R
September 3, 2009
7050-128B
Page 15
Santa Fe Pellet Stove
We recommend a minimum of 60 inches (1.5m)
vertical, however above the eave is preferred.
Both installations are approved for mobile home
installations. Must use 3 or 4 inch (76 to 102mm)
“L” or “PL” Listed pellet venting or Listed double
wall pipe and Quadra-Fire Outside Air Kit in mobile
homes. Single wall pipe is approved for residential
installations only.
Air Clearance to Pipe
:
This appliance was tested with standard 3 inch
(76mm) Listed pellet clearance pipe to combus-
tibles.
Pellet pipe manufactures Listed reduce clearance
pipe may be use for reduce clearance from 3 inch
(76mm) air clearance to no less than 1 inch (25mm)
air clearance to combustibles for approved Listed
pellet pipe.
Follow stove pipe manufactures listed air clearances
to combustibles and installation instructions for all
reduced air clearances installations.
C. Vertical into Existing Class A Chimney
D. Through The Wall & Vertical - External
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Minimum.
Non-combustible Hearth Pad
3 in. (76mm) Minimum.
Cleanout Cover
24 in. (610mm) Minimum
Ceiling Support
6 in. (152mm) Flue
Connector
6 in. (152mm) Class A
Chimney Connector
Adapter
3 in. to 6 in.
(76-152mm)
Top Vent Kit
Non-combustible Hearth Pad
Clean-out Cover
Tee
Wall Thimble
Support
Bracket
every 60 in.
(1.5m)
24 in.
(610mm)
Minimum
Rain Cap
Flashing
2 in. (51mm) minimum
6 in. (152mm)
Minimum
Figure 15.1
Figure 15.2
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
3 in. (76mm) Min.
12 in.
(305mm)
Minimum
3 in. to 3 in.
(76-76mm)
Top Vent Kit
Clean-out Cover
on other side
E. Vertical - Interior - Typical Installation