS-SCAT-8-AC-C500

ATS-SCAT-8-BC-C500

ATS-SCAT-86-AC-C750

ATS-SCAT-86-BC-C750

ATS-SCAT-88-AC-C1000

ATS-SCAT-88-BC-C1000

ATS-SCAT-886-AC-C1250

ATS-SCAT-886-BC-C1250

ATS-SCAT-888-AC-C1500

ATS-SCAT-888-BC-C1500

We are eager to assist you with any questions or problems. Please contact QUANICS at 1-877-QUANICS 
to request assistance.
PROCESS DESCRIPTION
The QUANICS AeroCell & Bio-COIR are individual wastewater treatment systems utilizing fixed film 

media. The module(s) consist of a fiberglass tank(s) containing a pre-determined amount of media. Ef-

fluent is sprayed over the media utilizing specialized spay nozzles. This patented delivery system evenly 

distributes wastewater to achieve the desired treatment levels.

The AeroCell utilizes open cell foam media. The foam has a high porosity, large surface area and ease 

of microbial attachment that allows for loading rates up to ten times that of sand. Open cell foam has 

a fifteen year track record of treating wastewater to the highest quality treatment levels. The application 

rates for the AeroCell system have been carefully selected to provide optimal treatment and performance 

in a long lasting media.

The Bio-COIR utilizes a patent pending Bio-COIR media for treatment.  The Bio-COIR media is com-

posed of fibers that constitutes the thick mesocarp, or husk, of the coconut fruit. The long fibers are used 

for ropes, door mats etc, leaving pith tissue and short to medium length fibers as a waste which has ac-

cumulated in heaps in many third world countries.  The short to medium length Bio-COIR fibers used in 

Bio-COIR are a lingocellulosic material. The high lignin content of these fibers results in a more durable 

material than other natural medias. The high lignin content of 45.84% also results in a slower degrada-

tion of the media and assures that excellent water/air ratio is maintained over a longer period of time.

In both AeroCell & Bio-COIR systems, pretreatment of the wastewater occurs through the use of a septic 

tank equipped with a QUANICS A300 series effluent filter on the outlet. The pretreated wastewater then 

moves into a dosing tank where an effluent pump doses the wastewater to the treatment module(s). The 

dosing of effluent occurs in short frequent doses over a 24-hour period utilizing a timed dosed control 

panel. Effluent is sprayed over the media through the use of specially designed helical spray nozzles that 

provide uniform distribution of the effluent over the entire surface area.

Summary of Contents for AeroCell ATS-SCAT-86-AC-C750

Page 1: ...ESTWOOD KY 40014 FAX 502 992 8249 www quanics net CLASS I NSF STD 40 WASTEWATER TREATMENT SYSTEM OPERATION MAINTENANCE MANUAL MANUFACTURED PRODUCTS BY QUANICSTM FIXED FILM MEDIA WASTEWATER TREATMENT SYSTEMS Revised August 2007 E n g i n e e r i n g Water S o l u t i o n s ...

Page 2: ...ic Tank 3 Section 2 0 A300 8 Series Effluent Filter 3 Section 3 0 Dosing Tank 4 Section 4 0 Filtered Pump Vault 4 Section 5 0 Controls Pumps Floats 4 Section 6 0 Treatment Module 4 Section 7 0 Recirculation Device 5 TROUBLESHOOTING GUIDE 5 6 SAFETY 6 DRAWINGS TECHNICAL DATA 7 19 WIRING SCHEMATICS 20 21 DATA PLATES 21 ...

Page 3: ...ms utilizing fixed film media The module s consist of a fiberglass tank s containing a pre determined amount of media Ef fluent is sprayed over the media utilizing specialized spay nozzles This patented delivery system evenly distributes wastewater to achieve the desired treatment levels The AeroCell utilizes open cell foam media The foam has a high porosity large surface area and ease of microbia...

Page 4: ...nable float is down the pump will need to be activated manually by switching the HOA switch in the control panel to HAND 6 While the pump is running observe the spray nozzles in the treatment module for flow and pressure 7 While the pump is running observe the recirculation device for proper flow 8 Once the current operating condition of the system is established turn the HOA switch to the OFF pos...

Page 5: ...ned 2 Remove the filter panel Rinse the filter plates with fresh water making sure all septage is rinsed back into the tank The filter plates should be cleaned until all slots are open and free of de bris 3 Replace the filter panel and remove the white maintenance plate Repeat steps 1 and 2 for the second filter panel Section 5 0 Controls Pump Floats 1 Inspect the floats for proper placement and m...

Page 6: ...located at the proper level When the ball float is at its lowest position it should be located equal to or just above the on position of the timer enable float figure 1 2 Check that the design recirculation rates are maintained by observing the discharge through all five out falls of the recirculation assembly Adjust as needed by loosening the quick disconnects and leveling TROUBLESHOOTING GUIDE T...

Page 7: ...ridge has been removed b Check the septic tank to see if it appears normal If not check with the PROPERTY OWNER to determine what inappropriate materials might have been added to the waste stream 3 Recirculation device is not splitting properly a Check the out falls for clogging b Check the device for level 4 Control panel malfunction a Check all fuses and breakers b Check originating power source...

Page 8: ...sory personnel Follow these safety precautions when performing any excavation or construction work Follow all construction safety procedures during installation Follow electrical safety procedures during installation Fill all holes and depressions in and around the installation area remove and dispose of all debris from installation TECHNICAL DATA DRAWINGS INDEX ATS SCAT 8 AC C500 8 PDS ED 1 5 16 ...

Page 9: ...uanics net autocad htm 750 GPD AeroCell System www quanics net autocad htm The septic tank shall have a minimum L W ratio of equal to or greater than one The septic tank shall have a minimum L W ratio of equal to or greater than one ...

Page 10: ...uanics net autocad htm 1250 GPD AeroCell System www quanics net autocad htm The septic tank shall have a minimum L W ratio of equal to or greater than one The septic tank shall have a minimum L W ratio of equal to or greater than one ...

Page 11: ...nics net autocad htm The septic tank shall have a minimum L W ratio of equal to or greater than one The septic tank shall have a minimum L W ratio of equal to or greater than one 500 gallons per day 85ft3 of Bio COIR media 5 88 gpd ft3 hydraulic loading rate Four 120 degrees spray nozzles ...

Page 12: ...L W ratio of equal to or greater than one The septic tank shall have a minimum L W ratio of equal to or greater than one 750 gallons per day 138ft3 of Bio COIR media 5 88 gpd ft3 hydraulic loading rate Eight 120 degrees spray nozzles 1000 gallons per day 170ft3 of Bio COIR media 5 88 gpd ft3 hydraulic loading rate Eight 120 degrees spray nozzles ...

Page 13: ... W ratio of equal to or greater than one The septic tank shall have a minimum L W ratio of equal to or greater than one 1250 gallons per day 223ft3 of Bio COIR media 5 88 gpd ft3 hydraulic loading rate Twelve 120 degrees spray nozzles 1500 gallons per day 255ft3 of Bio COIR media 5 88 gpd ft3 hydraulic loading rate Twelve 120 degrees spray nozzles ...

Page 14: ...AT 886 BC C1250 1250 12 3 223 5 61 2500 1250 76 8 15 3 81 ATS SCAT 888 AC C1500 ATS SCAT 888 BC C1500 1500 12 3 255 5 88 3000 1500 76 8 15 3 98 The Zabel A300 8x18 VC model effluent filter is used in systems of 1200 gpd or less The A300 8x26 VC filter is used in systems up to 1800 gpd The septic tank shall have a minimum L W ratio of equal to or greater than one Features Effluent discharge and car...

Page 15: ...on Outlet hub accepts 4 or 6 SCH 40 outlet pipe All Zabel Filters accept SmartFilter alarm switch GPD Maximum Gallons Per Day FS Filtration Size Warranty for Defects in Material and Workmanship Effluent Filters Limited Lifetime FILTERED PUMP VAULT Hanging FPV H44 4 FPV H56 4 High density non corrosive polyethylene plastic with stainless steel screws Features Hanging filtered pump vault installs in...

Page 16: ... 3M 300 V SJOW jacketed 2 wire with ground Materials of Construction 300 grade stainless and cast iron Discharge 1 1 2 Warranty for Defects in Material and Workmanship All components 3 Years STEP SYSTEMS Effluent Discharges PDS ED 1 5 Materials Pipe 1 5 or 2 SCH 40 PVC 1 5 or 2 PVC flex tubing True Union Ball Valve PVC Plastic Double block full port design 1 5 or 2 slip slip hubs Fittings SCH 40 P...

Page 17: ...Years PDS GT 2 0 STEP SYSTEMS Float Tree AC FT 3 Materials Pipe 1 5 or 2 SCH 40 PVC 1 5 or 2 PVC flex tubing True Union Ball Valve PVC Plastic Double block full port design 1 5 or 2 slip slip hubs Fittings SCH 40 PVC threaded slip adapter SCH 40 PVC slip slip adapter Warranty for Defects in Material and Workmanship All components 2 Years ...

Page 18: ... electrical lines HOA Switch for manual pump control mounted on cir cuit board Float Switch Terminal Block Alarm and Control Fuses Programmable Timer with separate variable controls al lows for setting the on and off times from 05 seconds to 30 hours Circuit Breaker provides pump disconnect and branch circuit protection Power Supply Pump 120 208 240V 7 15FLA Alarm 120V Standard Alarm Package Red A...

Page 19: ...charge Assembly 2 Years Float Valve Assembly 2 Years ATS GRD 100 80 20 N Materials Risers and Lids High density non corrosive polyethyl ene plastic Stainless steel screws Neoprene gasket IMPORTANT When adding risers together for deeper installations QUANICS does not recommend exceeding a maximum depth of 48 Neoprene gaskets must be installed as per instructions To prevent unauthorized entry instal...

Page 20: ...19 Wiring Schematics ...

Page 21: ...20 Consecutively Serial Numbered Data Plates Maintenance Sticker ...

Page 22: ...TY OWNER Responsibilities The PROPERTY OWNER confirms that he has read and understands the AeroCell Bio COIR Operation Manual and agrees to operate the QUANICS AeroCell Bio COIR Advanced Treatment System in accordance with QUANICS s oper ating instructions Failure to use the system in accordance with the Operation Manual will void all warranties All repairs required to restore the system to normal...

Page 23: ...om the date of installation pumps for a period of three years from the date of installation and AeroCell Bio COIR foam for a period of ten years from the date of installation Failed warranted parts shall be prorated over the period of use with cost calculated at the list price at the time of failure Discontinued parts will be replaced with the closest current QUANICS equivalent In no event shall Q...

Page 24: ...OX 1520 PHONE 502 992 8200 6244 OLD LAGRANGE ROAD 1 877 QUANICS CRESTWOOD KY 40014 FAX 502 992 8249 www quanics net Treatment system service provider 082707 326 E n g i n e e r i n g Water S o l u t i o n s ...

Reviews: