R
May 12, 2014
7050-128G
Page 11
Santa Fe Pellet Stove
*L Exception for Horizontal Installations:
USA INSTALLATIONS
:
The non-combustible fl oor protector
must be 1/2 inch (13mm) minimum thickness, “k” value = 0.49.
Floor protection requires Type II thermal protection R = 1.0 or
greater.
A non-combustible fl oor protection extending beneath the
fl ue pipe is recommended with horizontal venting or under
the top vent adapter with vertical installation.
Figure 10.2.
CANADA INSTALLATIONS
: A non-combustible fl oor pro-
tection extending beneath the fl ue pipe is
required
with
horizontal venting or under the top vent adapter with vertical
installation.
Must extend 2 inches (51mm) beyond each
side of pipe (shaded area)
C. Hearth Pad Requirements (UL and ULC)
Use a non-combustible fl oor protector, extending beneath
appliance and to the front, sides and rear as indicated.
Measure front distance “M” from the surface of the glass
door.
Hearth Pad Requirements
Inches
K
Sides
6
L*
Back
2
M
Front
6
L*
K
K
M
Figure 11.2
Figure 11.1
Hearth Pad Requirements
Millimeters
K
Sides
203
L*
Back
51
M
Front
457
USA Hearth Pad Requirements
Canada Hearth Pad Requirements